| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 23+, 24- | |
| Rated voltage | 20 ... 30 V DC | |
| Rated current | approx. 130 mA | |
| Power dissipation | 2 W | |
| Power consumption | 2.5 W | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3 | |
| Input I | ||
| Input signal | 0/4 ... 20 mA | |
| Available voltage | &ge 15 V at 20 mA | |
| Open circuit voltage/short-circuit current | 24 V / 33 mA | |
| Input resistance | 45 &Omega (terminals 2, 3) | |
| Line fault detection | breakage I < 0.2 mA short-circuit I > 22 mA | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 Output: analog terminals 8+, 7- | |
| Output signal | 0 ... 20 mA or 4 ... 20 mA | |
| Output I, II | signal, relay | |
| Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 V DC / 2 A | |
| Mechanical life | 5 x 107 switching cycles | |
| Output III | Signal, analog | |
| Current range | 0 ... 20 mA or 4 ... 20 mA | |
| Open loop voltage | max. 24 V DC | |
| Load | max. 650 &Omega | |
| Fault signal | downscale I &le 3.6 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| International approvals | ||
| UL approval | E223772 | |
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | NPN | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | terminals 23, 24 | |
| Rated voltage | 20 ... 90 V DC or 48 ... 253 V AC | |
| Power dissipation | 2 W / 3 VA | |
| Power consumption | 2.2 W / 4 VA | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3 | |
| Input I | ||
| Input signal | 0/4 ... 20 mA | |
| Available voltage | > 15 V at 20 mA | |
| Open circuit voltage/short-circuit current | 24 V / 33 mA | |
| Input resistance | 45 &Omega (terminals 2, 3) | |
| Line fault detection | breakage I < 0.2 mA short-circuit I > 22 mA | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 Output: analog terminals 8+, 7- | |
| Output signal | 0 ... 20 mA or 4 ... 20 mA | |
| Output I, II | signal, relay | |
| Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 V DC / 2 A | |
| Mechanical life | 5 x 107 switching cycles | |
| Output III | Signal, analog | |
| Current range | 0 ... 20 mA or 4 ... 20 mA | |
| Open loop voltage | max. 24 V DC | |
| Load | max. 650 &Omega | |
| Fault signal | downscale I &le 3.6 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | terminals 14, 15 | |
| Rated voltage | 19 ... 90 V DC / 48 ... 253 V AC | |
| Rated current | &le 110 mA DC / &le 75 mA AC | |
| Power dissipation | 1.3 W | |
| Power consumption | 2.1 W | |
| Input | ||
| Connection side | field side | |
| Input I | ||
| Input signal | 0/4 ... 20 mA | |
| Rated current | 22 mA | |
| Available voltage | > 15 V at 20 mA , terminals 1+, 3- | |
| Open circuit voltage/short-circuit current | 21 V / 26 mA , terminals 1+, 3- terminals 1+, 2- not short-circuit protected | |
| Input resistance | < 55 &Omega , terminals 2-, 3+ | |
| Input II | ||
| Input signal | 0/2 ... 10 V | |
| Input resistance | > 1 M&Omega | |
| Output | ||
| Connection side | control side | |
| Output I | current output | |
| Connection | source: terminals 7(-), 8(+) sink: terminals 7(+), 9(-) | |
| Output signal | 0/4 ... 20 mA | |
| Source | load 0 ... 750 &Omega open circuit voltage < 21 V | |
| Sink | voltage across terminals 5 ... 30 V | |
| Output II | voltage output | |
| Connection | terminals 10-, 11+ | |
| Output signal | 0/2 ... 10 V | |
| Load | min. 10 k&Omega | |
| Transfer characteristics | ||
| Reaction time | 150 ms | |
| Indicators/settings | ||
| Display elements | LED | |
| Control elements | DIP-switch rotary switch | |
| Configuration | via DIP switches via rotary switch | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2004/108/EC | EN 61326-1:2006 | |
| Low voltage | ||
| Directive 2006/95/EC | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 150 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.7 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | < 0.5 mA | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1640 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Standard conformity | ||
| Standards | IEC / EN 60947-5-2:2004 | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 5 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA, green | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| Описание оборудования | ||
|---|---|---|
| Input 4 mA ... 20 mA Output 4 mA ... 20 mA | ||
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1640 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M8 x 1 , 4-pin | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Rated voltage | 12 ... 35 V DC loop powered | |
| Power dissipation | 0.4 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2-, 3+ suitable for Pt100, 2- and 3-wire connection | |
| Lead resistance | max. 100 &Omega per line | |
| Measuring current | approx. 1 mA | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 9+, 8- | |
| Load | (U -12 V) / 0.02 A | |
| Current output | 4 ... 20 mA , limited to &le 35 mA | |
| Fault signal | sensor burnout: upscaling &ge 22 mA , limited to &le 35 mA | |
| Transfer characteristics | ||
| Measurement range | span without linearization 25 ... 800 °C (77 ... 1472 °F)/ with linearisation 25 ... 375 °C (77 ... 707 °F) zero point without linearization -200 ... 400 °C (-328 ... 752 °F)/ with linearisation -30 ... 375 °C (-22 ... 707 °F) span and zero point adjustable | |
| Rise time | 250 ms | |
| Indicators/settings | ||
| Control elements | DIP-switch rotary switch | |
| Configuration | via DIP switches via rotary switch | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2004/108/EC | EN 61326-1:2006 | |
| Conformity | ||
| Insulation coordination | EN 50178 | |
| Galvanic isolation | EN 50178 | |
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 150 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | terminals 23+, 24- or power feed module/Power Rail | |
| Rated voltage | 20 ... 30 V DC | |
| Rated current | approx. 100 mA | |
| Power dissipation/power consumption | &le 2 W / 2.2 W | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3, 4, 6 | |
| RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 | |
| Measuring current | approx. 400 µA | |
| Types of measuring | 2-, 3-, 4-wire technology | |
| Lead resistance | max. 50 &Omega | |
| Measurement loop monitoring | sensor breakage, sensor short-circuit | |
| Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) | |
| Cold junction compensation | external and internal | |
| Measurement loop monitoring | sensor breakage | |
| Potentiometer | 0.8 ... 20 k&Omega | |
| Types of measuring | 2-, 3-, 5-wire technology | |
| Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV | |
| Input resistance | &ge 250 k&Omega (0 ... 10 V) min. 1 M&Omega (0 ... 1 V, -100 ... 100 mV) | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
| Output I, II | relay | |
| Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 DC / 2 A | |
| Mechanical life | 5 x 107 switching cycles | |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
| Output III | Analog current output | |
| Current range | 0 ... 20 mA or 4 ... 20 mA | |
| Open loop voltage | max. 24 V DC | |
| Load | max. 650 &Omega | |
| Fault signal | downscale I &le 3.6 mA, upscale I &ge 21 mA (acc. NAMUR NE43) | |
| Collective error message | Power Rail | |
| Transfer characteristics | ||
| Sampling rate | approx. 700 ms | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | terminals 23, 24 | |
| Rated voltage | 20 ... 90 V DC / 48 ... 253 V AC | |
| Power dissipation/power consumption | &le 2 W 2.5 VA / 2.2 W 3 VA | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3, 4, 6 | |
| RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 | |
| Measuring current | approx. 400 µA | |
| Types of measuring | 2-, 3-, 4-wire technology | |
| Lead resistance | max. 50 &Omega | |
| Measurement loop monitoring | sensor breakage, sensor short-circuit | |
| Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) | |
| Cold junction compensation | external and internal | |
| Measurement loop monitoring | sensor breakage | |
| Potentiometer | 0.8 ... 20 k&Omega | |
| Types of measuring | 2-, 3-, 5-wire technology | |
| Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV | |
| Input resistance | &ge 250 k&Omega (0 ... 10 V) min. 1 M&Omega (0 ... 1 V, -100 ... 100 mV) | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
| Output I, II | relay | |
| Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 DC / 2 A | |
| Mechanical life | 5 x 107 switching cycles | |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
| Output III | Analog current output | |
| Current range | 0 ... 20 mA or 4 ... 20 mA | |
| Open loop voltage | max. 24 V DC | |
| Load | max. 650 &Omega | |
| Fault signal | downscale I &le 3.6 mA, upscale I &ge 21 mA (acc. NAMUR NE43) | |
| Transfer characteristics | ||
| Sampling rate | approx. 700 ms | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | NPN | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1530 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | terminals 14, 15 | |
| Rated voltage | 19 ... 90 V DC / 48 ... 253 V AC | |
| Rated current | &le 110 mA DC / &le 75 mA AC | |
| Power dissipation | 1.3 W | |
| Power consumption | 2.1 W | |
| Input | ||
| Connection side | field side | |
| Input I | ||
| Input signal | 0/4 ... 20 mA | |
| Rated current | 22 mA | |
| Available voltage | > 15 V at 20 mA , terminals 1+, 3- | |
| Open circuit voltage/short-circuit current | 21 V / 26 mA , terminals 1+, 3- terminals 1+, 2- not short-circuit protected | |
| Input resistance | < 55 &Omega , terminals 2-, 3+ | |
| Input II | ||
| Input signal | 0/2 ... 10 V | |
| Input resistance | > 1 M&Omega | |
| Output | ||
| Connection side | control side | |
| Output I | current output | |
| Connection | source: terminals 7(-), 8(+) sink: terminals 7(+), 9(-) | |
| Output signal | 0/4 ... 20 mA | |
| Source | load 0 ... 750 &Omega open circuit voltage < 21 V | |
| Sink | voltage across terminals 5 ... 30 V | |
| Output II | voltage output | |
| Connection | terminals 10-, 11+ | |
| Output signal | 0/2 ... 10 V | |
| Load | min. 10 k&Omega | |
| Transfer characteristics | ||
| Reaction time | 150 ms | |
| Indicators/settings | ||
| Display elements | LED | |
| Control elements | DIP-switch rotary switch | |
| Configuration | via DIP switches via rotary switch | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2004/108/EC | EN 61326-1:2006 | |
| Low voltage | ||
| Directive 2006/95/EC | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 150 g | |
| Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | NPN | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1530 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M8 x 1 , 3-pin | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 23+, 24- | |
| Rated voltage | 20 ... 30 V DC | |
| Rated current | approx. 130 mA | |
| Power dissipation | 2 W | |
| Power consumption | 2.5 W | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3 | |
| Input I | ||
| Input signal | 0/4 ... 20 mA | |
| Available voltage | &ge 15 V at 20 mA | |
| Open circuit voltage/short-circuit current | 24 V / 33 mA | |
| Input resistance | 45 &Omega (terminals 2, 3) | |
| Line fault detection | breakage I < 0.2 mA short-circuit I > 22 mA | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 Output: analog terminals 8+, 7- | |
| Output signal | 0 ... 20 mA or 4 ... 20 mA | |
| Output I, II | signal, relay | |
| Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 V DC / 2 A | |
| Mechanical life | 5 x 107 switching cycles | |
| Output III | Signal, analog | |
| Current range | 0 ... 20 mA or 4 ... 20 mA | |
| Open loop voltage | max. 24 V DC | |
| Load | max. 650 &Omega | |
| Fault signal | downscale I &le 3.6 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| International approvals | ||
| UL approval | E223772 | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | NPN | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | M8 x 1 connector, 3-pin | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | terminals 23+, 24- or power feed module/Power Rail | |
| Rated voltage | 20 ... 30 V DC | |
| Rated current | approx. 100 mA | |
| Power dissipation/power consumption | &le 2 W / 2.2 W | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3, 4, 6 | |
| RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 | |
| Measuring current | approx. 400 µA | |
| Types of measuring | 2-, 3-, 4-wire technology | |
| Lead resistance | max. 50 &Omega | |
| Measurement loop monitoring | sensor breakage, sensor short-circuit | |
| Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) | |
| Cold junction compensation | external and internal | |
| Measurement loop monitoring | sensor breakage | |
| Potentiometer | 0.8 ... 20 k&Omega | |
| Types of measuring | 2-, 3-, 5-wire technology | |
| Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV | |
| Input resistance | &ge 250 k&Omega (0 ... 10 V) min. 1 M&Omega (0 ... 1 V, -100 ... 100 mV) | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
| Output I, II | relay | |
| Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 DC / 2 A | |
| Mechanical life | 5 x 107 switching cycles | |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
| Output III | Analog current output | |
| Current range | 0 ... 20 mA or 4 ... 20 mA | |
| Open loop voltage | max. 24 V DC | |
| Load | max. 650 &Omega | |
| Fault signal | downscale I &le 3.6 mA, upscale I &ge 21 mA (acc. NAMUR NE43) | |
| Collective error message | Power Rail | |
| Transfer characteristics | ||
| Sampling rate | approx. 700 ms | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | terminals 23, 24 | |
| Rated voltage | 20 ... 90 V DC or 48 ... 253 V AC | |
| Power dissipation | 2 W / 3 VA | |
| Power consumption | 2.2 W / 4 VA | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3 | |
| Input I | ||
| Input signal | 0/4 ... 20 mA | |
| Available voltage | > 15 V at 20 mA | |
| Open circuit voltage/short-circuit current | 24 V / 33 mA | |
| Input resistance | 45 &Omega (terminals 2, 3) | |
| Line fault detection | breakage I < 0.2 mA short-circuit I > 22 mA | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 Output: analog terminals 8+, 7- | |
| Output signal | 0 ... 20 mA or 4 ... 20 mA | |
| Output I, II | signal, relay | |
| Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 V DC / 2 A | |
| Mechanical life | 5 x 107 switching cycles | |
| Output III | Signal, analog | |
| Current range | 0 ... 20 mA or 4 ... 20 mA | |
| Open loop voltage | max. 24 V DC | |
| Load | max. 650 &Omega | |
| Fault signal | downscale I &le 3.6 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | NPN | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | terminals 23, 24 | |
| Rated voltage | 20 ... 90 V DC / 48 ... 253 V AC | |
| Power dissipation/power consumption | &le 2 W 2.5 VA / 2.2 W 3 VA | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3, 4, 6 | |
| RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 | |
| Measuring current | approx. 400 µA | |
| Types of measuring | 2-, 3-, 4-wire technology | |
| Lead resistance | max. 50 &Omega | |
| Measurement loop monitoring | sensor breakage, sensor short-circuit | |
| Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) | |
| Cold junction compensation | external and internal | |
| Measurement loop monitoring | sensor breakage | |
| Potentiometer | 0.8 ... 20 k&Omega | |
| Types of measuring | 2-, 3-, 5-wire technology | |
| Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV | |
| Input resistance | &ge 250 k&Omega (0 ... 10 V) min. 1 M&Omega (0 ... 1 V, -100 ... 100 mV) | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
| Output I, II | relay | |
| Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 DC / 2 A | |
| Mechanical life | 5 x 107 switching cycles | |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
| Output III | Analog current output | |
| Current range | 0 ... 20 mA or 4 ... 20 mA | |
| Open loop voltage | max. 24 V DC | |
| Load | max. 650 &Omega | |
| Fault signal | downscale I &le 3.6 mA, upscale I &ge 21 mA (acc. NAMUR NE43) | |
| Transfer characteristics | ||
| Sampling rate | approx. 700 ms | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Описание оборудования | ||
|---|---|---|
| 1-channel | ||
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | M8 x 1 connector, 3-pin | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | 16.8 ... 31.2 V DC | |
| Power dissipation | 0.9 W | |
| Power consumption | 1.3 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 5+, 6, 7- | |
| Input signal | 0/4 ... 20 mA | |
| Open circuit voltage/short-circuit current | &le 22 V / 30 mA | |
| Input resistance | max. 50 &Omega | |
| Transmission range | linearity range: -1 ... 110 % | |
| Available voltage | 16 V at 20 mA | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 3-, 4+ | |
| Ripple | &le 10 mV eff | |
| Transfer characteristics | ||
| Accuracy | max. 0.1 % of full-scale value | |
| Influence of ambient temperature | < 100 ppm/K of full-scale value | |
| Rise time/fall time | &le 3.5 ms | |
| Indicators/settings | ||
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
| Mass | approx. 70 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | DEMKO 16 ATEX 1750X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| IECEx approval | IECEx UL 16.0116X | |
| Approved for | Ex nA IIC T4 Gc | |
| Accessories | ||
| Optional accessories | power feed module S1SD-2PF Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | 16.8 ... 31.2 V DC | |
| Power dissipation | 0.9 W | |
| Power consumption | 1.3 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 5+, 6, 7- | |
| Input signal | 0/4 ... 20 mA | |
| Open circuit voltage/short-circuit current | &le 22 V / 30 mA | |
| Input resistance | 25 &Omega | |
| Transmission range | linearity range: -1 ... 110 % | |
| Available voltage | 16 V at 20 mA | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 3-, 4+ | |
| Ripple | &le 10 mV eff | |
| Transfer characteristics | ||
| Accuracy | max. 0.1 % of full-scale value | |
| Influence of ambient temperature | < 100 ppm/K of full-scale value | |
| Frequency range | 0 ... 100 Hz | |
| Rise time/fall time | &le 3.5 ms | |
| Indicators/settings | ||
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
| Mass | approx. 70 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | DEMKO 16 ATEX 1750X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| IECEx approval | IECEx UL 16.0116X | |
| Approved for | Ex nA IIC T4 Gc | |
| Accessories | ||
| Optional accessories | power feed module S1SD-2PF Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | 16.8 ... 31.2 V DC | |
| Power dissipation | 0.6 W | |
| Power consumption | 0.7 W | |
| Input | ||
| Connection side | field side | |
| Transmission range | linearity range: -1 ... 110 % | |
| Input I | ||
| Input signal | 0/4 ... 20 mA , max. 50 mA | |
| Input resistance | &le 25 &Omega | |
| Input II | ||
| Input signal | 0/2 ... 10 V , max. 30 V | |
| Input resistance | > 100 k&Omega | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 3-, 4+ | |
| Ripple | &le 10 mV eff | |
| Transfer characteristics | ||
| Accuracy | max. 0.1 % of full-scale value | |
| Influence of ambient temperature | < 100 ppm/K of full-scale value | |
| Frequency range | 0 ... 10 Hz , 0 ... 100 Hz , 0 ... 5 kHz | |
| Settling time | 70 ms , 7 ms , 150 µs | |
| Indicators/settings | ||
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
| Mass | approx. 70 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | DEMKO 16 ATEX 1750X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| IECEx approval | IECEx UL 16.0116X | |
| Approved for | Ex nA IIC T4 Gc | |
| Accessories | ||
| Optional accessories | power feed module S1SD-2PF Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | 16.8 ... 31.2 V DC | |
| Power dissipation | 0.6 W | |
| Power consumption | 0.8 W | |
| Input | ||
| Connection side | field side | |
| Transmission range | linearity range: unipolar -1 ... 110 % bipolar -110 ... 110 % | |
| Input I | ||
| Input signal | 0/4 ... 20 mA , 0/2 ... 10 mA , ± 10 mA, ± 20 mA , max. 50 mA | |
| Input resistance | &le 25 &Omega | |
| Input II | ||
| Input signal | 0/1 ... 5 V , 0/2 ... 10 V , ± 5 V , ± 10 V , max. 30 V | |
| Input resistance | > 1 M&Omega | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 3-, 4+ | |
| Ripple | &le 10 mV eff | |
| Transfer characteristics | ||
| Accuracy | max. 0.1 % of full-scale value | |
| Influence of ambient temperature | < 100 ppm/K of full-scale value | |
| Frequency range | 0 ... 100 Hz , 0 ... 8 kHz | |
| Settling time | 7 ms , 100 µs | |
| Indicators/settings | ||
| Control elements | DIP-switch potentiometer | |
| Configuration | via DIP switches via potentiometer | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
| Mass | approx. 70 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | DEMKO 16 ATEX 1750X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| IECEx approval | IECEx UL 16.0116X | |
| Approved for | Ex nA IIC T4 Gc | |
| Accessories | ||
| Optional accessories | power feed module S1SD-2PF Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP | |
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1640 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | 16.8 ... 31.2 V DC | |
| Power dissipation | 0.6 W | |
| Power consumption | 0.8 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 5+, 6- | |
| Input signal | ±60 mV, ±100 mV, ±150 mV, ±250 mV, ±300 mV, ±500 mV | |
| Input resistance | &ge 100 k&Omega | |
| Transmission range | linearity range: unipolar -1 ... 110 % bipolar -110 ... 110 % | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 3-, 4+ | |
| Ripple | &le 10 mV eff | |
| Transfer characteristics | ||
| Accuracy | max. 0.1 % of full-scale value | |
| Influence of ambient temperature | < 100 ppm/K of full-scale value | |
| Frequency range | 0 ... 100 Hz , 0 ... 8 kHz | |
| Settling time | 7 ms , 150 µs | |
| Indicators/settings | ||
| Control elements | DIP-switch potentiometer | |
| Configuration | via DIP switches via potentiometer | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
| Mass | approx. 70 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | DEMKO 16 ATEX 1750X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| IECEx approval | IECEx UL 16.0116X | |
| Approved for | Ex nA IIC T4 Gc | |
| Accessories | ||
| Optional accessories | power feed module S1SD-2PF Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP | |
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1640 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 6 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
Компания Zipstore.ru поставляет оптом и в розницу запчасти Pepperl+Fuchs.
В каталоге сайта представлено 13440 запчастей Pepperl+Fuchs. Также вы можете приобрести опции и аксессуары для расширения функциональных возможностей, транспортировки и эксплуатации оборудования. Запчасти в каталоге могут иметь полное название, каталожный номер, фотографию, краткое описание, а также модели принтеров, с которыми они совместимы.
Для оформления заказа вы можете воспользоваться одним из следующих способов:
Мы осуществляем поставки запчастей Pepperl+Fuchs во все города России, а также в Республику Беларусь, Казахстан и другие страны СНГ.
Продажа осуществляется за наличный и безналичный расчет. На сайте указаны розничные цены в рублях и долларах, с учетом НДС. Чтобы узнать оптовые цены на запчасти Pepperl+Fuchs, нужно отправить запрос по электронной почте. Подробнее о способах доставки и оплаты можно узнать в разделе сайта «Оплата и доставка». В разделе «%Скидки и акции» Вы можете найти наиболее выгодные предложения по продаже запчастей, а также сезонные скидки и акции.
При возникновении вопросов по обслуживанию, эксплуатации, ремонту Pepperl+Fuchs, Вы можете проконсультироваться со специалистами на форуме сайта.