| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: 56-pin Elco connector RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 333 x 125 x 79 mm (13.1 x 4.9 x 3.1 inch) with Mux2700: 333 x 125 x 208 mm (13.1 x 4.9 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Ambient conditions | ||
|---|---|---|
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Mass | approx. 50 g | |
| Dimensions | 43.5 x 45 x 114 mm (1.71 x 1.77 x 4.48 inch) | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | no | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | no | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: KS connector (proprietary) RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 330 x 107 x 79 mm (12.9 x 4.2 x 3.1 inch) with HiDMux2700: 330 x 107 x 208 mm (12.9 x 4.2 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Описание оборудования | ||
|---|---|---|
| Beschriftungsträger für HiD-Termination-Boards | ||
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | no | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | no | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: KS connector (proprietary) RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 330 x 107 x 79 mm (12.9 x 4.2 x 3.1 inch) with HiDMux2700: 330 x 107 x 208 mm (12.9 x 4.2 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Описание оборудования | ||
|---|---|---|
| Placeholder for HiC type isoators | ||
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: 56-pin Elco connector RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 256 x 125 x 79 mm (10 x 4.9 x 3.1 inch) with HiDMux2700: 256 x 125 x 208 mm (10 x 4.9 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Описание оборудования | ||
|---|---|---|
| Placeholder for HiD type isoators | ||
| Supply | ||
|---|---|---|
| Rated voltage | 19.6 ... 30 V DC | |
| Ripple | &le 10 % | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Redundancy | ||
| Supply | Redundancy available. Each supply is decoupled. | |
| Fault indication output | ||
| Output type | volt-free contact | |
| Contact loading | 30 V DC , 1 A | |
| Indicators/settings | ||
| Display elements | LED Power (power supply), green LED LED Supply I (missing supply I), red LED LED Supply II (missing supply II), red LED LED Fault (fault signal), red LED | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | ||
| Supply | pluggable screw terminals , black | |
| Fault output | pluggable screw terminals , black | |
| Core cross-section | screw terminals: 0.2 ... 2.5 mm2 (24 ... 12 AWG) | |
| Material | housing: polycarbonate, 10 % glass fiber reinforced | |
| Mass | approx. 150 g | |
| Dimensions | 50 x 200 x 60 mm (1.97 x 7.9 x 2.36 inch) , height including module assembly | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Signal type | Universal | |
| Supply | ||
| Connection | SL1: 1a(-), 1b(-) 2a(+), 2b(+) | |
| Rated voltage | 20.4 ... 30 V via Termination Board | |
| Power dissipation | 0.2 W | |
| Current | &le 75 mA (per channel) | |
| Control circuit | ||
| Connection | SL1: 8a(+), 7a(-) 10a(+), 9a(-) | |
| Signal | 0 ... 20 mA 0 ... 5 V | |
| Internal resistor | 250 &Omega via DIP switch and programmable | |
| Field circuit | ||
| Connection | terminals 1, 2, 3, 4 | |
| Signal | 0 ... 20 mA | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 60 °C (32 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 140 g | |
| Dimensions | 18 x 106 x 135 mm (0.7 x 4.2 x 5.3 inch) | |
| Mounting | on Termination Board | |
| Electrical specifications | ||
|---|---|---|
| Rated voltage | 300 V AC/DC | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 105 °C (-4 ... 221 °F) | |
| Mechanical specifications | ||
| Connection | 37 pins/32 pins | |
| Material | ||
| Connector | plastic/plastic | |
| Cable | 22 AWG | |
| Data for application in connection with hazardous areas | ||
| Directive conformity | UL VM-1 flame test CSA FT4 flame test RoHS compliant | |
| Electrical specifications | ||
|---|---|---|
| Rated voltage | 300 V AC/DC | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 105 °C (-4 ... 221 °F) | |
| Mechanical specifications | ||
| Connection | 37 pins/32 pins | |
| Material | ||
| Connector | plastic/plastic | |
| Cable | 22 AWG | |
| Data for application in connection with hazardous areas | ||
| Directive conformity | UL VM-1 flame test CSA FT4 flame test RoHS compliant | |
| Electrical specifications | ||
|---|---|---|
| Rated voltage | 300 V AC/DC | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 80 °C (-4 ... 176 °F) | |
| Mechanical specifications | ||
| Connection | 37 pins/32 pins | |
| Material | ||
| Connector | plastic/plastic | |
| Cable | 22 AWG | |
| Construction type | 22 AWG 7/0096 tinned copper 18 individual twisted pairs overall foil | |
| Shielding | aluminum/poly foil 100% coverage 24 AWG 7/32 T.C. DW. | |
| Data for application in connection with hazardous areas | ||
| Directive conformity | UL/cULus RoHS compliant | |
| Electrical specifications | ||
|---|---|---|
| Rated voltage | 30 V | |
| Standard conformity | ||
| Flammability | IEC 60332-1-2 , flame-resistant | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , fixed | |
| Mechanical specifications | ||
| Connection | Sub-D plug , 37 pins/37 pins IDC plug, 16-pin, 20-pin and 24-pin | |
| Material | ||
| Connector | Zinc die cast, nickel plated | |
| Sheathing | PVC | |
| Core insolation | PVC | |
| Cable | LiYCY | |
| Diameter | 18 cores: 7.3 mm (0.29 inch) | |
| Bending radius | min. 6 x external diameter, fixed cable | |
| Cores | 18 x 0.14 mm2 | |
| Conductor construction | stranded wire , fine-strand | |
| Shield | Tinned copper braiding | |
| Mechanical specifications | ||
|---|---|---|
| Construction type | protective conductor terminal block 0.2 ... 4 mm2 | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 22 &Omega | |
| Series resistance | max. 29 &Omega | |
| Fuse rating | 160 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 | |
| Safe area connection | ||
| Connection | terminals 7, 8 | |
| Working voltage | ||
| Supply loop | max. 14.1 V | |
| Measurement loop | max. 13.7 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 100 &Omega | |
| Series resistance | max. 107 &Omega | |
| Fuse rating | 100 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 | |
| Safe area connection | ||
| Connection | terminals 7, 8 | |
| Working voltage | ||
| Supply loop | max. 13.3 V | |
| Measurement loop | max. 13 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 1 k&Omega | |
| Series resistance | max. 1025 &Omega | |
| Fuse rating | 100 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 | |
| Safe area connection | ||
| Connection | terminals 7, 8 | |
| Working voltage | ||
| Supply loop | max. 13.3 V | |
| Measurement loop | max. 13 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 150 &Omega | |
| Series resistance | max. 166 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 | |
| Safe area connection | ||
| Connection | terminals 7, 8 | |
| Working voltage | ||
| Supply loop | max. 19.5 V | |
| Measurement loop | max. 19 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 300 &Omega | |
| Series resistance | max. 341 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 | |
| Safe area connection | ||
| Connection | terminals 7, 8 | |
| Working voltage | ||
| Supply loop | max. 26.9 V | |
| Measurement loop | max. 26.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 00 ATEX 7096 | |
| Marking | II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA II T4 [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0355 (cULus) | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 240 &Omega | |
| Series resistance | max. 250 &Omega | |
| Fuse rating | 80 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 | |
| Safe area connection | ||
| Connection | terminals 7, 8 | |
| Working voltage | ||
| Supply loop | max. 26.9 V | |
| Measurement loop | max. 26.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 10 &Omega | |
| Series resistance | max. 15.5 &Omega | |
| Fuse rating | 200 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 6.4 V | |
| Measurement loop | max. 6 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 100 &Omega | |
| Series resistance | max. 107 &Omega | |
| Fuse rating | 100 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 13.3 V | |
| Measurement loop | max. 13 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 600 &Omega | |
| Series resistance | max. 646 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 27 V | |
| Measurement loop | max. 26.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 300 &Omega | |
| Series resistance | terminals 1, 8: max. 327 &Omega | |
| Voltage drop | terminals 4, 5: 1.2 V + (36 &Omega x signal current) | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 27 V | |
| Measurement loop | max. 26.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 300 &Omega | |
| Series resistance | max. 341 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 27 V | |
| Measurement loop | max. 26.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 00 ATEX 7096 | |
| Marking | II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA II T4 [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0355 (cULus) | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 240 &Omega | |
| Series resistance | max. 250 &Omega | |
| Fuse rating | 80 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 27 V | |
| Measurement loop | max. 26.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| Search characteristics | ||
|---|---|---|
| Additional functions | ||
| Asymmetrical version | yes | |
| General specifications | ||
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | terminals 1, 8: 300 &Omega terminals 4, 5: 50 &Omega | |
| Series resistance | terminals 1, 8: max. 327 &Omega terminals 4, 5: max. 64 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | terminals 7, 8: max. 27 V terminals 5, 6: max. 8.6 V | |
| Measurement loop | terminals 7, 8: max. 26.5 V at 10 µA terminals 5, 6: max. 6.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 300 &Omega | |
| Series resistance | max. 640 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 27 V | |
| Measurement loop | max. 26.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| Search characteristics | ||
|---|---|---|
| Additional functions | ||
| Asymmetrical version | yes | |
| General specifications | ||
| Type | DC version, negative polarity | |
| Electrical specifications | ||
| Nominal resistance | terminals 1, 8: 320 &Omega terminals 4, 5: 415 &Omega | |
| Series resistance | terminals 1, 8: max. 340 &Omega terminals 4, 5: max. 437 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | terminals 7, 8: max. 24.6 V terminals 5, 6: max. 19 V | |
| Measurement loop | terminals 7, 8: max. 24 V at 10 µA terminals 5, 6: max. 18 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
Компания Zipstore.ru поставляет оптом и в розницу запчасти Pepperl+Fuchs.
В каталоге сайта представлено 13440 запчастей Pepperl+Fuchs. Также вы можете приобрести опции и аксессуары для расширения функциональных возможностей, транспортировки и эксплуатации оборудования. Запчасти в каталоге могут иметь полное название, каталожный номер, фотографию, краткое описание, а также модели принтеров, с которыми они совместимы.
Для оформления заказа вы можете воспользоваться одним из следующих способов:
Мы осуществляем поставки запчастей Pepperl+Fuchs во все города России, а также в Республику Беларусь, Казахстан и другие страны СНГ.
Продажа осуществляется за наличный и безналичный расчет. На сайте указаны розничные цены в рублях и долларах, с учетом НДС. Чтобы узнать оптовые цены на запчасти Pepperl+Fuchs, нужно отправить запрос по электронной почте. Подробнее о способах доставки и оплаты можно узнать в разделе сайта «Оплата и доставка». В разделе «%Скидки и акции» Вы можете найти наиболее выгодные предложения по продаже запчастей, а также сезонные скидки и акции.
При возникновении вопросов по обслуживанию, эксплуатации, ремонту Pepperl+Fuchs, Вы можете проконсультироваться со специалистами на форуме сайта.