| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 2 A , in each case for 8 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 50-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 490 g | |
| Dimensions | 205 x 175 x 153 mm (8.1 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.7 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 150 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA | |
| Off-state current TU =40 °C, switching element off | &le | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED yellow | |
| Functional safety related parameters | ||
| MTTFd | 1770 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 5 m | |
| Core cross-section | 0.14 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Housing diameter | 12 mm | |
| Degree of protection | IP67 | |
| Mass | 30 g | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 2 A , in each case for 8 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 40-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 490 g | |
| Dimensions | 205 x 175 x 153 mm (8.1 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| Supply | ||
|---|---|---|
| Connection | X20: terminals 3, 5 (+) 4, 6 (-) | |
| Nominal voltage | 24 V DC , in consideration of rated voltage of used isolators | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the isolators is decoupled, monitored and fused. | |
| Fault indication output | ||
| Connection | X20: terminals 1, 2 | |
| Output type | volt-free contact | |
| Contact loading | 30 V DC, 1 A | |
| Indicators/settings | ||
| Display elements | LED PWR1 (Termination Board power supply), green LED LED PWR2 (Termination Board power supply), green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | ||
| Field side | explosion hazardous area: 4 screw terminals per module , blue | |
| Control side | non-explosion hazardous area: 1 37-pin Sub-D connector | |
| Supply | pluggable screw terminals , black | |
| Core cross-section | screw terminals: 0.25 ... 1.5 mm2 (24 ... 12 AWG) | |
| Material | housing: polycarbonate, 10 % glass fiber reinforced | |
| Mass | approx. 730 g | |
| Dimensions | 216 x 200 x 163 mm (8.5 x 7.9 x 6.42 inch) , height including module assembly | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CESI 06 ATEX 022 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
| International approvals | ||
| UL approval | ||
| Control drawing | 116-0327 | |
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.7 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 500 Hz | |
| Hysteresis | 1 ... 20 typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 100 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | Multihole-LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1940 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
| Mechanical specifications | ||
| Connection type | 4-pin, M12 x 1 connector | |
| Cable version | PBT | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Housing diameter | 12 mm | |
| Degree of protection | IP67 | |
| Mass | 30 g | |
| Supply | ||
|---|---|---|
| Connection | X20: terminals 3, 5 (+) 4, 6 (-) | |
| Nominal voltage | 24 V DC , in consideration of rated voltage of used isolators | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the isolators is decoupled, monitored and fused. | |
| Fault indication output | ||
| Connection | X20: terminals 1, 2 | |
| Output type | volt-free contact | |
| Contact loading | 30 V DC, 1 A | |
| Indicators/settings | ||
| Display elements | LED PWR1 (Termination Board power supply), green LED LED PWR2 (Termination Board power supply), green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | ||
| Field side | explosion hazardous area: 4 screw terminals per module , blue | |
| Control side | non-explosion hazardous area: 2 37-pin Sub-D connector | |
| Supply | pluggable screw terminals , black | |
| Core cross-section | screw terminals: 0.25 ... 1.5 mm2 (24 ... 12 AWG) | |
| Material | housing: polycarbonate, 10 % glass fiber reinforced | |
| Mass | approx. 760 g | |
| Dimensions | 216 x 200 x 163 mm (8.5 x 7.9 x 6.42 inch) , height including module assembly | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CESI 06 ATEX 022 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
| International approvals | ||
| UL approval | ||
| Control drawing | 116-0327 | |
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 2 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): ELCO socket, 56-pin | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 840 g | |
| Dimensions | 216 x 200 x 163 mm (8.5 x 7.9 x 6.42 inch) , height including module assembly | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
| International approvals | ||
| UL approval | ||
| Control drawing | 116-0327 | |
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.7 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 500 Hz | |
| Hysteresis | typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 150 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| Off-state current TU =40 °C, switching element off | &le | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | Multihole-LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1770 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| EAC conformity | TR CU 020/2011 | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M8 x 1 , 3-pin | |
| Cable version | PBT | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Housing diameter | 12 mm | |
| Degree of protection | IP67 | |
| Mass | 30 g | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED | |
| Configuration | jumper SW1: card selection - position 1: DI card 3564 - position 2: n.c. (factory setting) - position 3: DI card 3504E | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): ELCO socket, 56-pin | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 840 g | |
| Dimensions | 216 x 200 x 163 mm (8.5 x 7.9 x 6.42 inch) , height including module assembly | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
| International approvals | ||
| UL approval | ||
| Control drawing | 116-0327 | |
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.7 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 150 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA | |
| Off-state current TU =40 °C, switching element off | &le | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | Multihole-LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1770 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Cable connector PVC , 0.8 m Schlemmer corrugated tube 1926304 | |
| Core cross-section | 0.14 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Housing diameter | 12 mm | |
| Degree of protection | IP67 | |
| Mass | 30 g | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): ELCO socket, 56-pin | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 840 g | |
| Dimensions | 216 x 200 x 163 mm (8.5 x 7.9 x 6.42 inch) , height including module assembly | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
| International approvals | ||
| UL approval | ||
| Control drawing | 116-0327 | |
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.7 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 150 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA | |
| Off-state current TU =40 °C, switching element off | &le | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | Multihole-LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1770 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Cable connector PVC , 0.1 m Schlemmer corrugated tube 1926304 | |
| Core cross-section | 0.14 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Housing diameter | 12 mm | |
| Degree of protection | IP67 | |
| Mass | 30 g | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): ELCO socket, 56-pin | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 840 g | |
| Dimensions | 216 x 200 x 163 mm (8.5 x 7.9 x 6.42 inch) , height including module assembly | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
| International approvals | ||
| UL approval | ||
| Control drawing | 116-0327 | |
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 50-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 650 g | |
| Dimensions | 240 x 175 x 153 mm (9.45 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.7 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 150 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | Multihole-LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1770 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.14 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Housing diameter | 12 mm | |
| Degree of protection | IP67 | |
| Mass | 30 g | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 40-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 650 g | |
| Dimensions | 240 x 175 x 153 mm (9.45 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 40-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 650 g | |
| Dimensions | 240 x 175 x 153 mm (9.45 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.7 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 150 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | Multihole-LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1770 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M12 x 1 , 4-pin | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Housing diameter | 12 mm | |
| Degree of protection | IP67 | |
| Mass | 30 g | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 40-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 650 g | |
| Dimensions | 240 x 175 x 153 mm (9.45 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 40-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 650 g | |
| Dimensions | 240 x 175 x 153 mm (9.45 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | NPN | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Actuating element | mild steel, e. g. 1.0037, SR235JR (formerly St37-2) 12 mm x 12 mm x 1 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.75 | |
| Reduction factor rBrass | 0.5 | |
| Output type | 4-wire | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | &ge 2500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 1.8 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 10 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1723 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.34 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| Mass | 71 g | |
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 40-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 650 g | |
| Dimensions | 240 x 175 x 153 mm (9.45 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | NPN | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Actuating element | mild steel, e. g. 1.0037, SR235JR (formerly St37-2) 12 mm x 12 mm x 1 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.3 | |
| Reduction factor r304 | 0.75 | |
| Reduction factor rBrass | 0.45 | |
| Output type | 4-wire | |
| Nominal ratings | ||
| Operating voltage | 7 ... 30 V | |
| Switching frequency | 0 ... 2200 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 4 µA at 25 °C | |
| No-load supply current | &le 10 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1484 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| E1 Type approval | 10R-04 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | cable PUR , 2 m | |
| Core cross-section | 0.34 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Housing diameter | 12 mm | |
| Degree of protection | IP68 / IP69K | |
| Mass | 66 g | |
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 40-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 650 g | |
| Dimensions | 240 x 175 x 153 mm (9.45 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | NPN | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Actuating element | mild steel, e. g. 1.0037, SR235JR (formerly St37-2) 12 mm x 12 mm x 1 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.75 | |
| Reduction factor rBrass | 0.5 | |
| Output type | 4-wire | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | &ge 2500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 1.8 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 10 mA | |
| Switching state indicator | Multihole-LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1723 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M12 x 1 , 4-pin | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| Mass | 15 g | |
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 50-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 650 g | |
| Dimensions | 240 x 175 x 153 mm (9.45 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Actuating element | mild steel, e. g. 1.0037, SR235JR (formerly St37-2) 12 mm x 12 mm x 1 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.75 | |
| Reduction factor rBrass | 0.5 | |
| Output type | 4-wire | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | &ge 2500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 1.8 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 10 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1723 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.34 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| Mass | 71 g | |
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 50-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 650 g | |
| Dimensions | 240 x 175 x 153 mm (9.45 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Actuating element | mild steel, e. g. 1.0037, SR235JR (formerly St37-2) 12 mm x 12 mm x 1 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.75 | |
| Reduction factor rBrass | 0.5 | |
| Output type | 4-wire | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | &ge 2500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 1.8 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 10 mA | |
| Switching state indicator | Multihole-LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1723 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M12 x 1 , 4-pin | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| Mass | 15 g | |
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 4 A , in each case for 16 modules | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Electrical specifications | ||
| volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
| Redundancy | ||
| Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
| Indicators/settings | ||
| Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED flashes: power supply failure | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 40-pin | |
| Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
| Material | housing: polycarbonate, 30 % glass fiber reinforced | |
| Mass | approx. 650 g | |
| Dimensions | 240 x 175 x 153 mm (9.45 x 6.9 x 6.02 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | CESI 06 ATEX 022 | |
| Group, category, type of protection | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Safe area | ||
| Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
| Galvanic isolation | ||
| Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
| International approvals | ||
| IECEx approval | IECEx CES 06.0003 | |
| Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I | |
Компания Zipstore.ru поставляет оптом и в розницу запчасти Pepperl+Fuchs.
В каталоге сайта представлено 13440 запчастей Pepperl+Fuchs. Также вы можете приобрести опции и аксессуары для расширения функциональных возможностей, транспортировки и эксплуатации оборудования. Запчасти в каталоге могут иметь полное название, каталожный номер, фотографию, краткое описание, а также модели принтеров, с которыми они совместимы.
Для оформления заказа вы можете воспользоваться одним из следующих способов:
Мы осуществляем поставки запчастей Pepperl+Fuchs во все города России, а также в Республику Беларусь, Казахстан и другие страны СНГ.
Продажа осуществляется за наличный и безналичный расчет. На сайте указаны розничные цены в рублях и долларах, с учетом НДС. Чтобы узнать оптовые цены на запчасти Pepperl+Fuchs, нужно отправить запрос по электронной почте. Подробнее о способах доставки и оплаты можно узнать в разделе сайта «Оплата и доставка». В разделе «%Скидки и акции» Вы можете найти наиболее выгодные предложения по продаже запчастей, а также сезонные скидки и акции.
При возникновении вопросов по обслуживанию, эксплуатации, ремонту Pepperl+Fuchs, Вы можете проконсультироваться со специалистами на форуме сайта.