| General specifications | ||
|---|---|---|
| Number of protected signal lines | 4 | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 70 g | |
| Dimensions | 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 inch) | |
| Mounting | on the KF module | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 02 ATEX 2044 | |
| Marking | II (1)G [Ex ia Ga] IIC | |
| Internal capacitance | negligible | |
| Internal inductance | 200 µH | |
| Certificate | PF 16 CERT 3908 X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| IECEx approval | ||
| IECEx certificate | IECEx BAS 12.0123 | |
| IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 | |
| General specifications | ||
|---|---|---|
| Number of protected signal lines | 6 | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 70 g | |
| Dimensions | 20 x 62 x 115 mm (0.8 x 2.4 x 4.5 inch) | |
| Mounting | on the KF module | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 02 ATEX 2044 | |
| Marking | II (1)G [Ex ia Ga] IIC | |
| Internal capacitance | negligible | |
| Internal inductance | 200 µH | |
| Certificate | PF 16 CERT 3908 X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| IECEx approval | ||
| IECEx certificate | IECEx BAS 12.0123 | |
| IECEx marking | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| Standards | IEC 60079-0:2011 , IEC 60079-11:2011 | |
| General specifications | ||
|---|---|---|
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 1 | |
| Suitable components | protection module M-LB-1.150.M | |
| Electrical specifications | ||
| Nominal voltage | 120 V AC | |
| Maximum continuous operating voltage | max. 150 V AC max. 200 V DC | |
| Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 15 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
| Reaction time | max. 25 ns | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 240 g | |
| Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 1 | |
| Electrical specifications | ||
| Nominal voltage | 120 V AC | |
| Maximum continuous operating voltage | max. 150 V AC max. 200 V DC | |
| Nominal discharge current (8/20 µs) | 15 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 50 g | |
| Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
| Mounting | in the surge protection barrier M-LB-*.****.* | |
| Описание оборудования | ||
|---|---|---|
| &lambda/4 surge protection, N socket to N socket | ||
| General specifications | ||
|---|---|---|
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 1 | |
| Suitable components | protection module M-LB-1.275.M | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC | |
| Maximum continuous operating voltage | max. 275 V AC max. 350 V DC | |
| Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 20 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
| Reaction time | max. 25 ns | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 240 g | |
| Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 1 | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC | |
| Maximum continuous operating voltage | max. 275 V AC max. 350 V DC | |
| Nominal discharge current (8/20 µs) | 20 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 50 g | |
| Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
| Mounting | in the surge protection barrier M-LB-*.****.* | |
| Electrical specifications | ||
|---|---|---|
| Nominal voltage | 3.6 V | |
| Nominal current | 5 mA | |
| Nominal capacity | 19 Ah , capacity can varies with usage conditions | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | 15 ... 30 °C (59 ... 86 °F) recommended -40 ... 80 °C (-40 ... 176 °F) at accelerated derating | |
| Mechanical specifications | ||
| Mass | approx. 90 g | |
| Dimensions | Ø33 x 61,5 mm (1.3 x 2.4 inch) | |
| General specifications | ||
|---|---|---|
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 1 | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC | |
| Maximum continuous operating voltage | max. 255 V AC | |
| Nominal discharge current (8/20 µs) | 20 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 50 g | |
| Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
| Mounting | in the surge protection barrier M-LB-*.****.* | |
| Описание оборудования | ||
|---|---|---|
| Adapter N socket to N socket | ||
| General specifications | ||
|---|---|---|
| Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
| Number of protected supply lines | 2 | |
| Suitable components | protection module M-LB-2.150.T3.M | |
| Electrical specifications | ||
| Nominal voltage | 120 V AC | |
| Maximum continuous operating voltage | max. 150 V AC/DC | |
| Nominal discharge current (8/20 µs) | 2 kA | |
| Max. surge current (8/20 µs) | 4 kA | |
| Voltage protection level | max. 640 V (L-N) max. 800 V (L/N-PE) | |
| Reaction time | max. 25 ns (L-N) max. 100 ns (L/N-PE) | |
| Short-circuit-proof | 6 kA eff at max. mains-side overcurrent protection | |
| Overcurrent protection | max. 25 A gL/gG (B 25 A) , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529:2013 | |
| Operating conditions | ||
| Installation conditions | ||
| Mounting location | indoor | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 120 g | |
| Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
| Number of protected supply lines | 1 | |
| Electrical specifications | ||
| Nominal voltage | 120 V AC | |
| Maximum continuous operating voltage | max. 150 V AC/DC | |
| Nominal discharge current (8/20 µs) | 2 kA | |
| Max. surge current (8/20 µs) | 4 kA | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529:2013 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 50 g | |
| Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
| Mounting | in the surge protection barrier M-LB-*.****.* | |
| Описание оборудования | ||
|---|---|---|
| Adapter N socket to TNC socket | ||
| Search characteristics | ||
|---|---|---|
| Network | TN | |
| General specifications | ||
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 2 | |
| Suitable components | protection module M-LB-1.150.M | |
| Electrical specifications | ||
| Nominal voltage | 120 V AC | |
| Maximum continuous operating voltage | max. 150 V AC | |
| Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 15 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
| Reaction time | max. 25 ns | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 240 g | |
| Dimensions | 36 x 90 x 73 mm (1.4 x 3.6 x 2.9 inch) (2 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
| Number of protected supply lines | 2 | |
| Suitable components | protection module M-LB-2.255.T3.M | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC | |
| Maximum continuous operating voltage | max. 255 V AC | |
| Temporary over-voltage | 335 V 335 V/5 s (TOV withstand) (L-N) 400 V/5 s (TOV withstand) (L/N-PE) 1200 V+Ucs/200 ms (TOV safe failure) (L+N-PE) 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 3 kA | |
| Max. surge current (8/20 µs) | 5 kA | |
| Voltage protection level | max. 1.25 kV (L-N) max. 1.5 kV (L/N-PE) | |
| Reaction time | max. 25 ns (L-N) max. 100 ns (L/N-PE) | |
| Short-circuit-proof | 6 kA eff at max. mains-side overcurrent protection | |
| Overcurrent protection | max. 25 A gL/gG (B 25 A) , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529:2013 | |
| Operating conditions | ||
| Installation conditions | ||
| Mounting location | indoor | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 120 g | |
| Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
| Number of protected supply lines | 1 | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC | |
| Maximum continuous operating voltage | max. 255 V AC/DC | |
| Nominal discharge current (8/20 µs) | 3 kA | |
| Max. surge current (8/20 µs) | 5 kA | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529:2013 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 50 g | |
| Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
| Mounting | in the surge protection barrier M-LB-*.****.* | |
| Описание оборудования | ||
|---|---|---|
| Adapter N plug to TNC plug | ||
| Search characteristics | ||
|---|---|---|
| Network | TN | |
| General specifications | ||
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 2 | |
| Suitable components | protection module M-LB-1.275.M | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC | |
| Maximum continuous operating voltage | max. 275 V AC | |
| Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 20 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
| Reaction time | max. 25 ns | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 240 g | |
| Dimensions | 36 x 90 x 73 mm (1.4 x 3.6 x 2.9 inch) (2 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Search characteristics | ||
|---|---|---|
| Network | TT | |
| General specifications | ||
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 2 | |
| Suitable components | protection module M-LB-1.275.M protection module M-LB-1.NPE.M | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC | |
| Maximum continuous operating voltage | max. 275 V AC (L-N) max. 255 V AC (N-PE) | |
| Temporary over-voltage | 335 V/5 s (TOV withstand) (L-N) 1200 V/200 ms (TOV withstand) (N-PE) | |
| Nominal discharge current (8/20 µs) | 20 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Total discharge current (8/20 µs) | 12 kA (N-PE) | |
| Voltage protection level | max. 1.25 kV (L-N) max. 1 kV at 5 kA (L-N) &le 1.5 kV (N-PE) | |
| Reaction time | max. 25 ns (L-N) max. 100 ns (N-PE) | |
| Follow current extinguishing capability | 100 A eff (N-PE) | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 240 g | |
| Dimensions | 36 x 90 x 73 mm (1.4 x 3.6 x 2.9 inch) (2 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
| Number of protected supply lines | 2 | |
| Suitable components | protection module M-LB-2.30.T3.M | |
| Electrical specifications | ||
| Nominal voltage | 24 V AC | |
| Maximum continuous operating voltage | max. 30 V AC/DC | |
| Nominal discharge current (8/20 µs) | 1 kA | |
| Max. surge current (8/20 µs) | 2 kA | |
| Voltage protection level | max. 180 V (L-N) max. 630 V (L/N-PE) | |
| Reaction time | max. 25 ns (L-N) max. 100 ns (L/N-PE) | |
| Short-circuit-proof | 6 kA eff at max. mains-side overcurrent protection | |
| Overcurrent protection | max. 25 A gL/gG (B 25 A) , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529:2013 | |
| Operating conditions | ||
| Installation conditions | ||
| Mounting location | indoor | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 120 g | |
| Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
| Number of protected supply lines | 1 | |
| Electrical specifications | ||
| Nominal voltage | 24 V AC | |
| Maximum continuous operating voltage | max. 30 V AC/DC | |
| Nominal discharge current (8/20 µs) | 1 kA | |
| Max. surge current (8/20 µs) | 2 kA | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529:2013 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 50 g | |
| Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
| Mounting | in the surge protection barrier M-LB-*.****.* | |
| Описание оборудования | ||
|---|---|---|
| Adapter TNC plug to N socket | ||
| Search characteristics | ||
|---|---|---|
| Network | TN-C | |
| General specifications | ||
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 3 | |
| Suitable components | protection module M-LB-1.150.M | |
| Electrical specifications | ||
| Nominal voltage | 120 V AC / 240 V AC | |
| Maximum continuous operating voltage | max. 150 V AC | |
| Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 15 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
| Reaction time | max. 25 ns | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 360 g | |
| Dimensions | 54 x 90 x 73 mm (2.1 x 3.6 x 2.9 inch) (3 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Search characteristics | ||
|---|---|---|
| Network | TN-C | |
| General specifications | ||
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 3 | |
| Suitable components | protection module M-LB-1.275.M | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC / 400 V AC | |
| Maximum continuous operating voltage | max. 275 V AC | |
| Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 20 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
| Reaction time | max. 25 ns | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 360 g | |
| Dimensions | 54 x 90 x 73 mm (2.1 x 3.6 x 2.9 inch) (3 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Search characteristics | ||
|---|---|---|
| Network | TN-S | |
| General specifications | ||
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 4 | |
| Suitable components | protection module M-LB-1.150.M | |
| Electrical specifications | ||
| Nominal voltage | 120 V AC / 240 V AC | |
| Maximum continuous operating voltage | max. 150 V AC | |
| Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 15 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
| Reaction time | max. 25 ns | |
| Short-circuit-proof | 50 kA eff | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 480 g | |
| Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Search characteristics | ||
|---|---|---|
| Network | TN-S | |
| General specifications | ||
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 4 | |
| Suitable components | protection module M-LB-1.275.M | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC / 400 V AC | |
| Maximum continuous operating voltage | max. 275 V AC | |
| Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 20 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
| Reaction time | max. 25 ns | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 480 g | |
| Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Search characteristics | ||
|---|---|---|
| Network | TT | |
| General specifications | ||
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 4 | |
| Suitable components | protection module M-LB-1.275.M protection module M-LB-1.NPE.M | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC / 400 V AC | |
| Maximum continuous operating voltage | max. 275 V AC (L-N) max. 255 V AC (N-PE) | |
| Temporary over-voltage | 335 V/5 s (TOV withstand) (L-N) 1200 V/200 ms (TOV withstand) (N-PE) | |
| Nominal discharge current (8/20 µs) | 20 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Total discharge current (8/20 µs) | 12 kA (N-PE) | |
| Voltage protection level | max. 1.25 kV (L-N) max. 1 kV at 5 kA (L-N) &le 1.5 kV (N-PE) | |
| Reaction time | max. 25 ns (L-N) max. 100 ns (N-PE) | |
| Follow current extinguishing capability | 100 A eff (N-PE) | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 480 g | |
| Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC SELV/PELV | |
| Power consumption | < 5 W | |
| External bus | ||
| Connection | screw terminals for - 0.2 ... 4 mm2 (rigid wire) - 0.2 ... 2.5 mm2 (flexible wire) | |
| Interface 1 | Ethernet 10 BASE-T/100 BASE-TX , full galvanic isolation | |
| Protocol | HART UDP, MODBUS TCP | |
| Interface 2 | RS-485 | |
| Protocol | HART, MODBUS RTU | |
| Transfer rate | max. 115 kBit/s | |
| Galvanic isolation | ||
| Interface/interface | basic insulation according to IEC 61140, rated insulation voltage 50 Veff | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
| Directive 2014/53/EU | EN 300328: V2.1.1 EN 301489-17: V1.3.2 | |
| FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
| Mechanical specifications | ||
| Degree of protection | IP66/IP67 | |
| Mass | approx. 1 kg | |
| Dimensions | 258 mm x 114 mm x 84 mm without antenna and cable glands | |
| Mounting | panel mounting | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | FM 12 ATEX 0061 | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | Coc3042646 | |
| Approved for | NI Class I, Div. 2, GPS A-D NI Class II, Class III, Div. 2, GPS E-G | |
| IECEx approval | IECEx FMG 12.0002 | |
| Approved for | Ex nA IIC T4 Gc , Ex nAc T4 | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC SELV/PELV | |
| Power consumption | < 5 W | |
| External bus | ||
| Connection | screw terminals for - 0.2 ... 4 mm2 (rigid wire) - 0.2 ... 2.5 mm2 (flexible wire) | |
| Interface 1 | Ethernet 10 BASE-T/100 BASE-TX , full galvanic isolation | |
| Protocol | HART UDP, EtherNet/IP | |
| Interface 2 | RS-485 | |
| Protocol | HART | |
| Transfer rate | max. 115 kBit/s | |
| Galvanic isolation | ||
| Interface/interface | basic insulation according to IEC 61140, rated insulation voltage 50 Veff | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
| Directive 2014/53/EU | EN 300328: V2.1.1 EN 301489-17: V1.3.2 | |
| FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
| Mechanical specifications | ||
| Degree of protection | IP66/IP67 | |
| Mass | approx. 1 kg | |
| Dimensions | 258 mm x 114 mm x 84 mm without antenna and cable glands | |
| Mounting | panel mounting | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | FM 12 ATEX 0061 , for additional certificates see www.pepperl-fuchs.com | |
| Marking | II 3 G Ex nA nC IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | Coc3042646 | |
| Approved for | NI Class I, Div. 2, GPS A-D NI Class II, Class III, Div. 2, GPS E-G | |
| IECEx approval | IECEx FMG 12.0002 | |
| Approved for | Ex nA nC IIC T4 Gc Ex nAc nCc T4 | |
| Supply | ||
|---|---|---|
| Rated voltage | 7 ... 32 V DC | |
| Rated current | < 1 mA , max. 25 mA | |
| Electrical specifications | ||
| Output rated operating current | 3.2 ... 25 mA | |
| Supply | loop power for field devices voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V | |
| Input | ||
| Connection | - 5 wires, 600 mm long, exiting from male thread NPT1/2 - 1 external grounding point | |
| HART communication | ||
| Protocol | HART 7.1, backward compatible | |
| Number of devices | up to 8 HART field devices (depending on installation) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013+A11:2013 | |
| Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
| Directive 2014/53/EU | EN 300 328 V1.8.1:2012 EN 301 489-1 V1.9.2:2011 EN 301 489-17 V2.2.1:2012-09 | |
| Conformity | ||
| Degree of protection | IEC 60529:2013 | |
| Ambient conditions | ||
| Ambient temperature | temperature class T5: -40 ... 85 °C (-40 ... 185 °F) temperature class T6: -40 ... 75 °C (-40 ... 167 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP67 | |
| Material | Aluminum alloy with polyurethane enamel paint | |
| Mass | 460 g | |
| Dimensions | 60.8 x 60.8 x 100 mm (l x w x h) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | FM 12 ATEX 0021 X | |
| Marking | II 2 G Ex db IIC T6/T5 Gb II 2 D Ex tb IIIC T95°C Db | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | Coc3041762(C) | |
| Approved for | Class I, Zone 1, (A)Ex db IIC T6/T5 Gb Class I, Zone 21, (A)Ex tb IIIC T95°C Db Class I, Division 1, Groups A - D Class II, Division 1, Groups E - G Class III | |
| IECEx approval | IECEx FMG 12.0005X | |
| Approved for | Ex db IIC T6/T5 Gb Ex tb IIIC T95°C Db | |
| Standards | IEC 60079-0:2011 , IEC 60079-1:2014 , IEC 60079-31:2013 | |
Компания Zipstore.ru поставляет оптом и в розницу запчасти Pepperl+Fuchs.
В каталоге сайта представлено 13440 запчастей Pepperl+Fuchs. Также вы можете приобрести опции и аксессуары для расширения функциональных возможностей, транспортировки и эксплуатации оборудования. Запчасти в каталоге могут иметь полное название, каталожный номер, фотографию, краткое описание, а также модели принтеров, с которыми они совместимы.
Для оформления заказа вы можете воспользоваться одним из следующих способов:
Мы осуществляем поставки запчастей Pepperl+Fuchs во все города России, а также в Республику Беларусь, Казахстан и другие страны СНГ.
Продажа осуществляется за наличный и безналичный расчет. На сайте указаны розничные цены в рублях и долларах, с учетом НДС. Чтобы узнать оптовые цены на запчасти Pepperl+Fuchs, нужно отправить запрос по электронной почте. Подробнее о способах доставки и оплаты можно узнать в разделе сайта «Оплата и доставка». В разделе «%Скидки и акции» Вы можете найти наиболее выгодные предложения по продаже запчастей, а также сезонные скидки и акции.
При возникновении вопросов по обслуживанию, эксплуатации, ремонту Pepperl+Fuchs, Вы можете проконсультироваться со специалистами на форуме сайта.