| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Actuating element | mild steel, e. g. 1.0037, SR235JR (formerly St37-2) 12 mm x 12 mm x 1 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.3 | |
| Reduction factor r304 | 0.75 | |
| Reduction factor rBrass | 0.45 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 7 ... 30 V | |
| Switching frequency | 0 ... 2200 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 4 µA at 25 °C | |
| No-load supply current | &le 10 mA | |
| Switching state indicator | Multihole-LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1484 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| E1 Type approval | 10R-04 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M12 x 1 , 3-pin | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP68 / IP69K | |
| Mass | 20 g | |
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 300 &Omega | |
| Series resistance | max. 327 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 27 V | |
| Measurement loop | max. 26.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Output type | Digital current output | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Actuating element | mild steel, e. g. 1.0037, SR235JR (formerly St37-2) 12 mm x 12 mm x 1 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.3 | |
| Reduction factor r304 | 0.7 | |
| Reduction factor rBrass | 0.45 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 9 ... 30 V DC | |
| Switching frequency | 0 ... 1800 Hz | |
| Hysteresis | 2 ... 15 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | yes | |
| Temperature drift | &le 10 % | |
| Load resistor | 100 ... 250 Ohm | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1601 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Digital output | ||
| Output type | object detected: 10 mA ± 1 mA object not detected: 5 mA ± 1 mA | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | cable PUR , 2 m | |
| Core cross-section | 3 x 0.34 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP68 / IP69K | |
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 300 &Omega | |
| Series resistance | max. 341 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 27 V | |
| Measurement loop | max. 26.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 00 ATEX 7096 | |
| Marking | II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA II T4 [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0355 (cULus) | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| General specifications | ||
|---|---|---|
| Type | AC version | |
| Electrical specifications | ||
| Nominal resistance | 10 &Omega | |
| Series resistance | max. 18.18 &Omega | |
| Fuse rating | 250 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 4.3 V | |
| Measurement loop | max. 0.9 V at 1 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Output type | Digital current output | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Actuating element | mild steel, e. g. 1.0037, SR235JR (formerly St37-2) 12 mm x 12 mm x 1 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.3 | |
| Reduction factor r304 | 0.7 | |
| Reduction factor rBrass | 0.45 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 9 ... 30 V DC | |
| Switching frequency | 0 ... 1800 Hz | |
| Hysteresis | 2 ... 15 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | yes | |
| Temperature drift | &le 10 % | |
| Load resistor | 100 ... 250 Ohm | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1601 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Digital output | ||
| Output type | object detected: 10 mA ± 1 mA object not detected: 5 mA ± 1 mA | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M12 x 1 , 4-pin | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP68 / IP69K | |
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| General specifications | ||
|---|---|---|
| Type | AC version | |
| Electrical specifications | ||
| Nominal resistance | 1000 &Omega | |
| Series resistance | max. 1033 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 11.1 V | |
| Measurement loop | max. 10 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | 240 &Omega | |
| Series resistance | max. 273 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 27 V | |
| Measurement loop | max. 26.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 00 ATEX 7096 | |
| Marking | II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA II T4 [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0355 (cULus) | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | Two-wire | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | AC/DC | |
| Reduction factor rAl | 0.5 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.75 | |
| Nominal ratings | ||
| Operating voltage | 20 ... 250 V AC/20 ... 300 V DC | |
| Switching frequency | 30 Hz | |
| Hysteresis | 3 ... 15 typ. 5 % | |
| Reverse polarity protection | yes | |
| Short-circuit protection | yes | |
| Voltage drop | &le 8 V | |
| Operating current | 8 ... 200 mA AC/DC | |
| Off-state current | &le 0.8 mA | |
| Operating voltage indicator | LED, green | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | M12 connector, male, 4-pin, B-coded | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Housing diameter | 12 mm | |
| Degree of protection | IP67 | |
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| Search characteristics | ||
|---|---|---|
| Additional functions | ||
| Asymmetrical version | yes | |
| General specifications | ||
| Type | DC version, positive polarity | |
| Electrical specifications | ||
| Nominal resistance | terminals 1, 8: 300 &Omega terminals 4, 5: 50 &Omega | |
| Series resistance | terminals 1, 8: max. 327 &Omega terminals 4, 5: max. 64 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Measuring resistor | terminals 2, 3 to 4: internal resistor 250 &Omega for 5 V signal on terminals 6, 7 to 5 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | terminals 7, 8: max. 27 V terminals 5, 6: max. 8.6 V | |
| Measurement loop | terminals 7, 8: max. 26.5 V at 10 µA terminals 5, 6: max. 6.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Type | AC version | |
| Electrical specifications | ||
| Nominal resistance | 10 &Omega | |
| Series resistance | max. 79 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 8.8 V | |
| Measurement loop | max. 6.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 00 ATEX 7096 | |
| Marking | II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA II T4 [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0355 (cULus) | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| General specifications | ||
|---|---|---|
| Type | AC version | |
| Electrical specifications | ||
| Nominal resistance | 360 &Omega | |
| Series resistance | max. 380 &Omega | |
| Fuse rating | 50 mA | |
| Hazardous area connection | ||
| Connection | terminals 1, 2 3, 4 | |
| Safe area connection | ||
| Connection | terminals 5, 6 7, 8 | |
| Working voltage | ||
| Supply loop | max. 7.7 V | |
| Measurement loop | max. 6.5 V at 10 µA | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | max. 2 x 2.5 ... mm2 | |
| Mass | approx. 150 g | |
| Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
| Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
| Certificate | TÜV 99 ATEX 1484 X | |
| Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0118 | |
| UL approval | ||
| Control drawing | 116-0139 | |
| CSA approval | ||
| Control drawing | 116-0119 | |
| IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc | |
| Описание оборудования | ||
|---|---|---|
| 24 V DC | ||
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | Two-wire | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | AC/DC | |
| Reduction factor rAl | 0.5 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.75 | |
| Nominal ratings | ||
| Operating voltage | 20 ... 250 V AC/20 ... 300 V DC | |
| Switching frequency | 30 Hz | |
| Hysteresis | 3 ... 15 typ. 5 % | |
| Reverse polarity protection | reverse polarity tolerant | |
| Short-circuit protection | yes | |
| Voltage drop | &le 8 V | |
| Operating current | 8 ... 200 mA AC/DC | |
| Off-state current | &le 0.8 mA | |
| Operating voltage indicator | LED, green | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector 1/2"-20 UN , 3-pin | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Housing diameter | 12 mm | |
| Degree of protection | IP67 | |
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| General specifications | ||
|---|---|---|
| Signal type | Digital Input | |
| Supply | ||
| Connection | terminals 14, 15 | |
| Rated voltage | 20 ... 48 V DC or 90 ... 253 V AC , 45 ... 65 Hz | |
| Rated current | &le 230 mA | |
| Power dissipation | 2.3 W | |
| Power consumption | max. 4.5 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1+, 2, 3- | |
| Rated values | 22 ... 24 V DC / 100 mA , see additional information | |
| Short-circuit current | max. 125 mA | |
| Switching point | PNP: 0-signal: < 12.5 V 1-signal: > 13.5 V NPN and push-pull output: 0-signal: < 4.5 V 1-signal: > 5.5 V | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
| Output I, II | signal, relay | |
| Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 125 V AC/4 A/ cos &phi > 0.7 40 V DC / 2 A | |
| Mechanical life | 20 x 106 switching cycles | |
| Electrical life | 0.2 x 106 switching cycles (40 V DC, 2 A, ohmic) 0.4 x 106 switching cycles (253 V AC, 2 A, cos &phi = 1) 0.25 x 106 switching cycles (253 V AC, 2 A, cos &phi = 0.7) | |
| Minimum load | 50 mW, 5 V DC | |
| Energized/De-energized delay | &le 90 ms / &le 90 ms | |
| Transfer characteristics | ||
| Switching frequency | &le 5 Hz for delay 0 s adjustable energized/de-energized delay: 0 ... 79 s | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 166 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 10 CERT 1417 X | |
| Marking | II 3G Ex nA nC IIC T4 Gc | |
| Output I, II | ||
| Contact loading | 50 V AC/2 A/cos &phi > 0.7 40 V DC/1 A resistive load | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| General specifications | ||
|---|---|---|
| Signal type | Digital Input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | terminals 14+, 15- | |
| Rated voltage | 20 ... 30 V DC | |
| Power consumption | max. 1.5 W | |
| Input | ||
| Connection side | field side | |
| Connection | Input I: terminals 1+, 2+, 3- Input II: terminals 4+, 5+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
| Line fault detection | not available | |
| Control input | sensor power supply approx. 8.2 V, impedance 1.2 k&Omega | |
| Pulse duration | > 200 µs for standstill monitoring, > 250 µs for rotation direction detecion | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
| Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
| Minimum switch current | 2 mA / 24 V DC | |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
| Mechanical life | 107 switching cycles | |
| Trip value | for standstill monitoring: 0.1 Hz 0.5 Hz 2 Hz 10 Hz adjustable via DIP switch (S1 and S2) | |
| Transfer characteristics | ||
| Accuracy | 5 % (S3 = I), 30 % (S3 = II) | |
| Start-up override | 5 seconds or 20 seconds, programmable | |
| Frequency range | &le 2 kHz | |
| Rotation direction detection | 90° phase difference between pulse input signal 1 and 2, overlapping &ge 125 µs | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 150 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Описание оборудования | ||
|---|---|---|
| 24 V DC | ||
| General specifications | ||
|---|---|---|
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.75 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 5 ... 60 V | |
| Switching frequency | 0 ... 2500 Hz | |
| Hysteresis | typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2 V | |
| Operating current | 0 ... 150 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA | |
| No-load supply current | &le 7 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1183 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose Class 2 power source | |
| CSA approval | cCSAus Listed, General Purpose Class 2 power source | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 100 °C (-40 ... 212 °F) | |
| Mechanical specifications | ||
| Connection type | Cable connector , Deutsch with PUR cable , 740 mm | |
| Connection assembly | Deutsch housing DT04-3P-C015 Deutsch wedge W3P Deutsch contact 1060-16-0622 | |
| Core cross-section | 3 x 0.75 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP69K, not connector! | |
| Mass | 72 g | |
| Описание оборудования | ||
|---|---|---|
| 48 V AC ... 253 V AC/20 V DC ... 90 V DC | ||
| General specifications | ||
|---|---|---|
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.35 | |
| Reduction factor r304 | 0.75 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 5 ... 60 V | |
| Switching frequency | 0 ... 2500 Hz | |
| Hysteresis | typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2 V | |
| Operating current | 0 ... 150 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA | |
| No-load supply current | &le 7 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1183 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose Class 2 power source | |
| CSA approval | cCSAus Listed, General Purpose Class 2 power source | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 100 °C (-40 ... 212 °F) | |
| Mechanical specifications | ||
| Connection type | Cable connector , Deutsch with PUR cable , 880 mm | |
| Connection assembly | Deutsch housing DT04-4P-C015 Deutsch wedge W4P Deutsch contact 1060-16-0622 | |
| Core cross-section | 3 x 0.75 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP69K, not connector! | |
| Mass | 80 g | |
| Описание оборудования | ||
|---|---|---|
| 48 V AC ... 253 V AC/20 V DC ... 90 V DC | ||
| General specifications | ||
|---|---|---|
| Output type | Digital current output | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Actuating element | mild steel, e. g. 1.0037, SR235JR (formerly St37-2) 12 mm x 12 mm x 1 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.65 | |
| Reduction factor rBrass | 0.35 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 9 ... 16 V DC | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | 2 ... 15 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | yes | |
| Temperature drift | &le 10 % | |
| Load resistor | 100 ... 250 Ohm | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1601 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Digital output | ||
| Output type | object detected: 18,5 mA ± 1,5 mA object not detected: 5,5 mA ± 1,5 mA | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | Cable connector PUR , 1.1 m AMP Superseal | |
| Core cross-section | 3 x 0.34 mm2 | |
| Housing material | Stainless steel | |
| Sensing face | PBT | |
| Degree of protection | IP68 / IP69K | |
| General information | ||
| Scope of delivery | 2 self locking nuts in scope of delivery | |
| General specifications | ||
|---|---|---|
| Signal type | Digital Output | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Rated voltage | loop powered | |
| Power dissipation | < 1.5 W | |
| Power consumption | < 1.5 W | |
| Input | ||
| Connection side | control side | |
| Connection | Input terminals 5, 6 test input terminals 7, 8, 9, 10 | |
| Pulse/Pause ratio | 150 ms / 150 ms | |
| Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V | |
| Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
| Output | ||
| Connection side | field side | |
| Connection | terminals 1, 2 | |
| Contact loading | 253 V AC/3 A/cos &phi 0.7 30 V DC/3 A resistive load 253 V AC / 1/8 HP | |
| Minimum switch current | 10 mA / 24 V DC | |
| Energized/De-energized delay | 150 ms / 150 ms | |
| Mechanical life | 5 x 106 switching cycles | |
| Transfer characteristics | ||
| Switching frequency | < 3 Hz | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 | |
| Degree of protection | IEC 60529:2013 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 15 CERT 3932 X | |
| Marking | II 3G Ex nC ec IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| General specifications | ||
|---|---|---|
| Signal type | Digital Output | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 3 | |
| Performance level (PL) | PL e | |
| Supply | ||
| Rated voltage | loop powered | |
| Power dissipation | < 1.5 W | |
| Power consumption | < 1.5 W | |
| Input | ||
| Connection side | control side | |
| Connection | Input terminals 7, 8 test input terminals 9, 10, 11, 12 | |
| Pulse/Pause ratio | 150 ms / 150 ms | |
| Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V | |
| Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
| Output | ||
| Connection side | field side | |
| Connection | terminals 4, 5, 6 | |
| Contact loading | 253 V AC/5 A/cos &phi 0.7 30 V DC/5 A resistive load 253 V AC / 1/2 HP | |
| Minimum switch current | 10 mA / 24 V DC | |
| Energized/De-energized delay | 150 ms / 150 ms | |
| Mechanical life | 5 x 106 switching cycles | |
| Transfer characteristics | ||
| Switching frequency | < 3 Hz | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Machinery Directive | ||
| Directive 2006/42/EC | EN 62061:2005+AC:2010+A1:2013+A2:2015 , EN/ISO 13849-1:2015 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 | |
| Degree of protection | IEC 60529:2013 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 120 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 15 CERT 3933 X | |
| Marking | II 3G Ex nC ec IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | NPN | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1530 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Digital Output | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Rated voltage | loop powered | |
| Power dissipation | < 1.5 W | |
| Power consumption | < 1.5 W | |
| Input | ||
| Connection side | control side | |
| Connection | Input terminals 7, 8 test input terminals 9, 10, 11, 12 | |
| Pulse/Pause ratio | 150 ms / 150 ms | |
| Signal level | 0-signal: -5 ... 5 V 1-signal: 19 ... 26.5 V | |
| Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 2, 3 | |
| Contact loading | 253 V AC/5 A/cos &phi 0.7 30 V DC/5 A resistive load 253 V AC / 1/2 HP | |
| Minimum switch current | 10 mA / 24 V DC | |
| Energized/De-energized delay | 150 ms / 150 ms | |
| Mechanical life | 5 x 106 switching cycles | |
| Transfer characteristics | ||
| Switching frequency | < 3 Hz | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 | |
| Degree of protection | IEC 60529:2013 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) Observe the temperature range limited by derating, see section derating. | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 120 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 15 CERT 3933 X | |
| Marking | II 3G Ex nC ec IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | NPN | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.7 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | < 0.5 mA | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Standard conformity | ||
| Standards | IEC / EN 60947-5-2:2004 | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 5 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA, green | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Digital Output | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Rated voltage | loop powered | |
| Power dissipation | < 1.5 W | |
| Power consumption | < 1.5 W | |
| Input | ||
| Connection side | control side | |
| Connection | Input terminals 7, 8 test input terminals 10, 11, 12 | |
| Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
| Signal level | 0-signal: -3 ... 3 V DC 1-signal: 20 ... 26.5 V | |
| Rated current | 45 ... 50 mA | |
| Output | ||
| Connection side | field side | |
| Connection | output I (ETS): terminals 2, 3 output II (DTS): terminals 4, 5, 6 output I and II (DPS): terminals 2, 3, 4, 5, 6 | |
| Contact loading | 253 V AC/5 A/cos &phi 0.7 30 V DC/5 A resistive load | |
| Minimum switch current | 2 mA / 24 V DC | |
| Energized/De-energized delay | approx. 10 ms / approx. 5 ms | |
| Mechanical life | 5 x 106 switching cycles | |
| Transfer characteristics | ||
| Switching frequency | < 10 Hz | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 | |
| Degree of protection | IEC 60529:2013 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 15 CERT 3844 X | |
| Marking | II 3G Ex nA nC IIC T4 Gc [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013, EN 60079-15:2010 | |
| Описание оборудования | ||
|---|---|---|
| Input 0/4 mA ... 20 mA Output 0/4 mA ... 20 mA | ||
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | NPN | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1530 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M8 x 1 , 4-pin | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
Компания Zipstore.ru поставляет оптом и в розницу запчасти Pepperl+Fuchs.
В каталоге сайта представлено 13440 запчастей Pepperl+Fuchs. Также вы можете приобрести опции и аксессуары для расширения функциональных возможностей, транспортировки и эксплуатации оборудования. Запчасти в каталоге могут иметь полное название, каталожный номер, фотографию, краткое описание, а также модели принтеров, с которыми они совместимы.
Для оформления заказа вы можете воспользоваться одним из следующих способов:
Мы осуществляем поставки запчастей Pepperl+Fuchs во все города России, а также в Республику Беларусь, Казахстан и другие страны СНГ.
Продажа осуществляется за наличный и безналичный расчет. На сайте указаны розничные цены в рублях и долларах, с учетом НДС. Чтобы узнать оптовые цены на запчасти Pepperl+Fuchs, нужно отправить запрос по электронной почте. Подробнее о способах доставки и оплаты можно узнать в разделе сайта «Оплата и доставка». В разделе «%Скидки и акции» Вы можете найти наиболее выгодные предложения по продаже запчастей, а также сезонные скидки и акции.
При возникновении вопросов по обслуживанию, эксплуатации, ремонту Pepperl+Fuchs, Вы можете проконсультироваться со специалистами на форуме сайта.