| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Rated voltage | 12 ... 35 V DC loop powered | |
| Power dissipation | 0.4 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1+, 2- | |
| Current range | 0 ... 20 mA , load &le 50 &Omega | |
| Voltage range | 0 ... 10 V , load &ge 100 k&Omega | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 9+, 8- | |
| Load | (U -12 V) / 0.02 A | |
| Current output | 4 ... 20 mA , limited to &le 35 mA | |
| Fault signal | downscaling &le 3 mA | |
| Transfer characteristics | ||
| Rise time | 250 ms | |
| Indicators/settings | ||
| Control elements | DIP-switch potentiometer | |
| Configuration | via DIP switches via potentiometer | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Galvanic isolation | EN 50178:1997 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | ZELM 00 ATEX 0034 | |
| Marking | II (1)GD [EEx ia] IIC | |
| Certificate | TÜV 01 ATEX 1777 X | |
| Marking | II 3G Ex nA II T4 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| CSA approval | ||
| Control drawing | 116-0132 | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 11+, 12- | |
| Rated voltage | 20 ... 35 V DC | |
| Ripple | within the supply tolerance | |
| Power dissipation | 0.5 W | |
| Power consumption | 0.6 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 4-, 5-, 3+, 2+, 1+ | |
| Potentiometer | ||
| Types of measuring | 3-, 4-, 5-wire technology | |
| Lead resistance | 5 % of the potentiometer resistance (adjustable) | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 7-, 8+ | |
| Voltage output | 0 ... 10 V | |
| Output resistance | max. 30 &Omega | |
| Transfer characteristics | ||
| Accuracy | 0.05 % | |
| Rise time | 10 to 90 % &le 8 ms 10 to 90 % within 1 % of span &le 25 ms | |
| Indicators/settings | ||
| Control elements | potentiometer | |
| Configuration | via potentiometer | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 120 g | |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 00 ATEX 7171 | |
| Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) | |
| Certificate | TÜV 02 ATEX 1797 X | |
| Marking | II 3G Ex nA II T4 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 | |
| UL approval | ||
| Control drawing | 116-0173 (cULus) | |
| CSA approval | ||
| Control drawing | 116-0132 | |
| IECEx approval | IECEx BAS 10.0060 IECEx BAS 10.0061X | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 11+, 12- | |
| Rated voltage | 20 ... 35 V DC | |
| Ripple | within the supply tolerance | |
| Power dissipation | 0.5 W | |
| Power consumption | 0.6 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 4-, 5-, 3+, 2+, 1+ | |
| Potentiometer | ||
| Types of measuring | 3-, 4-, 5-wire technology | |
| Lead resistance | 5 % of the potentiometer resistance (adjustable) | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 7-, 8+ | |
| Voltage output | 0 ... 5 V | |
| Output resistance | max. 30 &Omega | |
| Transfer characteristics | ||
| Accuracy | 0.05 % | |
| Rise time | 10 to 90 % &le 8 ms 10 to 90 % within 1 % of span &le 25 ms | |
| Indicators/settings | ||
| Control elements | potentiometer | |
| Configuration | via potentiometer | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 120 g | |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 00 ATEX 7171 | |
| Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) | |
| Certificate | TÜV 02 ATEX 1797 X | |
| Marking | II 3G Ex nA II T4 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 | |
| UL approval | ||
| Control drawing | 116-0173 (cULus) | |
| CSA approval | ||
| Control drawing | 116-0132 | |
| IECEx approval | IECEx BAS 10.0060 IECEx BAS 10.0061X | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 11+, 12- | |
| Rated voltage | 20 ... 35 V DC | |
| Ripple | within the supply tolerance | |
| Power dissipation | 1 W | |
| Power consumption | 1.3 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 4-, 5-, 3+, 2+, 1+ | |
| Potentiometer | ||
| Types of measuring | 3-, 4-, 5-wire technology | |
| Lead resistance | 5 % of the potentiometer resistance (adjustable) | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 7-, 8+ | |
| Current output | 0 ... 20 mA, load &le1 k&Omega | |
| Transfer characteristics | ||
| Accuracy | 0.05 % | |
| Rise time | 10 to 90 % &le 8 ms 10 to 90 % within 1 % of span &le 25 ms | |
| Indicators/settings | ||
| Control elements | potentiometer | |
| Configuration | via potentiometer | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 120 g | |
| Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 00 ATEX 7171 | |
| Marking | II (1)G [Ex ia Ga] IIC , II (1)D [Ex ia Da] IIIC , I (M1) [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) | |
| Certificate | TÜV 02 ATEX 1797 X | |
| Marking | II 3G Ex nA II T4 | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 | |
| UL approval | ||
| Control drawing | 116-0173 (cULus) | |
| CSA approval | ||
| Control drawing | 116-0132 | |
| IECEx approval | IECEx BAS 10.0060 IECEx BAS 10.0061X | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc | |