Запасные части Pepperl+Fuchs
Каталожный номер: 906238
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | NPN |
| Rated operating distance | 1.5 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.215 mm |
| Actuating element | Ferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.6 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 80 Hz |
| Hysteresis | 5 ... 15 typ. 10 % |
| Reverse polarity protection | yes |
| Short-circuit protection | yes |
| Voltage drop | &le 2 V |
| Operating current | &le 100 mA |
| Current consumption | &le 15 mA |
| Off-state current | &le 10 µA |
| Indicators/operating means |
|---|
| Operation indicator | LED red: output |
| Standard conformity |
|---|
| Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M8 x 1 , 3-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 8 mm |
| Degree of protection | IP67 |
Каталожный номер: 904077
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 1.5 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.215 mm |
| Actuating element | Ferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.6 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 80 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | yes |
| Short-circuit protection | yes |
| Voltage drop | &le 2 V |
| Operating current | &le 100 mA |
| Current consumption | &le 15 mA |
| Off-state current | &le 10 µA |
| Indicators/operating means |
|---|
| Operation indicator | LED red: output |
| Standard conformity |
|---|
| Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 8 mm |
| Degree of protection | IP67 |
Каталожный номер: 904075
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 1.5 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.215 mm |
| Actuating element | Ferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.6 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 80 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | yes |
| Short-circuit protection | yes |
| Voltage drop | &le 2 V |
| Operating current | &le 100 mA |
| Current consumption | &le 15 mA |
| Off-state current | &le 10 µA |
| Indicators/operating means |
|---|
| Operation indicator | LED red: output |
| Standard conformity |
|---|
| Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M8 x 1 , 3-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 8 mm |
| Degree of protection | IP67 |
Каталожный номер: 288267
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 10 mm |
| Installation | flush in mild steel |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.5 (0.9 of material thickness 2 mm) |
| Reduction factor rSt37 | 1 |
| Output type | 3-wire |
| Nominal ratings |
|---|
| Installation conditions | |
| A | 0 mm |
| B | 16 mm |
| C | 30 mm |
| F | 60 mm |
| Operating voltage | 10 ... 30 V |
| Switching frequency | 0 ... 300 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | yes |
| Short-circuit protection | yes |
| Voltage drop | &le 2 V |
| Operating current | 0 ... 200 mA |
| Off-state current | &le 0.1 mA |
| No-load supply current | &le 10 mA |
| Switching state indicator | LED, yellow |
| Limit data |
|---|
| Operating pressure statically | 60 bar (870.2 psi) max. |
| Functional safety related parameters |
|---|
| MTTFd | 375 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | cable TPE-S , 2 m   3 x 0.34 mm2 |
| Housing material | Stainless steel 1.4435 / AISI 316L |
| Sensing face | Stainless steel 1.4435 / AISI 316L |
| Degree of protection | IP68 / IP69K |
| Mass | 112 g |
Каталожный номер: 288265
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 10 mm |
| Installation | flush in mild steel |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.5 (0.9 of material thickness 2 mm) |
| Reduction factor rSt37 | 1 |
| Output type | 3-wire |
| Nominal ratings |
|---|
| Installation conditions | |
| A | 0 mm |
| B | 16 mm |
| C | 30 mm |
| F | 60 mm |
| Operating voltage | 10 ... 30 V |
| Switching frequency | 0 ... 300 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | yes |
| Short-circuit protection | yes |
| Voltage drop | &le 2 V |
| Operating current | 0 ... 200 mA |
| Off-state current | &le 0.1 mA |
| No-load supply current | &le 10 mA |
| Switching state indicator | LED, yellow |
| Limit data |
|---|
| Operating pressure statically | 60 bar (870.2 psi) max. |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4435 / AISI 316L |
| Sensing face | Stainless steel 1.4435 / AISI 316L |
| Degree of protection | IP68 / IP69K |
| Mass | 24 g |
Каталожный номер: 911280
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | NPN |
| Rated operating distance | 10 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Output type | 3-wire |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 0 ... 240 Hz |
| Hysteresis | 3 ... 15 typ. 10 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V |
| Operating current | &le 200 mA |
| Off-state current | 10 µA |
| No-load supply current | &le 10 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 2 m |
| Core cross-section | 0.5 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 18 mm |
| Degree of protection | IP69K |
Каталожный номер: 913387
| General specifications |
|---|
| Rated operating distance | 10 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Output type | 3-wire |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 0 ... 240 Hz |
| Hysteresis | 3 ... 15 typ. 10 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V |
| Operating current | &le 200 mA |
| Off-state current | 10 µA |
| No-load supply current | &le 10 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 5 m |
| Core cross-section | 0.5 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 18 mm |
| Degree of protection | IP67 |
Каталожный номер: 913763
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 10 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.8 |
| Reduction factor rSt37 | 1 |
| Reduction factor rBrass | 0 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Operating voltage | 6 ... 30 V DC |
| Switching frequency | 1 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | yes |
| Voltage drop | < 3 V DC |
| Operating current | 2 ... 100 mA |
| Off-state current | < 400 µA |
| Switching state indicator | LED, red |
| Mag. Field strength, AC fields | 250 mT |
| Mag. Field strength, DC fields | 250 mT |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | 300 mm POC cable with 3-pin , M12 x 1 connector |
| Core cross-section | 0.34 mm2 |
| Housing material | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Sensing face | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 18 mm |
| Degree of protection | IP67 |
Каталожный номер: 913764
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 10 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.8 |
| Reduction factor rSt37 | 1 |
| Reduction factor rBrass | 0 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Operating voltage | 6 ... 30 V DC |
| Switching frequency | 1 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | yes |
| Voltage drop | < 3 V DC |
| Operating current | 2 ... 100 mA |
| Off-state current | < 400 µA |
| Switching state indicator | LED, red |
| Mag. Field strength, AC fields | 250 mT |
| Mag. Field strength, DC fields | 250 mT |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | 300 mm POC cable with 3-pin , M12 x 1 connector |
| Core cross-section | 0.34 mm2 |
| Housing material | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Sensing face | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 18 mm |
| Degree of protection | IP67 |
Каталожный номер: 911276
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | NPN |
| Rated operating distance | 10 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 0 ... 240 Hz |
| Hysteresis | 3 ... 15 typ. 10 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V |
| Operating current | &le 200 mA |
| Off-state current | 10 µA |
| No-load supply current | &le 10 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 18 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Каталожный номер: 911270
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 10 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Output type | 3-wire |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 0 ... 5 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V |
| Operating current | 0 ... 200 mA |
| Current consumption | &le 10 mA |
| Off-state current | &le 10 µA |
| No-load supply current | &le 15 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | Multihole-LED, yellow |
| Mag. Field strength, AC fields | 250 mT |
| Mag. Field strength, DC fields | 250 mT |
| Functional safety related parameters |
|---|
| MTTFd | 906 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Sensing face | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 18 mm |
| Degree of protection | IP67 |
Каталожный номер: 913605
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 10 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 1 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V |
| Operating current | 0 ... 200 mA |
| Current consumption | &le 10 mA |
| Off-state current | &le 10 µA |
| No-load supply current | &le 15 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | Multihole-LED, yellow |
| Mag. Field strength, AC fields | 250 mT |
| Mag. Field strength, DC fields | 250 mT |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Sensing face | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 18 mm |
| Degree of protection | IP67 |
Каталожный номер: 911285
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | PNP |
| Rated operating distance | 10 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 0 ... 240 Hz |
| Hysteresis | 3 ... 15 typ. 10 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V |
| Operating current | &le 200 mA |
| Off-state current | 10 µA |
| No-load supply current | &le 10 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 880 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 18 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Каталожный номер: 912736
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 10 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 6 ... 30 V DC |
| Switching frequency | 200 Hz |
| Hysteresis | 5 ... 15 typ. 10 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | < 3 V |
| Operating current | 2 ... 200 mA |
| Off-state current | &le 400 µA |
| Operating voltage indicator | |
| Switching state indicator | LED, yellow |
| Standard conformity |
|---|
| Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 18 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Каталожный номер: 912735
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 10 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 6 ... 30 V DC |
| Switching frequency | 200 Hz |
| Hysteresis | 5 ... 15 typ. 10 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | < 3 V |
| Operating current | 2 ... 200 mA |
| Off-state current | &le 400 µA |
| Operating voltage indicator | |
| Switching state indicator | LED, yellow |
| Standard conformity |
|---|
| Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 18 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Каталожный номер: 911272
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 10 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 240 Hz |
| Hysteresis | 3 ... 15 typ. 10 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V |
| Operating current | &le 200 mA |
| Off-state current | 10 µA |
| No-load supply current | &le 10 mA |
| Indicators/operating means |
|---|
| Operation indicator | Dual LED Green: power Yellow: output |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector 7/8"-16 UN , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 18 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Каталожный номер: 94803
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 10 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actuating element | Nonferrous targets |
| Reduction factor rAl | 1 |
| Reduction factor rCu | 1.1 |
| Reduction factor r304 | 0 |
| Reduction factor rSt37 | 0 |
| Reduction factor rBrass | 0.9 |
| Nominal ratings |
|---|
| Operating voltage | 6 ... 30 V |
| Switching frequency | 5 Hz |
| Hysteresis | 3 ... 15 typ. 10 % |
| Reverse polarity protection | yes |
| Short-circuit protection | no |
| Voltage drop | &le 5.5 V |
| Operating current | 2 ... 100 mA |
| Off-state current | &le 1 mA |
| Indicators/operating means |
|---|
| Operation indicator | 4-way LED Yellow: output |
| Standard conformity |
|---|
| Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Mechanical specifications |
|---|
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 30 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Каталожный номер: 911282
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | NPN |
| Rated operating distance | 15 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 12.15 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.2 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 0 ... 150 Hz |
| Hysteresis | 3 ... 15 typ. 10 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V |
| Operating current | &le 200 mA |
| Off-state current | &le 10 µA |
| No-load supply current | &le 10 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 2 m |
| Core cross-section | 0.5 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 30 mm |
| Degree of protection | IP69K |
Каталожный номер: 913767
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 15 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 12.15 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.8 |
| Reduction factor rSt37 | 1 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Operating voltage | 6 ... 30 V DC |
| Switching frequency | 1 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | yes |
| Voltage drop | < 3 V DC |
| Operating current | 2 ... 100 mA |
| Off-state current | < 400 µA |
| Switching state indicator | LED, red |
| Mag. Field strength, AC fields | 250 mT |
| Mag. Field strength, DC fields | 250 mT |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | 0 ... 70 °C (32 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | 300 mm POC cable with 3-pin , M12 x 1 connector |
| Housing material | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Sensing face | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 30 mm |
| Degree of protection | IP67 / according to cable specification |
Каталожный номер: 913768
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 15 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 12.15 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.8 |
| Reduction factor rSt37 | 1 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Operating voltage | 6 ... 30 V DC |
| Switching frequency | 1 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | yes |
| Voltage drop | < 3 V DC |
| Operating current | 2 ... 100 mA |
| Off-state current | < 400 µA |
| Switching state indicator | LED, red |
| Mag. Field strength, AC fields | 250 mT |
| Mag. Field strength, DC fields | 250 mT |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | 0 ... 70 °C (32 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | 300 mm POC cable with 3-pin , M12 x 1 connector |
| Housing material | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Sensing face | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 30 mm |
| Degree of protection | IP67 / according to cable specification |
Каталожный номер: 911277
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | NPN |
| Rated operating distance | 15 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 12.15 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.2 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 0 ... 150 Hz |
| Hysteresis | 3 ... 15 typ. 10 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V |
| Operating current | &le 200 mA |
| Off-state current | &le 10 µA |
| No-load supply current | &le 15 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 30 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Каталожный номер: 911273
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 15 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 12.15 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.2 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 0 ... 5 Hz |
| Hysteresis | 3 ... 15 typ. 10 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V |
| Operating current | &le 200 mA |
| Current consumption | &le 10 mA |
| Off-state current | &le 10 µA |
| No-load supply current | &le 15 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | Multihole-LED, yellow |
| Mag. Field strength, AC fields | 250 mT |
| Mag. Field strength, DC fields | 250 mT |
| Functional safety related parameters |
|---|
| MTTFd | 884 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Sensing face | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 30 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Каталожный номер: 913606
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 15 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 12.15 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.2 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 1 Hz |
| Hysteresis | 3 ... 15 typ. 10 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V |
| Operating current | &le 200 mA |
| Current consumption | &le 10 mA |
| Off-state current | &le 10 µA |
| No-load supply current | &le 15 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | Multihole-LED, yellow |
| Mag. Field strength, AC fields | 250 mT |
| Mag. Field strength, DC fields | 250 mT |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Sensing face | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 30 mm |
| Degree of protection | IP67 |
Каталожный номер: 912738
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 15 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 12.15 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.2 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 6 ... 30 V |
| Switching frequency | 150 Hz |
| Hysteresis | 5 ... 15 typ. 10 % |
| Reverse polarity protection | yes |
| Short-circuit protection | yes |
| Voltage drop | < 3 V DC |
| Operating current | 2 ... 100 mA |
| Off-state current | < 400 µA |
| Functional safety related parameters |
|---|
| MTTFd | 970 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Indicators/operating means |
|---|
| Operation indicator | 4-way LED Yellow: output |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | 0 ... 70 °C (32 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | M12 connector, 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 30 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Каталожный номер: 912737
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 15 mm |
| Installation | flush (Requirements: see drawing below) |
| Output polarity | DC |
| Assured operating distance | 0 ... 12.15 mm |
| Actuating element | Ferrous and nonferrous targets |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.2 |
| Reduction factor r304 | 0.85 |
| Reduction factor rSt37 | 1 |
| Nominal ratings |
|---|
| Operating voltage | 6 ... 30 V |
| Switching frequency | 150 Hz |
| Hysteresis | 5 ... 15 typ. 10 % |
| Reverse polarity protection | yes |
| Short-circuit protection | yes |
| Voltage drop | < 3 V DC |
| Operating current | 2 ... 100 mA |
| Off-state current | < 400 µA |
| Functional safety related parameters |
|---|
| MTTFd | 970 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Indicators/operating means |
|---|
| Operation indicator | 4-way LED Yellow: output |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | 0 ... 70 °C (32 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | M12 connector, 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 30 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Каталожный номер: 905495
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 2 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.62 mm |
| Actuating element | Ferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.6 - 0.8 |
| Reduction factor rSt37 | 1 |
| Reduction factor rBrass | 0 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Operating voltage | 6 ... 30 V DC |
| Switching frequency | 0 ... 5 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | no |
| Voltage drop | &le 5.5 V DC |
| Operating current | 2 ... 100 mA |
| Off-state current | &le 800 µA |
| Switching state indicator | LED, red |
| Mag. Field strength, AC fields | 250 mT |
| Mag. Field strength, DC fields | 250 mT |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | 300 mm POC cable with 3-pin , M12 x 1 connector |
| Core cross-section | 0.34 mm2 |
| Housing material | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Sensing face | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 12 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Каталожный номер: 905037
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 2 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.62 mm |
| Actuating element | Ferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.6 - 0.8 |
| Reduction factor rSt37 | 1 |
| Reduction factor rBrass | 0 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Operating voltage | 6 ... 30 V DC |
| Switching frequency | 0 ... 5 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | no |
| Voltage drop | &le 5.5 V DC |
| Operating current | 2 ... 100 mA |
| Off-state current | &le 800 µA |
| Switching state indicator | LED, red |
| Mag. Field strength, AC fields | 250 mT |
| Mag. Field strength, DC fields | 250 mT |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | 300 mm POC cable with 3-pin , M12 x 1 connector |
| Core cross-section | 0.34 mm2 |
| Housing material | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Sensing face | Xylan coated - Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 12 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Каталожный номер: 908427
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | NPN |
| Rated operating distance | 2 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.62 mm |
| Actuating element | Ferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.6 - 0.8 |
| Reduction factor r316Ti | 0.1 |
| Reduction factor rSt37 | 1 |
| Reduction factor rBrass | 0 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 100 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V DC |
| Operating current | &le 200 mA |
| Current consumption | < 14 mA |
| Off-state current | &le 10 µA |
| Functional safety related parameters |
|---|
| MTTFd | 990 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Indicators/operating means |
|---|
| Operation indicator | Dual LED Green: power Yellow: output |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | 2 m PUR cable |
| Core cross-section | 0.34 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 12 mm |
| Degree of protection | IP69K |
Каталожный номер: 908430
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 2 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.62 mm |
| Actuating element | Ferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.2 |
| Reduction factor r316Ti | 0 |
| Reduction factor rSt37 | 1 |
| Reduction factor rBrass | 0 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 100 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V DC |
| Operating current | &le 200 mA |
| Current consumption | < 14 mA |
| Off-state current | &le 10 µA |
| Functional safety related parameters |
|---|
| MTTFd | 990 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Indicators/operating means |
|---|
| Operation indicator | Dual LED Green: power Yellow: output |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | 2 m PUR cable |
| Core cross-section | 0.34 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 12 mm |
| Degree of protection | IP69K |
Каталожный номер: 908426
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | NPN |
| Rated operating distance | 2 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.62 mm |
| Actuating element | Ferrous targets |
| Reduction factor rAl | 0 |
| Reduction factor rCu | 0 |
| Reduction factor r304 | 0.6 - 0.8 |
| Reduction factor r316Ti | 0.1 |
| Reduction factor rSt37 | 1 |
| Reduction factor rBrass | 0 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V DC |
| Switching frequency | 100 Hz |
| Hysteresis | 3 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2 V DC |
| Operating current | &le 200 mA |
| Current consumption | < 14 mA |
| Off-state current | &le 10 µA |
| Functional safety related parameters |
|---|
| MTTFd | 990 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Indicators/operating means |
|---|
| Operation indicator | 4-way dual LED Green: power Yellow: output |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | V1 connector (M12 x 1), 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | Stainless steel 1.4305 / AISI 303 |
| Housing diameter | 12 mm |
| Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
Pepperl+Fuchs — ориентир в промышленной автоматизации и взрывозащите
Pepperl+Fuchs — немецкий бренд с более чем 75-летней историей инженерного превосходства. Основанная в 1945 году в Мангейме, компания стала пионером бесконтактных датчиков и одним из мировых лидеров в области intrinsically safe решений для опасных сред. Сегодня Pepperl+Fuchs объединяет два направления — Factory Automation и Process Automation — предлагая датчики, интерфейсную электронику, системы взрывозащиты и HMI, которые повышают надежность, безопасность и эффективность производственных процессов.
Ключевые преимущества Pepperl+Fuchs
- Инженерное качество: стабильные измерения, высокая повторяемость и минимальные ошибки в жестких условиях эксплуатации.
- Безопасность и соответствие: решения с сертификатами ATEX, IECEx, UL и соответствием SIL/PL для критически важных применений.
- Готовность к IIoT: поддержка IO-Link, AS-Interface, промышленного Ethernet и современных протоколов для прозрачности данных и предиктивного обслуживания.
- Устойчивость к среде: широкий температурный диапазон, стойкость к вибрациям, влаге, пыли и химическим воздействиям (включая IP-защиту).
- Совместимость и интеграция: бесшовная работа с ведущими ПЛК и системами управления, унифицированные интерфейсы и аксессуары.
- Глобальная поддержка: доступность документации, сервисной сети и запасных частей для надежной долгосрочной эксплуатации.
Продуктовые направления
- Датчики и системы распознавания: индуктивные, емкостные, магнитные, ультразвуковые и фотоэлектрические датчики; датчики расстояния, уплотнения контуров и позиционирования; энкодеры, 2D-ридеры и сканеры кода, RFID (HF/UHF), а также интеллектуальные решения с IO-Link. Для задач объемного контроля — лидарные сенсоры и визион-системы.
- Интерфейсная техника и искробезопасность: гальванические изоляторы и барьеры (K-System, H-System, Zener), модули ввода/вывода, защита от перенапряжений, источники питания и диагностика шины FieldConnex для Foundation Fieldbus и PROFIBUS PA.
- Оборудование для взрывоопасных зон: корпуса и клеммные коробки Ex e/Ex d из нержавеющей стали, алюминия и GRP; станции управления; системы продувки и наддува Bebco EPS; HMI и операторские панели для зон 1/21 и 2/22; мобильные устройства ecom для безопасной работы на площадках.
- Связь и подключение: мастера и хабы IO-Link, компоненты AS-Interface, распределительные блоки, коннекторы и кабельная арматура для быстрого и чистого монтажа.
- Функциональная безопасность: датчики и модули с подтвержденными уровнями SIL/PL, включая решения AS-i Safety at Work для защиты персонала и оборудования.
Области применения
Решения Pepperl+Fuchs используются в автомобильной промышленности, машиностроении, пищевой и фармацевтической отраслях, логистике и складской автоматизации, а также в нефтегазовом, химическом и горнодобывающем секторах, на объектах энергетики, водоснабжения и очистки стоков. Бренд одинаково эффективен для модернизации отдельных участков и для комплексной автоматизации линий и установок.
Почему это выгодно
- Минимум простоев: надежная диагностика и предсказуемое обслуживание снижают незапланированные остановки.
- Точность и качество: стабильные показания повышают выпуск и уменьшают брак.
- Масштабируемость: широкий ассортимент позволяет развивать систему без смены платформы.
- Долгий жизненный цикл: продуманная номенклатура и преемственность серий упрощают поставки и ремонт.
- Полный комплект: от датчика и интерфейсных модулей до взрывозащищенных корпусов и операторских панелей.
Как выбрать решение Pepperl+Fuchs
Определите среду (включая наличие взрывоопасных зон), необходимые интерфейсы и уровень безопасности, диапазон измерений и точность, а также условия монтажа. Сверьте каталожные номера с требуемыми сертификатами и аксессуарами. При сложных задачах стоит привлечь инженера для подбора комплекта устройств с учетом специфики технологического процесса.
Pepperl+Fuchs — это инвестиция в надежность, безопасность и предсказуемые результаты. Выбирайте оригинальные решения бренда для уверенной работы оборудования сегодня и готовности к задачам завтрашнего дня.