Supply | ||
---|---|---|
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | &le 10 % | |
Fusing | 4 A , in each case for 16 modules | |
Power dissipation | &le 500 mW , without modules | |
Reverse polarity protection | yes | |
Redundancy | ||
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
Indicators/settings | ||
Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): ELCO socket, 56-pin | |
Material | housing: polycarbonate, 30 % glass fiber reinforced | |
Mass | approx. 1600 g | |
Dimensions | 300 x 200 x 163 mm (11.8 x 7.9 x 6.42 inch) , height including module assembly | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | CESI 11 ATEX 062 | |
Group, category, type of protection | ![]() ![]() ![]() | |
Safe area | ||
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | see control drawing of correspoding modules | |
IECEx approval | IECEx CES 11.0022 | |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
Supply | ||
---|---|---|
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | &le 10 % | |
Fusing | 4 A , in each case for 16 modules | |
Power dissipation | &le 500 mW , without modules | |
Reverse polarity protection | yes | |
Redundancy | ||
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
Indicators/settings | ||
Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): ELCO socket, 56-pin | |
Material | housing: polycarbonate, 30 % glass fiber reinforced | |
Mass | approx. 1600 g | |
Dimensions | 300 x 200 x 163 mm (11.8 x 7.9 x 6.42 inch) , height including module assembly | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | CESI 11 ATEX 062 | |
Group, category, type of protection | ![]() ![]() ![]() | |
Safe area | ||
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | see control drawing of correspoding modules | |
IECEx approval | IECEx CES 11.0022 | |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
General specifications | ||
---|---|---|
Rated operating distance | 1.5 mm | |
Installation | flush | |
Output polarity | DC | |
Assured operating distance | 0 ... 1.215 mm | |
Reduction factor rAl | 0.3 | |
Reduction factor rCu | 0.2 | |
Reduction factor r304 | 0.7 | |
Output type | 3-wire | |
Nominal ratings | ||
Operating voltage | 5 ... 30 V DC | |
Switching frequency | 0 ... 1200 Hz | |
Hysteresis | typ. 5 % | |
Short-circuit protection | pulsing | |
Voltage drop | &le 1.5 V | |
Operating current | 0 ... 100 mA | |
Off-state current | &le 10 µA | |
No-load supply current | &le 15 mA | |
Functional safety related parameters | ||
MTTFd | 3910 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Approvals and certificates | ||
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | Cable connector M8 x 1 , 3-pin with PVC cable 100 mm | |
Core cross-section | 0.09 mm2 | |
Housing material | PA | |
Sensing face | PA | |
Degree of protection | IP67 |
Supply | ||
---|---|---|
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | &le 10 % | |
Fusing | 4 A , in each case for 16 modules | |
Power dissipation | &le 500 mW , without modules | |
Reverse polarity protection | yes | |
Redundancy | ||
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
Indicators/settings | ||
Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): ELCO socket, 56-pin | |
Material | housing: polycarbonate, 30 % glass fiber reinforced | |
Mass | approx. 1600 g | |
Dimensions | 300 x 200 x 163 mm (11.8 x 7.9 x 6.42 inch) , height including module assembly | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | CESI 11 ATEX 062 | |
Group, category, type of protection | ![]() ![]() ![]() | |
Safe area | ||
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | see control drawing of correspoding modules | |
IECEx approval | IECEx CES 11.0022 | |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
Supply | ||
---|---|---|
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | &le 10 % | |
Fusing | 2 A , in each case for 8 modules | |
Power dissipation | &le 500 mW , without modules | |
Reverse polarity protection | yes | |
Redundancy | ||
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
Indicators/settings | ||
Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED | |
Configuration | jumper SW1/SW2: card selection - position 1: DI card 3564 - position 2: n.c. (factory setting) - position 3: DI card 3504E | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | hazardous area connection (field side): screw terminals, blue safe area connection (control side): ELCO socket, 56-pin | |
Material | housing: polycarbonate, 30 % glass fiber reinforced | |
Mass | approx. 600 g | |
Dimensions | 300 x 200 x 163 mm (11.8 x 7.9 x 6.42 inch) , height including module assembly | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | CESI 11 ATEX 062 | |
Group, category, type of protection | ![]() ![]() ![]() | |
Safe area | ||
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | see control drawing of correspoding modules | |
IECEx approval | IECEx CES 11.0022 | |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
Supply | ||
---|---|---|
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | &le 10 % | |
Fusing | 4 A , in each case for 16 modules | |
Power dissipation | &le 500 mW , without modules | |
Reverse polarity protection | yes | |
Redundancy | ||
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
Indicators/settings | ||
Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): ELCO socket, 56-pin | |
Material | housing: polycarbonate, 30 % glass fiber reinforced | |
Mass | approx. 1600 g | |
Dimensions | 300 x 200 x 163 mm (11.8 x 7.9 x 6.42 inch) , height including module assembly | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | CESI 11 ATEX 062 | |
Group, category, type of protection | ![]() ![]() ![]() | |
Safe area | ||
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | see control drawing of correspoding modules | |
IECEx approval | IECEx CES 11.0022 | |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
Supply | ||
---|---|---|
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | &le 10 % | |
Fusing | 4 A , in each case for 32 modules | |
Power dissipation | &le 500 mW , without modules | |
Reverse polarity protection | yes | |
Electrical specifications | ||
volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
Redundancy | ||
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
Indicators/settings | ||
Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 50-pin | |
Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
Material | housing: polycarbonate, 30 % glass fiber reinforced | |
Mass | approx. 860 g | |
Dimensions | 310 x 175 x 153 mm (12.2 x 6.9 x 6.02 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | CESI 11 ATEX 062 | |
Group, category, type of protection | ![]() ![]() ![]() | |
Safe area | ||
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
International approvals | ||
IECEx approval | IECEx CES 11.0022 | |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NPN | |
Rated operating distance | 1.5 mm | |
Installation | flush | |
Output polarity | DC | |
Assured operating distance | 0 ... 1.215 mm | |
Reduction factor rAl | 0.3 | |
Reduction factor rCu | 0.2 | |
Reduction factor r304 | 0.7 | |
Nominal ratings | ||
Operating voltage | 5 ... 30 V DC | |
Switching frequency | 0 ... 1200 Hz | |
Hysteresis | typ. 5 % | |
Short-circuit protection | pulsing | |
Voltage drop | &le 1.5 V | |
Operating current | 0 ... 100 mA | |
Off-state current | &le 10 µA | |
No-load supply current | &le 15 mA | |
Functional safety related parameters | ||
MTTFd | 3910 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Approvals and certificates | ||
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 500 mm | |
Core cross-section | 3 x 0.09 mm2 | |
Housing material | PA | |
Sensing face | PA | |
Housing diameter | ||
Degree of protection | IP67 |
Supply | ||
---|---|---|
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | &le 10 % | |
Fusing | 4 A , in each case for 16 modules | |
Power dissipation | &le 500 mW , without modules | |
Reverse polarity protection | yes | |
Electrical specifications | ||
volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
Redundancy | ||
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
Indicators/settings | ||
Display elements | LEDs PWR ON (Termination Board power supply) - LED power supply I, green LED - LED power supply II, green LED LED FAULT (fault indication), red LED - LED lits: module failure - LED flashes: power supply failure | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | hazardous area connection (field side): spring terminals, blue safe area connection (control side): Yokogawa system connector, 40-pin | |
Core cross-section | spring terminals: rigid: 0.2 ... 2.5 mm2 flexible: 0.25 ... 1.5 mm2 | |
Material | housing: polycarbonate, 30 % glass fiber reinforced | |
Mass | approx. 860 g | |
Dimensions | 310 x 175 x 153 mm (12.2 x 6.9 x 6.02 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | CESI 11 ATEX 062 | |
Group, category, type of protection | ![]() ![]() ![]() | |
Safe area | ||
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
International approvals | ||
IECEx approval | IECEx CES 11.0022 | |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
Supply | ||
---|---|---|
Connection | terminal block TB3 (1-, 2+ 3-, 4+) | |
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | &le 10 % | |
Fusing | 4 A | |
Power dissipation | &le 500 mW , without modules | |
Reverse polarity protection | yes | |
Electrical specifications | ||
volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
Redundancy | ||
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
Indicators/settings | ||
Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED LED Fault (fault indication), green LED | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): 37-pin Sub-D connector (male) | |
Core cross-section | 0.2 ... 2.5 mm2 (24 ... 12 AWG) | |
Material | housing: polycarbonate, 30 % glass fiber reinforced | |
Mass | approx. 900 g | |
Dimensions | 273 x 155 x 153 mm (L x W x H) , height including module assembly | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | CESI 06 ATEX 022 | |
Group, category, type of protection | ![]() ![]() ![]() | |
Safe area | ||
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
International approvals | ||
UL approval | ||
Control drawing | 116-0327 | |
IECEx approval | IECEx CES 06.0003 | |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
Supply | ||
---|---|---|
Connection | terminal block TB3 (1-, 2+ 3-, 4+) | |
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | &le 10 % | |
Fusing | 4 A | |
Power dissipation | &le 500 mW , without modules | |
Reverse polarity protection | yes | |
Electrical specifications | ||
volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
Redundancy | ||
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
Indicators/settings | ||
Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED LED Fault (fault indication), green LED | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): 37-pin Sub-D connector (male) | |
Core cross-section | 0.2 ... 2.5 mm2 (24 ... 12 AWG) | |
Material | housing: polycarbonate, 30 % glass fiber reinforced | |
Mass | approx. 900 g | |
Dimensions | 273 x 155 x 153 mm (L x W x H) , height including module assembly | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | CESI 06 ATEX 022 | |
Group, category, type of protection | ![]() ![]() ![]() | |
Safe area | ||
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
International approvals | ||
UL approval | ||
Control drawing | 116-0327 | |
IECEx approval | IECEx CES 06.0003 | |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
Supply | ||
---|---|---|
Connection | terminal block TB3 (1-, 2+ 3-, 4+) | |
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | &le 10 % | |
Fusing | 2 A | |
Power dissipation | &le 500 mW , without modules | |
Reverse polarity protection | yes | |
Electrical specifications | ||
volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
Redundancy | ||
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
Indicators/settings | ||
Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED LED Fault (fault indication), green LED | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): 37-pin Sub-D connector (male) | |
Core cross-section | 0.2 ... 2.5 mm2 (24 ... 12 AWG) | |
Material | housing: polycarbonate, 30 % glass fiber reinforced | |
Mass | approx. 500 g | |
Dimensions | 201 x 155 x 153 mm (7.9 x 6.1 x 6.0 inch) , height including module assembly | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | CESI 11 ATEX 062 | |
Group, category, type of protection | ![]() ![]() ![]() | |
Safe area | ||
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | see control drawing of correspoding modules | |
IECEx approval | IECEx CES 11.0022 | |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NPN | |
Rated operating distance | 1.5 mm | |
Installation | flush | |
Output polarity | DC | |
Assured operating distance | 0 ... 1.215 mm | |
Reduction factor rAl | 0.3 | |
Reduction factor rCu | 0.2 | |
Reduction factor r304 | 0.7 | |
Nominal ratings | ||
Operating voltage | 5 ... 30 V DC | |
Switching frequency | 0 ... 1200 Hz | |
Hysteresis | typ. 5 % | |
Short-circuit protection | pulsing | |
Voltage drop | &le 1.5 V | |
Operating current | 0 ... 100 mA | |
Off-state current | &le 10 µA | |
No-load supply current | &le 15 mA | |
Approvals and certificates | ||
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 5 m | |
Core cross-section | 3 x 0.09 mm2 | |
Housing material | PA | |
Sensing face | PA | |
Housing diameter | ||
Degree of protection | IP67 |
Supply | ||
---|---|---|
Connection | terminal block TB3 (1-, 2+ 3-, 4+) | |
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | &le 10 % | |
Fusing | 4 A | |
Power dissipation | &le 500 mW , without modules | |
Reverse polarity protection | yes | |
Electrical specifications | ||
volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
Redundancy | ||
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
Indicators/settings | ||
Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED LED Fault (fault indication), green LED | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): 37-pin Sub-D connector (male) | |
Core cross-section | 0.2 ... 2.5 mm2 (24 ... 12 AWG) | |
Material | housing: polycarbonate, 30 % glass fiber reinforced | |
Mass | approx. 1000 g | |
Dimensions | 357 x 155 x 153 mm (L x W x H) , height including module assembly | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | CESI 11 ATEX 062 | |
Group, category, type of protection | ![]() ![]() ![]() | |
Safe area | ||
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | see control drawing of correspoding modules | |
IECEx approval | IECEx CES 11.0022 | |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
Supply | ||
---|---|---|
Connection | terminal block TB3 (1-, 2+ 3-, 4+) | |
Rated voltage | 24 V DC , in consideration of rated voltage of used isolated barriers | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Ripple | &le 10 % | |
Fusing | 4 A | |
Power dissipation | &le 500 mW , without modules | |
Reverse polarity protection | yes | |
Electrical specifications | ||
volt-free fault indication output | max. 30 V AC/40 V DC, 2 A | |
Redundancy | ||
Supply | Redundancy available. The supply for the modules is decoupled, monitored and fused. | |
Indicators/settings | ||
Display elements | LEDs PWR ON (power supply) - LED power supply I, green LED - LED power supply II, green LED LED Fault (fault indication), green LED | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | hazardous area connection (field side): pluggable screw terminals, blue safe area connection (control side): 37-pin Sub-D connector (male) | |
Core cross-section | 0.2 ... 2.5 mm2 (24 ... 12 AWG) | |
Material | housing: polycarbonate, 30 % glass fiber reinforced | |
Mass | approx. 1000 g | |
Dimensions | 357 x 155 x 153 mm (L x W x H) , height including module assembly | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | CESI 11 ATEX 062 | |
Group, category, type of protection | ![]() ![]() ![]() | |
Safe area | ||
Maximum safe voltage | 250 V (Attention! Um is no rated voltage.) | |
Galvanic isolation | ||
Field circuit/control circuit | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | see control drawing of correspoding modules | |
IECEx approval | IECEx CES 11.0022 | |
Approved for | [Ex ia Ga] IIC [Ex ia Da] IIIC [Ex ia Ma] I |
Search characteristics | ||
---|---|---|
Additional functions | ||
Asymmetrical version | yes | |
General specifications | ||
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | terminals 1, 8: 300 &Omega terminals 4, 5: 50 &Omega | |
Series resistance | terminals 1, 8: max. 327 &Omega terminals 4, 5: max. 64 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Measuring resistor | terminals 2, 3 to 4: internal resistor 250 &Omega for 5 V signal on terminals 6, 7 to 5 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | terminals 7, 8: max. 27 V terminals 5, 6: max. 8.6 V | |
Measurement loop | terminals 7, 8: max. 26.5 V at 10 µA terminals 5, 6: max. 6.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | terminals 14, 15 | |
Rated voltage | 20 ... 48 V DC or 90 ... 253 V AC , 45 ... 65 Hz | |
Rated current | &le 230 mA | |
Power dissipation | 2.3 W | |
Power consumption | max. 4.5 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2, 3- | |
Rated values | 22 ... 24 V DC / 100 mA , see additional information | |
Short-circuit current | max. 125 mA | |
Switching point | PNP: 0-signal: < 12.5 V 1-signal: > 13.5 V NPN and push-pull output: 0-signal: < 4.5 V 1-signal: > 5.5 V | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Output I, II | signal, relay | |
Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 125 V AC/4 A/ cos &phi > 0.7 40 V DC / 2 A | |
Mechanical life | 20 x 106 switching cycles | |
Electrical life | 0.2 x 106 switching cycles (40 V DC, 2 A, ohmic) 0.4 x 106 switching cycles (253 V AC, 2 A, cos &phi = 1) 0.25 x 106 switching cycles (253 V AC, 2 A, cos &phi = 0.7) | |
Minimum load | 50 mW, 5 V DC | |
Energized/De-energized delay | &le 90 ms / &le 90 ms | |
Transfer characteristics | ||
Switching frequency | &le 5 Hz for delay 0 s adjustable energized/de-energized delay: 0 ... 79 s | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 166 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 10 CERT 1417 X | |
Marking | ![]() | |
Output I, II | ||
Contact loading | 50 V AC/2 A/cos &phi > 0.7 40 V DC/1 A resistive load | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
General specifications | ||
---|---|---|
Switching function | Normally open (NO) | |
Output type | PNP | |
Rated operating distance | 1.5 mm | |
Installation | flush | |
Output polarity | DC | |
Assured operating distance | 0 ... 1.215 mm | |
Reduction factor rAl | 0.3 | |
Reduction factor rCu | 0.2 | |
Reduction factor r304 | 0.7 | |
Output type | 3-wire | |
Nominal ratings | ||
Operating voltage | 5 ... 30 V DC | |
Switching frequency | 0 ... 1200 Hz | |
Hysteresis | typ. 5 % | |
Short-circuit protection | pulsing | |
Voltage drop | &le 1.5 V | |
Operating current | 0 ... 100 mA | |
Off-state current | &le 10 µA | |
No-load supply current | &le 15 mA | |
Functional safety related parameters | ||
MTTFd | 4830 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Approvals and certificates | ||
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | Cable connector M12 x 1 , 3-pin with PVC cable L = 160 mm ± 5 mm | |
Core cross-section | 0.09 mm2 | |
Housing material | PA | |
Sensing face | PA | |
Housing diameter | ||
Degree of protection | IP67 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Power consumption | max. 1.5 W | |
Input | ||
Connection side | field side | |
Connection | Input I: terminals 1+, 2+, 3- Input II: terminals 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | not available | |
Control input | sensor power supply approx. 8.2 V, impedance 1.2 k&Omega | |
Pulse duration | > 200 µs for standstill monitoring, > 250 µs for rotation direction detecion | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Trip value | for standstill monitoring: 0.1 Hz 0.5 Hz 2 Hz 10 Hz adjustable via DIP switch (S1 and S2) | |
Transfer characteristics | ||
Accuracy | 5 % (S3 = I), 30 % (S3 = II) | |
Start-up override | 5 seconds or 20 seconds, programmable | |
Frequency range | &le 2 kHz | |
Rotation direction detection | 90° phase difference between pulse input signal 1 and 2, overlapping &ge 125 µs | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Rated voltage | loop powered | |
Power dissipation | < 1.5 W | |
Power consumption | < 1.5 W | |
Input | ||
Connection side | control side | |
Connection | Input terminals 5, 6 test input terminals 7, 8, 9, 10 | |
Pulse/Pause ratio | 150 ms / 150 ms | |
Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V | |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
Output | ||
Connection side | field side | |
Connection | terminals 1, 2 | |
Contact loading | 253 V AC/3 A/cos &phi 0.7 30 V DC/3 A resistive load 253 V AC / 1/8 HP | |
Minimum switch current | 10 mA / 24 V DC | |
Energized/De-energized delay | 150 ms / 150 ms | |
Mechanical life | 5 x 106 switching cycles | |
Transfer characteristics | ||
Switching frequency | < 3 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 15 CERT 3932 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-15:2010 | |
International approvals | ||
UL approval | E106378 |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Performance level (PL) | PL e | |
Supply | ||
Rated voltage | loop powered | |
Power dissipation | < 1.5 W | |
Power consumption | < 1.5 W | |
Input | ||
Connection side | control side | |
Connection | Input terminals 7, 8 test input terminals 9, 10, 11, 12 | |
Pulse/Pause ratio | 150 ms / 150 ms | |
Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V | |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
Output | ||
Connection side | field side | |
Connection | terminals 4, 5, 6 | |
Contact loading | 253 V AC/5 A/cos &phi 0.7 30 V DC/5 A resistive load 253 V AC / 1/2 HP | |
Minimum switch current | 10 mA / 24 V DC | |
Energized/De-energized delay | 150 ms / 150 ms | |
Mechanical life | 5 x 106 switching cycles | |
Transfer characteristics | ||
Switching frequency | < 3 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Machinery Directive | ||
Directive 2006/42/EC | EN 62061:2005+AC:2010+A1:2013+A2:2015 , EN/ISO 13849-1:2015 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 120 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 15 CERT 3933 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-15:2010 | |
International approvals | ||
UL approval | E106378 |
General specifications | ||
---|---|---|
Switching function | Normally open (NO) | |
Output type | PNP | |
Rated operating distance | 1.5 mm | |
Installation | flush | |
Output polarity | DC | |
Assured operating distance | 0 ... 1.215 mm | |
Reduction factor rAl | 0.3 | |
Reduction factor rCu | 0.2 | |
Reduction factor r304 | 0.7 | |
Nominal ratings | ||
Operating voltage | 5 ... 30 V DC | |
Switching frequency | 0 ... 1200 Hz | |
Hysteresis | typ. 5 % | |
Short-circuit protection | pulsing | |
Voltage drop | &le 1.5 V | |
Operating current | 0 ... 100 mA | |
Off-state current | &le 10 µA | |
No-load supply current | &le 15 mA | |
Functional safety related parameters | ||
MTTFd | 4830 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Approvals and certificates | ||
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | Cable connector M8 x 1 , 3-pin with PVC cable 100 mm | |
Core cross-section | 0.09 mm2 | |
Housing material | PA | |
Sensing face | PA | |
Housing diameter | ||
Degree of protection | IP67 |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Rated voltage | loop powered | |
Power dissipation | < 1.5 W | |
Power consumption | < 1.5 W | |
Input | ||
Connection side | control side | |
Connection | Input terminals 7, 8 test input terminals 9, 10, 11, 12 | |
Pulse/Pause ratio | 150 ms / 150 ms | |
Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V | |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
Output | ||
Connection side | control side | |
Connection | terminals 2, 3 | |
Contact loading | 253 V AC/5 A/cos &phi 0.7 30 V DC/5 A resistive load 253 V AC / 1/2 HP | |
Minimum switch current | 10 mA / 24 V DC | |
Energized/De-energized delay | 150 ms / 150 ms | |
Mechanical life | 5 x 106 switching cycles | |
Transfer characteristics | ||
Switching frequency | < 3 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 120 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 15 CERT 3933 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-15:2010 | |
International approvals | ||
UL approval | E106378 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 20 ... 30 V DC | |
Rated current | approx. 130 mA | |
Power dissipation | 2 W | |
Power consumption | 2.5 W | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3 | |
Input I | ||
Input signal | 0/4 ... 20 mA | |
Available voltage | &ge 15 V at 20 mA | |
Open circuit voltage/short-circuit current | 24 V / 33 mA | |
Input resistance | 45 &Omega (terminals 2, 3) | |
Line fault detection | breakage I < 0.2 mA short-circuit I > 22 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 Output: analog terminals 8+, 7- | |
Output signal | 0 ... 20 mA or 4 ... 20 mA | |
Output I, II | signal, relay | |
Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 V DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Output III | Signal, analog | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 &Omega | |
Fault signal | downscale I &le 3.6 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
International approvals | ||
UL approval | E223772 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 23, 24 | |
Rated voltage | 20 ... 90 V DC or 48 ... 253 V AC | |
Power dissipation | 2 W / 3 VA | |
Power consumption | 2.2 W / 4 VA | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3 | |
Input I | ||
Input signal | 0/4 ... 20 mA | |
Available voltage | > 15 V at 20 mA | |
Open circuit voltage/short-circuit current | 24 V / 33 mA | |
Input resistance | 45 &Omega (terminals 2, 3) | |
Line fault detection | breakage I < 0.2 mA short-circuit I > 22 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 Output: analog terminals 8+, 7- | |
Output signal | 0 ... 20 mA or 4 ... 20 mA | |
Output I, II | signal, relay | |
Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 V DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Output III | Signal, analog | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 &Omega | |
Fault signal | downscale I &le 3.6 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Switching function | Normally open (NO) | |
Output type | PNP | |
Rated operating distance | 1.5 mm | |
Installation | flush | |
Output polarity | DC | |
Assured operating distance | 0 ... 1.215 mm | |
Reduction factor rAl | 0.3 | |
Reduction factor rCu | 0.2 | |
Reduction factor r304 | 0.7 | |
Nominal ratings | ||
Operating voltage | 5 ... 30 V DC | |
Switching frequency | 0 ... 1200 Hz | |
Hysteresis | typ. 5 % | |
Short-circuit protection | pulsing | |
Voltage drop | &le 1.5 V | |
Operating current | 0 ... 100 mA | |
Off-state current | &le 10 µA | |
No-load supply current | &le 15 mA | |
Functional safety related parameters | ||
MTTFd | 4830 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Approvals and certificates | ||
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 500 mm | |
Core cross-section | 3 x 0.09 mm2 | |
Housing material | PA | |
Sensing face | PA | |
Housing diameter | ||
Degree of protection | IP67 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | terminals 14, 15 | |
Rated voltage | 19 ... 90 V DC / 48 ... 253 V AC | |
Rated current | &le 110 mA DC / &le 75 mA AC | |
Power dissipation | 1.3 W | |
Power consumption | 2.1 W | |
Input | ||
Connection side | field side | |
Input I | ||
Input signal | 0/4 ... 20 mA | |
Rated current | 22 mA | |
Available voltage | > 15 V at 20 mA , terminals 1+, 3- | |
Open circuit voltage/short-circuit current | 21 V / 26 mA , terminals 1+, 3- terminals 1+, 2- not short-circuit protected | |
Input resistance | < 55 &Omega , terminals 2-, 3+ | |
Input II | ||
Input signal | 0/2 ... 10 V | |
Input resistance | > 1 M&Omega | |
Output | ||
Connection side | control side | |
Output I | current output | |
Connection | source: terminals 7(-), 8(+) sink: terminals 7(+), 9(-) | |
Output signal | 0/4 ... 20 mA | |
Source | load 0 ... 750 &Omega open circuit voltage < 21 V | |
Sink | voltage across terminals 5 ... 30 V | |
Output II | voltage output | |
Connection | terminals 10-, 11+ | |
Output signal | 0/2 ... 10 V | |
Load | min. 10 k&Omega | |
Transfer characteristics | ||
Reaction time | 150 ms | |
Indicators/settings | ||
Display elements | LED | |
Control elements | DIP-switch rotary switch | |
Configuration | via DIP switches via rotary switch | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Low voltage | ||
Directive 2006/95/EC | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 23+, 24- or power feed module/Power Rail | |
Rated voltage | 20 ... 30 V DC | |
Rated current | approx. 100 mA | |
Power dissipation/power consumption | &le 2 W / 2.2 W | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 6 | |
RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 | |
Measuring current | approx. 400 µA | |
Types of measuring | 2-, 3-, 4-wire technology | |
Lead resistance | max. 50 &Omega | |
Measurement loop monitoring | sensor breakage, sensor short-circuit | |
Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) | |
Cold junction compensation | external and internal | |
Measurement loop monitoring | sensor breakage | |
Potentiometer | 0.8 ... 20 k&Omega | |
Types of measuring | 2-, 3-, 5-wire technology | |
Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV | |
Input resistance | &ge 250 k&Omega (0 ... 10 V) min. 1 M&Omega (0 ... 1 V, -100 ... 100 mV) | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
Output I, II | relay | |
Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output III | Analog current output | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 &Omega | |
Fault signal | downscale I &le 3.6 mA, upscale I &ge 21 mA (acc. NAMUR NE43) | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Sampling rate | approx. 700 ms | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 23, 24 | |
Rated voltage | 20 ... 90 V DC / 48 ... 253 V AC | |
Power dissipation/power consumption | &le 2 W 2.5 VA / 2.2 W 3 VA | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 6 | |
RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 | |
Measuring current | approx. 400 µA | |
Types of measuring | 2-, 3-, 4-wire technology | |
Lead resistance | max. 50 &Omega | |
Measurement loop monitoring | sensor breakage, sensor short-circuit | |
Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) | |
Cold junction compensation | external and internal | |
Measurement loop monitoring | sensor breakage | |
Potentiometer | 0.8 ... 20 k&Omega | |
Types of measuring | 2-, 3-, 5-wire technology | |
Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV | |
Input resistance | &ge 250 k&Omega (0 ... 10 V) min. 1 M&Omega (0 ... 1 V, -100 ... 100 mV) | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
Output I, II | relay | |
Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output III | Analog current output | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 &Omega | |
Fault signal | downscale I &le 3.6 mA, upscale I &ge 21 mA (acc. NAMUR NE43) | |
Transfer characteristics | ||
Sampling rate | approx. 700 ms | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Switching function | Normally open (NO) | |
Output type | PNP | |
Rated operating distance | 1.5 mm | |
Installation | flush | |
Output polarity | DC | |
Assured operating distance | 0 ... 1.215 mm | |
Reduction factor rAl | 0.3 | |
Reduction factor rCu | 0.2 | |
Reduction factor r304 | 0.7 | |
Nominal ratings | ||
Operating voltage | 5 ... 30 V DC | |
Switching frequency | 0 ... 1200 Hz | |
Hysteresis | typ. 5 % | |
Short-circuit protection | pulsing | |
Voltage drop | &le 1.5 V | |
Operating current | 0 ... 100 mA | |
Off-state current | &le 10 µA | |
No-load supply current | &le 15 mA | |
Functional safety related parameters | ||
MTTFd | 4830 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , L = 2 m | |
Core cross-section | 3 x 0.09 mm2 | |
Housing material | PA | |
Sensing face | PA | |
Housing diameter | ||
Degree of protection | IP67 |
Компания Zipstore.ru поставляет оптом и в розницу запчасти Pepperl+Fuchs.
В каталоге сайта представлено 13440 запчастей Pepperl+Fuchs. Также вы можете приобрести опции и аксессуары для расширения функциональных возможностей, транспортировки и эксплуатации оборудования. Запчасти в каталоге могут иметь полное название, каталожный номер, фотографию, краткое описание, а также модели принтеров, с которыми они совместимы.
Для оформления заказа вы можете воспользоваться одним из следующих способов:
Мы осуществляем поставки запчастей Pepperl+Fuchs во все города России, а также в Республику Беларусь, Казахстан и другие страны СНГ.
Продажа осуществляется за наличный и безналичный расчет. На сайте указаны розничные цены в рублях и долларах, с учетом НДС. Чтобы узнать оптовые цены на запчасти Pepperl+Fuchs, нужно отправить запрос по электронной почте. Подробнее о способах доставки и оплаты можно узнать в разделе сайта «Оплата и доставка». В разделе «%Скидки и акции» Вы можете найти наиболее выгодные предложения по продаже запчастей, а также сезонные скидки и акции.
При возникновении вопросов по обслуживанию, эксплуатации, ремонту Pepperl+Fuchs, Вы можете проконсультироваться со специалистами на форуме сайта.