| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | 16.8 ... 31.2 V DC | |
| Power dissipation | 0.8 W | |
| Power consumption | 1.4 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 5+, 6- | |
| Input signal | 0/4 ... 20 mA | |
| Open circuit voltage/short-circuit current | &le 22 V / 35 mA | |
| Input resistance | &le 25 &Omega | |
| Transmission range | linearity range: -1 ... 110 % | |
| Available voltage | 16 V at 20 mA | |
| Output | ||
| Connection side | control side | |
| Ripple | &le 10 mV eff | |
| Output I | ||
| Connection | terminals 3-, 4+ | |
| Output signal | 0/4 ... 20 mA, load &le 300 &Omega | |
| Output II | ||
| Connection | terminals 7+, 8- | |
| Output signal | 0/4 ... 20 mA, load &le 300 &Omega | |
| Transfer characteristics | ||
| Accuracy | max. 0.1 % of full-scale value | |
| Influence of ambient temperature | < 100 ppm/K of full-scale value | |
| Frequency range | 0 ... 100 Hz | |
| Rise time/fall time | &le 3.5 ms | |
| Indicators/settings | ||
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
| Mass | approx. 70 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | DEMKO 16 ATEX 1750X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| IECEx approval | IECEx UL 16.0116X | |
| Approved for | Ex nA IIC T4 Gc | |
| Accessories | ||
| Optional accessories | power feed module S1SD-2PF Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP | |
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | PNP | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.45 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.55 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 1400 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 2.5 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 250 mA | |
| Off-state current | 0 ... 0.01 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 1640 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| Protection class | II | |
| Rated insulation voltage | 60 V | |
| Rated impulse withstand voltage | 800 V | |
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M8 x 1 , 3-pin | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | 16.8 ... 31.2 V DC | |
| Power dissipation | 0.8 W | |
| Power consumption | 1.4 W | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 5+, 6- | |
| Input signal | 0/4 ... 20 mA | |
| Open circuit voltage/short-circuit current | &le 22 V / 35 mA | |
| Input resistance | &le 25 &Omega | |
| Transmission range | linearity range: -1 ... 110 % | |
| Available voltage | 16 V at 20 mA | |
| Output | ||
| Connection side | control side | |
| Ripple | &le 10 mV eff | |
| Output I | ||
| Connection | terminals 3-, 4+ | |
| Output signal | 0/1 ... 5 V, 0/2 ... 10 V , load &ge 5 k&Omega 0/4 ... 20 mA , load &le 300 &Omega | |
| Output II | ||
| Connection | terminals 7+, 8- | |
| Output signal | 0/1 ... 5 V, 0/2 ... 10 V , load &ge 5 k&Omega 0/4 ... 20 mA , load &le 300 &Omega | |
| Transfer characteristics | ||
| Accuracy | max. 0.1 % of full-scale value | |
| Influence of ambient temperature | < 100 ppm/K of full-scale value | |
| Frequency range | 0 ... 100 Hz | |
| Rise time/fall time | &le 3.5 ms | |
| Indicators/settings | ||
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
| Mass | approx. 70 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | DEMKO 16 ATEX 1750X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| IECEx approval | IECEx UL 16.0116X | |
| Approved for | Ex nA IIC T4 Gc | |
| Accessories | ||
| Optional accessories | power feed module S1SD-2PF Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP | |
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | Two-wire | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | AC/DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.7 | |
| Nominal ratings | ||
| Operating voltage | 20 ... 253 V AC/DC | |
| Switching frequency | 0 ... 25 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 7 V | |
| Momentary current (20 ms, 0.1 Hz) | 0 ... 2100 mA | |
| Operating current | 4 ... 250 mA AC 4 ... 100 mA DC | |
| Off-state current | &le 1.7 mA | |
| No-load supply current | &le 4 mA | |
| Operating voltage indicator | LED, green | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Digital Input | |
| Supply | ||
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | 16.8 ... 31.2 V DC | |
| Power dissipation | 0.6 W | |
| Power consumption | 1.1 W | |
| Input | ||
| Connection side | field side | |
| NAMUR sensor | ||
| Type | 2-wire | |
| Connection | terminals 5+, 6 | |
| Signal | acc. to EN 60947-5-6 (NAMUR) | |
| Sensor supply | 8 V | |
| Open-circuit | < 0.1 mA | |
| Switching point | 1.2 ... 2.1 mA | |
| Short-circuit | > 6 mA | |
| Input impedance | 1 k&Omega | |
| Mechanical contact | ||
| Type | 2-wire | |
| Connection | terminals 5+, 6 | |
| Sensor supply | 15 V | |
| External supply | &le 32 V | |
| Switching point | 8 ... 10 V / 1.2 ... 2.1 mA | |
| Input impedance | 4 k&Omega | |
| SN sensor | ||
| Type | 2-wire | |
| Connection | terminals 5+, 6 | |
| Sensor supply | 8 V | |
| Open-circuit | < 0.1 mA | |
| Switching point | 1.2 ... 2.1 mA | |
| Short-circuit | > 6 mA | |
| Input impedance | 1 k&Omega | |
| 2-wire DC sensor | ||
| Type | 2-wire | |
| Connection | terminals 5+, 6 | |
| Signal | acc. to EN 60947-5-2 | |
| Sensor supply | 16 V / 25 mA , short-circuit protected | |
| External supply | &le 32 V | |
| Switching point | 2 ... 5 mA | |
| Input impedance | 1 k&Omega | |
| S0 sensor | ||
| Type | 2-wire | |
| Connection | terminals 5+, 6 | |
| Signal | acc. to EN 62053-31 , Type B | |
| Sensor supply | 15 V | |
| Switching point | 0.15 ... 2 mA | |
| Input impedance | 4 k&Omega | |
| NPN sensor | ||
| Type | 3-wire | |
| Connection | terminals 5+, 6, 7- | |
| Signal | acc. to EN 60947-5-2 | |
| Sensor supply | 16 V / 25 mA , short-circuit protected | |
| External supply | &le 32 V | |
| Switching point | 3 ... 5 V | |
| Input impedance | 4 k&Omega | |
| PNP sensor | ||
| Type | 3-wire | |
| Connection | terminals 5+, 6, 7- | |
| Signal | acc. to EN 60947-5-2 | |
| Sensor supply | 16 V / 25 mA , short-circuit protected | |
| External supply | &le 32 V | |
| Switching point | 8 ... 10 V | |
| Input impedance | 4 k&Omega | |
| AC/DC voltage source | ||
| Connection | terminals 7, 8 | |
| Signal | 24 V AC/DC | |
| Switching point | 10 ... 15 V | |
| Input impedance | > 680 k&Omega | |
| AC/DC voltage source | ||
| Connection | terminals 7, 8 | |
| Signal | 115 V AC/DC | |
| Switching point | 40 ... 60 V | |
| Input impedance | > 680 k&Omega | |
| AC/DC voltage source | ||
| Connection | terminals 7, 8 | |
| Signal | 230 V AC/DC | |
| Switching point | 80 ... 115 V | |
| Input impedance | > 680 k&Omega | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 3, 4: | |
| Output | signal, relay | |
| Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/2 A/cos &phi > 0.7 30 V DC/2 A resistive load | |
| Minimum switch current | 2 mA / 24 V DC | |
| Energized/De-energized delay | &le 20 ms / &le 20 ms | |
| Mechanical life | 107 switching cycles | |
| Transfer characteristics | ||
| Switching frequency | &le 10 Hz | |
| Indicators/settings | ||
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
| Mass | approx. 60 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Accessories | ||
| Optional accessories | power feed module S1SD-2PF Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP | |
| General specifications | ||
|---|---|---|
| Signal type | Digital Input | |
| Supply | ||
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | 16.8 ... 31.2 V DC | |
| Power dissipation | 0.6 W | |
| Power consumption | 1.1 W | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| NAMUR sensor | ||
| Type | 2-wire | |
| Connection | terminals 5+, 6 | |
| Signal | acc. to EN 60947-5-6 (NAMUR) | |
| Sensor supply | 8 V | |
| Open-circuit | < 0.1 mA | |
| Switching point | 1.2 ... 2.1 mA | |
| Short-circuit | > 6 mA | |
| Input impedance | 1 k&Omega | |
| Mechanical contact | ||
| Type | 2-wire | |
| Connection | terminals 5+, 6 | |
| Sensor supply | 15 V | |
| External supply | &le 32 V | |
| Switching point | 8 ... 10 V / 1.2 ... 2.1 mA | |
| Frequency | 0 ... 50 Hz , debounce filter | |
| Input impedance | 4 k&Omega | |
| SN sensor | ||
| Type | 2-wire | |
| Connection | terminals 5+, 6 | |
| Sensor supply | 8 V | |
| Open-circuit | < 0.1 mA | |
| Switching point | 1.2 ... 2.1 mA | |
| Short-circuit | > 6 mA | |
| Input impedance | 1 k&Omega | |
| 2-wire DC sensor | ||
| Type | 2-wire | |
| Connection | terminals 5+, 6 | |
| Signal | acc. to EN 60947-5-2 | |
| Sensor supply | 16 V / 25 mA , short-circuit protected | |
| External supply | &le 32 V | |
| Switching point | 2 ... 5 mA | |
| Input impedance | 1 k&Omega | |
| S0 sensor | ||
| Type | 2-wire | |
| Connection | terminals 5+, 6 | |
| Signal | acc. to EN 62053-31 , Type B | |
| Sensor supply | 15 V | |
| Switching point | 0.15 ... 2 mA | |
| Input impedance | 4 k&Omega | |
| NPN sensor | ||
| Type | 3-wire | |
| Connection | terminals 5+, 6, 7- | |
| Signal | acc. to EN 60947-5-2 | |
| Sensor supply | 16 V / 25 mA , short-circuit protected | |
| External supply | &le 32 V | |
| Switching point | 3 ... 5 V | |
| Input impedance | 4 k&Omega | |
| PNP sensor | ||
| Type | 3-wire | |
| Connection | terminals 5+, 6, 7- | |
| Signal | acc. to EN 60947-5-2 | |
| Sensor supply | 16 V / 25 mA , short-circuit protected | |
| External supply | &le 32 V | |
| Switching point | 8 ... 10 V | |
| Input impedance | 4 k&Omega | |
| AC/DC voltage source | ||
| Connection | terminals 6, 7- | |
| Signal | max. ± 30 V | |
| Switching point | 150 ... 400 mV | |
| Input impedance | 4 k&Omega | |
| Function input | ||
| Connection | terminal 8 | |
| Open loop voltage | 7.5 V | |
| Input impedance | approx. 50 k&Omega | |
| Function 1 | activation start-up override | |
| Switching point | < 3 V , edge triggered | |
| Adjustment range | 1 ... 6500 s | |
| Function 2 | reset restart inhibit | |
| Switching point | > 12 V , edge triggered | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 3, 4: | |
| Output | signal, relay | |
| Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 30 V DC/2 A resistive load | |
| Minimum switch current | 2 mA / 24 V DC | |
| Energized/De-energized delay | &le 20 ms / &le 20 ms | |
| Mechanical life | 107 switching cycles | |
| Transfer characteristics | ||
| Accuracy | max. 0.1 % of the measurement value | |
| Measuring time | &le 100 ms | |
| Influence of ambient temperature | < 100 ppm/K of the measured value | |
| Frequency range | 0.01 ... 50000 Hz | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Control elements | DIP-switch | |
| Configuration | via DIP switches via software | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
| Mass | approx. 60 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Accessories | ||
| Optional accessories | power feed module S1SD-2PF adapter with USB interface S-ADP-USB Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP splitter VAZ-CHAIN-BU/BN70MM/1,0-25 | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | 16.8 ... 31.2 V DC | |
| Power dissipation | 0.7 W | |
| Power consumption | 0.8 W | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 5, 6, 7, 8 | |
| PTC | type KT, KTY, ST | |
| Measuring current | approx. 200 µA | |
| Types of measuring | 2-, 3-, 4-wire connection | |
| Lead resistance | &le 100 &Omega per line | |
| Measurement loop monitoring | sensor breakage, lead breakage, short circuit | |
| RTD | type Pt100, Pt200, Pt500, Pt1000 (EN 60751: 1995) type Ni100, Ni200, Ni500, Ni1000 (DIN 43760) | |
| Measuring current | approx. 200 µA | |
| Types of measuring | 2-, 3-, 4-wire connection | |
| Lead resistance | max. 100 &Omega per line | |
| Measurement loop monitoring | sensor breakage, lead breakage, short circuit | |
| Thermocouples | type B, E, J, K, N, S, T (IEC 584-1:1995) type L, U (DIN 43710:1985) type C, D (ASTM E988) | |
| Cold junction compensation | external (Pt100) and internal , manually | |
| Lead resistance | max. 10 k&Omega | |
| Measurement loop monitoring | sensor breakage, lead breakage | |
| Resistor | ||
| Measurement range | 0 ... 5 k&Omega | |
| Potentiometer | 0.2 ... 50 k&Omega | |
| Types of measuring | 3-wire connection | |
| Voltage | -100 ... 100 mV -1000 ... 1000 mV | |
| Input resistance | &ge 1 M&Omega | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 3-, 4+ | |
| Ripple | &le 10 mV eff | |
| Fault signal | downscale or upscale | |
| Transfer characteristics | ||
| Accuracy | max. 0.1 % of full-scale value | |
| Measuring time | &le 300 ms | |
| Influence of ambient temperature | < 100 ppm/K of full-scale value | |
| Indicators/settings | ||
| Control elements | DIP-switch keys | |
| Configuration | via DIP switches via keys via software | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
| Mass | approx. 70 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | DEMKO 16 ATEX 1750X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| IECEx approval | IECEx UL 16.0116X | |
| Approved for | Ex nA IIC T4 Gc | |
| Accessories | ||
| Optional accessories | power feed module S1SD-2PF adapter with USB interface S-ADP-USB Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | Two-wire | |
| Rated operating distance | 4 mm | |
| Installation | flush | |
| Output polarity | AC/DC | |
| Assured operating distance | 0 ... 3.24 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.7 | |
| Nominal ratings | ||
| Operating voltage | 20 ... 253 V AC/DC | |
| Switching frequency | 0 ... 25 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 7 V | |
| Momentary current (20 ms, 0.1 Hz) | 0 ... 2100 mA | |
| Operating current | 4 ... 250 mA AC 4 ... 100 mA DC | |
| Off-state current | &le 1.7 mA | |
| No-load supply current | &le 4 mA | |
| Operating voltage indicator | LED, green | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | PA | |
| Sensing face | PA | |
| Degree of protection | IP67 | |
| Tightening torque, fastening screws | Threading M3 max: 1.1 Nm | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Bus or terminals 1-, 2+ | |
| Rated voltage | 16.8 ... 31.2 V DC | |
| Power dissipation | 0.6 W | |
| Power consumption | 0.8 W | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Transmission range | linearity range: unipolar -1 ... 110 % bipolar -110 ... 110 % | |
| Input I | ||
| Input signal | 0/4 ... 20 mA , 0/2 ... 10 mA , ± 10 mA, ± 20 mA , max. 50 mA | |
| Input resistance | &le 25 &Omega | |
| Input II | ||
| Input signal | 0/1 ... 5 V , 0/2 ... 10 V , ± 5 V , ± 10 V , max. 30 V | |
| Input resistance | > 1 M&Omega | |
| Input III | ||
| Connection | terminals 5+, 6- | |
| Input signal | 0/4 ... 20 mA | |
| Available voltage | 16 V at 20 mA | |
| Open circuit voltage/short-circuit current | &le 22 V / 30 mA | |
| Input IV | ||
| Connection | terminals 5, 7 | |
| Input type | reset restart inhibit | |
| Output | ||
| Connection side | control side | |
| Connection | terminals 3, 4: | |
| Output | signal, relay | |
| Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/2 A/cos &phi > 0.7 30 V DC/2 A resistive load | |
| Minimum switch current | 2 mA / 24 V DC | |
| Energized/De-energized delay | &le 20 ms / &le 20 ms | |
| Mechanical life | 107 switching cycles | |
| Collective error message | Power Bus | |
| Transfer characteristics | ||
| Accuracy | max. 0.1 % of full-scale value | |
| Influence of ambient temperature | < 100 ppm/K of full-scale value | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Control elements | DIP-switch keys | |
| Configuration | via DIP switches via keys via software | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 14 AWG) | |
| Mass | approx. 70 g | |
| Dimensions | 6.2 x 97 x 107 mm (0.24 x 3.82 x 4.21 inch) , housing type S1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Accessories | ||
| Optional accessories | power feed module S1SD-2PF Power Bus POWERBUS-SETL5.*** Power Bus POWERBUS-SETH5.*** cover for DIN mounting rail POWERBUS-COV.250 end cap POWERBUS-CAP | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Motherboard based | |
| Supply | ||
| Rated voltage | 19.2 ... 35 V | |
| Rated current | 110 ... 30 mA | |
| Power dissipation | max. 2 W | |
| Fieldbus interface | ||
| Number of segments | 4 | |
| Fieldbus type | FOUNDATION Fieldbus/PROFIBUS PA | |
| Rated voltage | 9 ... 32 V | |
| Indicators/operating means | ||
| LED PRI PWR | green: on, primary bulk power supply connected | |
| LED SEC PWR | green: on, secondary bulk power supply connected | |
| LED Seg 1...4 | yellow: bus activity red 2 Hz flashing: alarm red: hardware error | |
| Fault signal | VFC alarm 1 A, 50 V DC, normally closed | |
| DIP switch | diagnostic address 1...247, binary coded | |
| Galvanic isolation | ||
| Fieldbus segment/Fieldbus segment | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Fieldbus segment/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Standard conformity | ||
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | < 95 % non-condensing | |
| Shock resistance | 15 g 11 ms | |
| Vibration resistance | 1 g , 10 ... 150 Hz | |
| Pollution degree | max. 2, according to IEC 60664 | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Connection type | motherboard specific | |
| Core cross-section | motherboard specific | |
| Housing material | Polycarbonate | |
| Housing width | 18 mm | |
| Housing height | 106 mm | |
| Housing depth | 128 mm | |
| Degree of protection | IP20 | |
| Mass | approx. 100 g | |
| Mounting | motherboard mounting | |
| Mating cycles | 100 | |
| Data for application in connection with hazardous areas | ||
| Certificate | TÜV 04 ATEX 2500 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | CoC 3024816, CoC 3024816C | |
| Approved for | Class I, Division 2, Groups A, B, C, D, T4 / Class I, Zone 2, AEx/Ex nA IIC T4 | |
| IECEx approval | IECEx TUN 13.0038X | |
| Approved for | Ex nA IIC T4 Gc | |
| Certificates and approvals | ||
| Marine approval | DNV A-14038 | |
| Patents | This product may be covered by the following patent: US7,698,103 | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Motherboard based | |
| Supply | ||
| Rated voltage | 19.2 ... 35 V DC SELV/PELV | |
| Rated current | 120 ... 70 mA | |
| Power dissipation | max. 2.5 W | |
| Fieldbus interface | ||
| Fieldbus type | FOUNDATION Fieldbus | |
| Physical layer profile | profile type 114 | |
| ITK version | 6 | |
| Implementation | resource block function block transducer block | |
| Firmware update | Ethernet | |
| Polarity | polarity-sensitive | |
| Rated voltage | 9 ... 35 V SELV/PELV | |
| Rated current | 0 mA | |
| Ethernet Interface | ||
| Port | 100 BASE-TX | |
| Protocol | TCP/IP and UDP/IP | |
| Services | ICMP , DHCP , AutoIP , HTTP | |
| Connection type | RJ-45 socket, 8-pin | |
| Transfer rate | 100 MBit/s | |
| Diagnostic Bus | ||
| Number of Diagnostic Bus Channels | 2 | |
| Number of Diagnostic Modules/Channel | 31 Using Ethernet Interface , 8 Using Fieldbus Interface | |
| Termination | integrated | |
| Cable length/Channel | 30 m | |
| Indicators/operating means | ||
| LED ERR | red: Hardware fault | |
| LED PWR | green: Power on | |
| LINK/ACT | yellow | |
| CH1, CH2 | yellow: diagnostic bus activity | |
| Outputs | ||
| Output I | alarm output diagnostic bus channel 1 , volt-free contact , NC contact | |
| Voltage | 50 V DC | |
| Current | max. 1 A | |
| Output II | alarm output diagnostic bus channel 2 , volt-free contact , NC contact | |
| Voltage | 50 V DC | |
| Current | max. 1 A | |
| Output III | common alarm , volt-free contact , NC contact | |
| Voltage | 50 V DC | |
| Current | max. 1 A | |
| Galvanic isolation | ||
| All circuits/FE | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Output I, II/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff | |
| Ethernet/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Ethernet/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Fieldbus/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Diagnostic Bus/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Low voltage | ||
| Directive 73/23/EEC | EN 61010 | |
| Standard conformity | ||
| Galvanic isolation | IEC 62103 | |
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Climatic conditions | DIN IEC 721 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ethernet | IEEE 802.3 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) hazardous area -40 ... 70 °C (-40 ... 158 °F) safe area horizontal DIN rail mounting | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | < 95 % non-condensing | |
| Shock resistance | 15 g 11 ms | |
| Vibration resistance | 1 g , 10 ... 150 Hz | |
| Pollution degree | max. 2, according to IEC 60664 | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Housing material | Polycarbonate | |
| Housing width | see dimensions | |
| Housing height | see dimensions | |
| Housing depth | see dimensions | |
| Degree of protection | IP20 | |
| Mass | 470 g | |
| Mounting | DIN rail mounting | |
| Data for application in connection with hazardous areas | ||
| Certificate | TÜV 14 ATEX 115980 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| IECEx approval | IECEx TUN 14.0003X | |
| Approved for | Ex nA IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 5 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 4.05 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.25 | |
| Reduction factor r304 | 0.7 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1000 Hz | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 100 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 2010 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M12 x 1 , 4-pin | |
| Housing material | stainless steel 1.4404 / AISI 316L | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Motherboard based | |
| Supply | ||
| Rated voltage | 19.2 ... 35 V DC SELV/PELV | |
| Rated current | 210 ... 120 mA | |
| Power dissipation | max. 4.2 W | |
| Fieldbus interface | ||
| Fieldbus type | FOUNDATION Fieldbus | |
| Physical layer profile | profile type 114 | |
| ITK version | 6 | |
| Implementation | resource block function block transducer block | |
| Firmware update | Ethernet | |
| Polarity | polarity-sensitive | |
| Rated voltage | 9 ... 35 V SELV/PELV | |
| Rated current | 0 mA | |
| Connection to power link | ||
| Connection | ||
| Ethernet Interface | ||
| Rated voltage | max. 35 V SELV/PELV | |
| Port | 100 BASE-TX | |
| Protocol | TCP/IP and UDP/IP | |
| Services | ICMP , DHCP , AutoIP , HTTP | |
| Connection type | RJ-45 socket, 8-pin | |
| Transfer rate | 100 MBit/s | |
| Diagnostic Bus | ||
| Connection | only for the connection to protected circuits | |
| Rated voltage | max. 35 V | |
| Number of Diagnostic Bus Channels | 2 | |
| Number of Diagnostic Modules/Channel | 31 Using Ethernet Interface , 8 Using Fieldbus Interface | |
| Termination | integrated | |
| Cable length/Channel | 30 m | |
| Indicators/operating means | ||
| LED ERR | red: Hardware fault | |
| LED PWR | green: Power on | |
| Fault signal | buzzer on | |
| LINK/ACT | yellow | |
| CH1, CH2 | yellow: diagnostic bus activity | |
| Inputs | ||
| Input I, II | ||
| Input type | selectable: Frequency input , NAMUR/mechanical contact | |
| Frequency | ||
| Connection | only passive load | |
| Rated voltage | max. 35 V | |
| Input frequency | 0.3 Hz to 1 kHz | |
| Pulse duration | min. 50 µs | |
| Accuracy | ± 1 % | |
| Cable length | max. 30 m | |
| Line fault detection | lead breakage , short-circuit | |
| NAMUR | ||
| Sensor type | NAMUR sensor according to DIN EN 60947-6 | |
| Connection | only passive load | |
| Rated voltage | max. 35 V | |
| Switching frequency | 10 Hz | |
| Cable length | max. 30 m | |
| Line fault detection | lead breakage , short circuit | |
| Input III, IV | ||
| Input type | NAMUR/mechanical contact | |
| NAMUR | ||
| Sensor type | NAMUR sensor according to DIN EN 60947-6 | |
| Connection | only passive load | |
| Rated voltage | max. 35 V | |
| Switching frequency | 10 Hz | |
| Cable length | max. 30 m | |
| Line fault detection | lead breakage , short circuit | |
| Input V | ||
| Input type | selectable: diagnostic bus CH 1 alarm input , NAMUR/mechanical contact | |
| Alarm Input | ||
| Connection | only passive load | |
| Rated voltage | max. 35 V | |
| Cable length | max. 30 m | |
| Line fault detection | lead breakage , short circuit | |
| NAMUR | ||
| Sensor type | NAMUR sensor according to DIN EN 60947-6 | |
| Connection | only passive load | |
| Rated voltage | max. 35 V | |
| Switching frequency | 10 Hz | |
| Cable length | max. 30 m | |
| Line fault detection | lead breakage , short circuit | |
| Input VI | ||
| Input type | selectable: diagnostic bus CH 2 alarm input , NAMUR/mechanical contact | |
| Alarm Input | ||
| Connection | only passive load | |
| Rated voltage | max. 35 V | |
| Cable length | max. 30 m | |
| Line fault detection | lead breakage , short-circuit | |
| NAMUR | ||
| Sensor type | NAMUR sensor according to DIN EN 60947-6 | |
| Connection | only passive load | |
| Rated voltage | max. 35 V | |
| Switching frequency | 10 Hz | |
| Cable length | max. 30 m | |
| Line fault detection | lead breakage , short circuit | |
| Input VII, VIII | ||
| Input type | selectable: Pt100 4-wire temperature input , NAMUR/mechanical contact | |
| Temperature | ||
| Connection | only passive load | |
| Rated voltage | max. 35 V | |
| Measurement range | -50 ... 90 °C (-58 ... 194 °F) | |
| Accuracy | 1 K | |
| Measuring current | 1 mA | |
| Lead resistance | 4.2 &Omega per line | |
| Cable length | max. 30 m | |
| Line fault detection | lead breakage , short-circuit | |
| NAMUR | ||
| Sensor type | NAMUR sensor according to DIN EN 60947-6 | |
| Connection | only passive load | |
| Rated voltage | max. 35 V | |
| Switching frequency | 10 Hz | |
| Cable length | max. 30 m | |
| Line fault detection | lead breakage , short circuit | |
| Humidity | ||
| Measurement range | 0 ... 95 % RH | |
| Accuracy | 2 % RH | |
| Resolution | 0.04 % | |
| Outputs | ||
| Output I | ||
| Output type | selectable: diagnostic bus CH 1 , relay , NO contact | |
| Contact loading | 250 V AC/ 6 A resistive load | |
| Mechanical life | 1 x 105 switching cycles | |
| Response time | turn-on time 7 ms , turn-off time 3 ms | |
| Switching frequency | 6 min-1 full load, 1200 min-1 without load | |
| Output II | ||
| Output type | selectable: diagnostic bus CH 2 , relay , NO contact | |
| Contact loading | 250 V AC/ 6 A resistive load | |
| Mechanical life | 1 x 105 switching cycles | |
| Response time | turn-on time 7 ms , turn-off time 3 ms | |
| Switching frequency | 6 min-1 full load, 1200 min-1 without load | |
| Output III | ||
| Output type | selectable: common alarm , volt-free contact , NC contact | |
| Connection | only for the connection to protected circuits | |
| Voltage | 50 V DC | |
| Current | max. 1 A | |
| Output IV | ||
| Output type | common alarm , buzzer | |
| Galvanic isolation | ||
| All circuits/FE | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Output I, II/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 250 Veff | |
| Ethernet/Supply | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Ethernet/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Fieldbus/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Diagnostic Bus/other circuits | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Low voltage | ||
| Directive 73/23/EEC | EN 61010 | |
| Standard conformity | ||
| Galvanic isolation | IEC 62103 | |
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Climatic conditions | DIN IEC 721 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ethernet | IEEE 802.3 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) hazardous area -40 ... 70 °C (-40 ... 158 °F) safe area horizontal DIN rail mounting | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | < 95 % non-condensing | |
| Shock resistance | 5 g 11 ms | |
| Vibration resistance | 1 g , 10 ... 150 Hz | |
| Pollution degree | max. 2, according to IEC 60664 | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Housing material | Polycarbonate | |
| Housing width | see dimensions | |
| Housing height | see dimensions | |
| Housing depth | see dimensions | |
| Degree of protection | IP20 | |
| Mass | 500 g | |
| Mounting | DIN rail mounting | |
| Data for application in connection with hazardous areas | ||
| FOUNDATION Fieldbus | ||
| Connection | For connection to circuits with safe limited voltage according to IEC 60079-11:2011, type of protection "ic" | |
| Voltage | max. 35 V | |
| Certificate | TÜV 14 ATEX 115980 X | |
| Marking | Motherboard MB-FB-GT.AD.FF.IO II 3 G Ex nA nC IIC T4 Gc , Gateway II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| IECEx approval | IECEx TUN 14.0003X | |
| Approved for | Motherboard Ex nA nC IIC T4 Gc , Gateway Ex nA IIC T4 Gc | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Motherboard based | |
| Supply | ||
| Rated voltage | 19.2 ... 35 V | |
| Rated current | 40 ... 25 mA | |
| Power dissipation | max. 1 W | |
| Fieldbus interface | ||
| Number of segments | 4 | |
| Fieldbus type | FOUNDATION Fieldbus/PROFIBUS PA | |
| Rated voltage | 9 ... 32 V | |
| Indicators/operating means | ||
| LED PRI PWR | green: on, primary bulk power supply connected | |
| LED SEC PWR | green: on, secondary bulk power supply connected | |
| LED Seg 1...4 | yellow: bus activity yellow 2 Hz flashing: Maintenance required red 2 Hz flashing: specification limit violated red: hardware error | |
| Fault signal | VFC alarm 1 A, 50 V DC, normally closed | |
| DIP switch | fieldbus type , redundant supply , Signal level , Noise level , Jitter | |
| Galvanic isolation | ||
| Fieldbus segment/Fieldbus segment | functional insulation acc. to IEC 62103, rated insulation voltage 50 Veff | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Standard conformity | ||
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | < 95 % non-condensing | |
| Shock resistance | 15 g 11 ms | |
| Vibration resistance | 1 g , 10 ... 150 Hz | |
| Pollution degree | max. 2, according to IEC 60664 | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Connection type | motherboard specific | |
| Core cross-section | motherboard specific | |
| Housing material | Polycarbonate | |
| Housing width | 18 mm | |
| Housing height | 106 mm | |
| Housing depth | 128 mm | |
| Degree of protection | IP20 | |
| Mass | approx. 100 g | |
| Mounting | motherboard mounting | |
| Data for application in connection with hazardous areas | ||
| Certificate | TÜV 04 ATEX 2500 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| IECEx approval | IECEx TUN 13.0038X | |
| Approved for | Ex nA IIC T4 Gc | |
| Certificates and approvals | ||
| Marine approval | DNV A-14038 | |
| Patents | This product may be covered by the following patent: US7,698,103 | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Outside installation | |
| Electronic component | Binary multi-input/output R8D0-MIO-Ex12.FF* For technical data on installed electronic component see data sheet. | |
| Fieldbus interface | ||
| Fieldbus type | FOUNDATION Fieldbus | |
| Galvanic isolation | ||
| Foundation Fieldbus/Field circuit | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Standard conformity | ||
| Galvanic isolation | EN 60079-11 | |
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g , 11 ms | |
| Vibration resistance | 10 g , 10 ... 150 Hz | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Connection type | plug-in terminals , spring terminal and screw terminal | |
| Core cross-section | ||
| Bus | up to 2.5 mm2 | |
| Inputs | up to 2.5 mm2 | |
| Cable diameter | see table 2 | |
| Cable gland | sensor inputs M16, fieldbus M20 | |
| Housing material | EN 1780-1 46000 , ISO AlSi9Cu3(Fe) , anodized | |
| Degree of protection | IP66 | |
| Mass | 1800 g | |
| Mounting | panel mounting | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BVS 16 ATEX E 075 X | |
| Marking | II 2 (1) G Ex ib [ia Ga] IIC T4 Gb , II 3 (1) G Ex ic [ia Ga] IIC T4 Gc , II 3 (1) G Ex ec [ia Ga] IIC T4 Gc , I (M1) [Ex ia Ma] I , II (1) D [Ex ia Da] IIIC , II 2 (1) D Ex tb [ia Da] IIIC T130 °C Db | |
| Bus | FISCO see EC-Type Examination Certificate | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
| International approvals | ||
| IECEx approval | IECEx BVS 16.0051X | |
| Approved for | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ec [ia Ga] IIC T4 Gc , [Ex ia Ma] I , [Ex ia Da] IIIC , Ex tb [ia Da] IIIC T130 °C Db | |
| Certificates and approvals | ||
| Marine approval | pending | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | NPN | |
| Rated operating distance | 5 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 4.05 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.25 | |
| Reduction factor r304 | 0.7 | |
| Reduction factor rSt37 | 1 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1000 Hz | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.34 mm2 | |
| Housing material | PBT | |
| Sensing face | PBT | |
| Housing diameter | 18 mm | |
| Degree of protection | IP68 / IP69K | |
| Note | use only delivered nuts | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Outside installation | |
| Electronic component | Temperature Multi-Input Device RD0-TI-Ex8.FF* For technical data on installed electronic component see data sheet. | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Standard conformity | ||
| Galvanic isolation | EN 60079-11 | |
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | see table 1 | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g , 11 ms | |
| Vibration resistance | 10 g , 10 ... 150 Hz | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Connection type | plug-in terminals , spring terminal and screw terminal | |
| Core cross-section | ||
| Bus | up to 2.5 mm2 | |
| Inputs | up to 2.5 mm2 | |
| Cable diameter | see table 2 | |
| Cable gland | sensor inputs M16, fieldbus M20 | |
| Housing material | EN 1780-1 46000 , ISO AlSi9Cu3(Fe) , anodized | |
| Degree of protection | IP67 | |
| Mass | 1800 g | |
| Mounting | panel mounting | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2237 | |
| Marking | II 2 (1) G Ex ia [ia Ga] IIC T4 Gb , II (1) G [Ex ia Ga] IIC , II (1) D [Ex ia Da] IIIC , II 3 G Ex ic IIC T4 Gc | |
| Bus | FISCO see EC-Type Examination Certificate | |
| Inputs | see EC-Type Examination Certificate | |
| Certificate | PTB 03 ATEX 2238 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Bus | see Statement of Conformity | |
| Input | see EC-Type Examination Certificate | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| IECEx approval | IECEx PTB 05.0001 , IECEx PTB 05.0002X | |
| Approved for | Ex ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc | |
| Certificates and approvals | ||
| Marine approval | DNV A-14038 | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Cabinet installation | |
| Fieldbus interface | ||
| Fieldbus type | FOUNDATION Fieldbus | |
| Physical layer profile | profile type 511 (FISCO), profile type 111 (Entity) | |
| ITK version | 6.1.1 | |
| Implementation | resource block 1x RS function block 4x DO, 12x DI, 1x AI, 2x MDI, 1x MDO transducer block 4x TB | |
| FDE (Fault Disconnect Equipment) | 6.7 mA | |
| Polarity | not polarity sensitive | |
| Rated voltage | 9 ... 32 V | |
| Rated current | max. 23 mA | |
| Indicators/operating means | ||
| LED PWR | green: on, bus voltage existent | |
| LED COM ERR | red, continuous lightning: hardware error red, flashing: no bus activities or bus fault off: no error | |
| LED CHANNEL ERROR | red, flashing: lead breakage/short circuit off: no error | |
| DIP switch | Address setting , write protection , simulation | |
| Analog input | ||
| Number of inputs | 1 | |
| Input type | Frequency input / Counter Input , channel 1 | |
| Switching frequency | min. 0.1 Hz max. 5 kHz | |
| Pulse duration | min. 80 µs | |
| Supply voltage | 5 V | |
| Supply current | 5 mA | |
| Line fault detection | lead breakage , short circuit (not in counter mode) | |
| Digital input | ||
| Number of inputs | 12 | |
| Input type | Sensor input , channels 1, 4, 7, 10 multiplexed , cycle adjustable | |
| Supply voltage | 6.6 V | |
| Supply current | 5 mA | |
| Line fault detection | lead breakage , short circuit | |
| Input type | Sensor input , channels 2, 3, 5, 6, 8, 9, 11, 12 multiplexed , cycle fixed | |
| Supply voltage | 5 V | |
| Supply current | 5 mA | |
| Time delay before availability | 2 ms | |
| Line fault detection | lead breakage , short circuit | |
| Digital output | ||
| Number of outputs | 4 | |
| Output type | Low power valve , channels 1, 4, 7, 10 | |
| Supply voltage | 6.6 V | |
| Supply current | 1.5 mA | |
| Line fault detection | lead breakage , short circuit | |
| Galvanic isolation | ||
| Foundation Fieldbus/Field circuit | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Standard conformity | ||
| Galvanic isolation | EN 60079-11 | |
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC/EN 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | -50 ... 75 °C (-58 ... 167 °F) hazardous area -50 ... 85 °C (-58 ... 185 °F) safe area | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g , 11 ms | |
| Vibration resistance | 5 g , 10 ... 150 Hz | |
| Pollution degree | 2 | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Connection type | plug-in terminals , spring terminal and screw terminal | |
| Core cross-section | ||
| Bus | up to 2.5 mm2 | |
| Inputs | up to 2.5 mm2 | |
| Housing material | Polycarbonate | |
| Degree of protection | IP20 | |
| Mass | approx. 290 g | |
| Mounting | mounting on DIN rail in cabinet | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BVS 16 ATEX E 075 X | |
| Marking | II 2 (1) G Ex ib [ia Ga] IIC T4 Gb , II 3 (1) G Ex ic [ia Ga] IIC T4 Gc , II 3 (1) G Ex ec [ia Ga] IIC T4 Gc , I (M1) [Ex ia Ma] I , II (1) D [Ex ia Da] IIIC | |
| Field-side | ||
| Voltage | 9 V | |
| Current | 43 mA | |
| Power | 96 mW | |
| FOUNDATION Fieldbus | ||
| Maximum safe voltage | 253 V | |
| Voltage | 24 V | |
| Current | 380 mA | |
| Power | 5.32 W | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-7:2015 | |
| International approvals | ||
| IECEx approval | IECEx BVS 16.0051X | |
| Approved for | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ec [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I | |
| Certificates and approvals | ||
| Marine approval | pending | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Cabinet installation | |
| Fieldbus interface | ||
| Fieldbus type | FOUNDATION Fieldbus | |
| Physical layer profile | profile type 511 (FISCO), profile type 111 (Entity) | |
| ITK version | 4.51 | |
| Implementation | resource block function block transducer block | |
| Execution time | AI, MAI 40 ms max. | |
| Macro cycle | typical for one device 8xAI or 1xMAI max. 500 ms | |
| Firmware update | via separate plug connection | |
| FDE (Fault Disconnect Equipment) | 6.7 mA | |
| Polarity | not polarity sensitive | |
| Rated voltage | 9 ... 32 V | |
| Rated current | max. 23 mA | |
| Indicators/operating means | ||
| LED PWR | green: on, bus voltage existent | |
| LED COM ERR | red: continuous lightning: hardware error 2 Hz flashing: no bus activities or bus fault off: no error | |
| LED CHANNEL ERROR | red: 2 Hz flashing: lead breakage, overrange off: no error | |
| Input | ||
| Number | 8 | |
| Sensor types | see table 1 | |
| Grounding | grounding of thermoelements possible | |
| Error detection | lead breakage, wiring error, hardware device error | |
| Common mode voltage | Input to Input 600 Vpeak | |
| Transfer characteristics | ||
| Deviation | ||
| Influence of ambient temperature | see table 3 | |
| Linearization | T/C input 0.1°C RTD input 0.03°C | |
| Internal measurement cycle | for all sensor types max. 1 s | |
| Galvanic isolation | ||
| Fieldbus/inputs | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Standard conformity | ||
| Galvanic isolation | EN 60079-11 | |
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area -40 ... 85 °C (-40 ... 185 °F) safe area | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g , 11 ms | |
| Vibration resistance | 5 g , 10 ... 150 Hz | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Connection type | plug-in terminals , spring terminal and screw terminal | |
| Core cross-section | ||
| Bus | up to 2.5 mm2 | |
| Inputs | up to 2.5 mm2 | |
| Housing material | Polycarbonate | |
| Degree of protection | IP20 | |
| Mass | 360 g | |
| Mounting | mounting on DIN rail in cabinet | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | PTB 03 ATEX 2237 | |
| Group, category, type of protection, temperature class | II 2 (1) G Ex ia [ia Ga] IIC T4 Gb , II (1) G [Ex ia Ga] IIC , II (1) D [Ex ia Da] IIIC , II 3 G Ex ic IIC T4 Gc | |
| Bus | FISCO see EC-Type Examination Certificate | |
| Inputs | see EC-Type Examination Certificate | |
| Statement of conformity | PTB 03 ATEX 2238 X | |
| Group, category, type of protection, temperature class | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Bus | see Statement of Conformity | |
| Input | see EC-Type Examination Certificate | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| IECEx approval | IECEx PTB 05.0001 , IECEx PTB 05.0002X | |
| Approved for | Ex ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc | |
| Certificates and approvals | ||
| Marine approval | DNV A-14038 | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | NPN | |
| Rated operating distance | 5 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 4.05 mm | |
| Reduction factor rAl | 0.35 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.4 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 5 ... 60 V | |
| Switching frequency | 0 ... 1500 Hz | |
| Hysteresis | typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Inductive overvoltage protection | yes | |
| Surge suppression | yes | |
| Voltage drop | &le 2 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 7 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 846 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
| CSA approval | cCSAus Listed, General Purpose, Class 2 Power Source | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| E1 Type approval | 10R-04 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | cable PUR , 2 m | |
| Core cross-section | 3 x 0.75 mm2 | |
| Housing material | PBT | |
| Sensing face | PBT | |
| Housing diameter | 18 mm | |
| Degree of protection | IP68 / IP69K | |
| Mass | 120 g | |
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | NPN | |
| Rated operating distance | 5 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 4.05 mm | |
| Reduction factor rAl | 0.35 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.8 | |
| Reduction factor rBrass | 0.4 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 5 ... 60 V | |
| Switching frequency | 0 ... 1500 Hz | |
| Hysteresis | typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Inductive overvoltage protection | yes | |
| Surge suppression | yes | |
| Voltage drop | &le 2 V | |
| Rated insulation voltage | 60 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 7 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 846 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose, Class 2 Power Source | |
| CSA approval | cCSAus Listed, General Purpose, Class 2 Power Source | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| E1 Type approval | 10R-04 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | cable PUR , 2 m | |
| Core cross-section | 3 x 0.75 mm2 | |
| Housing material | PBT | |
| Sensing face | PBT | |
| Housing diameter | 18 mm | |
| Degree of protection | IP68 / IP69K | |
| Mass | 120 g | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Outside installation | |
| Electronic component | Binary multi-input/output R8D0-MIO-Ex12.PA* For technical data on installed electronic component see data sheet. | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS PA | |
| Galvanic isolation | ||
| Foundation Fieldbus/Field circuit | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Standard conformity | ||
| Galvanic isolation | EN 60079-11 | |
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g , 11 ms | |
| Vibration resistance | 10 g , 10 ... 150 Hz | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Connection type | plug-in terminals , spring terminal and screw terminal | |
| Core cross-section | ||
| Bus | up to 2.5 mm2 | |
| Inputs | up to 2.5 mm2 | |
| Cable diameter | see table 2 | |
| Cable gland | sensor inputs M16, fieldbus M20 | |
| Housing material | EN 1780-1 46000 , ISO AlSi9Cu3(Fe) , anodized | |
| Degree of protection | IP66 | |
| Mass | 1800 g | |
| Mounting | panel mounting | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BVS 16 ATEX E 075 X | |
| Marking | II 2 (1) G Ex ib [ia Ga] IIC T4 Gb , II 3 (1) G Ex ic [ia Ga] IIC T4 Gc , II 3 (1) G Ex ec [ia Ga] IIC T4 Gc , I (M1) [Ex ia Ma] I , II (1) D [Ex ia Da] IIIC , II 2 (1) D Ex tb [ia Da] IIIC T130 °C Db | |
| Bus | FISCO see EC-Type Examination Certificate | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
| International approvals | ||
| IECEx approval | IECEx BVS 16.0051X | |
| Approved for | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ec [ia Ga] IIC T4 Gc , [Ex ia Ma] I , [Ex ia Da] IIIC , Ex tb [ia Da] IIIC T130 °C Db | |
| Certificates and approvals | ||
| Marine approval | pending | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 5 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 4.05 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.25 | |
| Reduction factor r304 | 0.7 | |
| Reduction factor rSt37 | 1 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1000 Hz | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.34 mm2 | |
| Housing material | PBT | |
| Sensing face | PBT | |
| Housing diameter | 18 mm | |
| Degree of protection | IP68 / IP69K | |
| Note | use only delivered nuts | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Outside installation | |
| Electronic component | Temperature Multi-Input Device RD0-TI-Ex8.PA* For technical data on installed electronic component see data sheet. | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Standard conformity | ||
| Galvanic isolation | EN 60079-11 | |
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | see table 1 | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g , 11 ms | |
| Vibration resistance | 10 g , 10 ... 150 Hz | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Connection type | plug-in terminals , spring terminal and screw terminal | |
| Core cross-section | ||
| Bus | up to 2.5 mm2 | |
| Inputs | up to 2.5 mm2 | |
| Cable diameter | see table 2 | |
| Cable gland | sensor inputs M16, fieldbus M20 | |
| Housing material | EN 1780-1 46000 , ISO AlSi9Cu3(Fe) , anodized | |
| Degree of protection | IP66 | |
| Mass | 1800 g | |
| Mounting | panel mounting | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2237 | |
| Marking | II 2 (1) G Ex ia [ia Ga] IIC T4 Gb , II (1) G [Ex ia Ga] IIC , II (1) D [Ex ia Da] IIIC , II 3 G Ex ic IIC T4 Gc | |
| Bus | FISCO see EC-Type Examination Certificate | |
| Voltage | 24 V | |
| Inputs | see EC-Type Examination Certificate | |
| Certificate | PTB 03 ATEX 2238 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Bus | see Statement of Conformity | |
| Input | see EC-Type Examination Certificate | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | CoC 3025732 | |
| CSA approval | CoC 3025732C | |
| IECEx approval | IECEx PTB 05.0001 , IECEx PTB 05.0002X | |
| Approved for | Ex ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc | |
| Certificates and approvals | ||
| Marine approval | DNV A-14038 | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Cabinet installation | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS PA | |
| FDE (Fault Disconnect Equipment) | 6.7 mA | |
| Polarity | not polarity sensitive | |
| Rated voltage | 9 ... 32 V | |
| Rated current | max. 23 mA | |
| Indicators/operating means | ||
| LED PWR | green: on, bus voltage existent | |
| LED COM ERR | red, continuous lightning: hardware error red, flashing: no bus activities or bus fault off: no error | |
| LED CHANNEL ERROR | red, flashing: lead breakage/short circuit off: no error | |
| DIP switch | Address setting , write protection , simulation | |
| Analog input | ||
| Number of inputs | 1 | |
| Input type | Frequency input / Counter Input , channel 1 | |
| Switching frequency | min. 0.1 Hz max. 5 kHz | |
| Pulse duration | min. 80 µs | |
| Supply voltage | 5 V | |
| Supply current | 5 mA | |
| Line fault detection | lead breakage , short circuit (not in counter mode) | |
| Digital input | ||
| Number of inputs | 12 | |
| Input type | Sensor input , channels 1, 4, 7, 10 multiplexed , cycle adjustable | |
| Supply voltage | 6.6 V | |
| Supply current | 5 mA | |
| Line fault detection | lead breakage , short circuit | |
| Input type | Sensor input , channels 2, 3, 5, 6, 8, 9, 11, 12 multiplexed , cycle fixed | |
| Supply voltage | 5 V | |
| Supply current | 5 mA | |
| Time delay before availability | 2 ms | |
| Line fault detection | lead breakage , short circuit | |
| Digital output | ||
| Number of outputs | 4 | |
| Output type | Low power valve , channels 1, 4, 7, 10 | |
| Supply voltage | 6.6 V | |
| Supply current | 1.5 mA | |
| Line fault detection | lead breakage , short circuit | |
| Galvanic isolation | ||
| Foundation Fieldbus/Field circuit | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Standard conformity | ||
| Galvanic isolation | EN 60079-11 | |
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC/EN 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | -50 ... 75 °C (-58 ... 167 °F) hazardous area -50 ... 85 °C (-58 ... 185 °F) safe area | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g , 11 ms | |
| Vibration resistance | 5 g , 10 ... 150 Hz | |
| Pollution degree | 2 | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Connection type | plug-in terminals , spring terminal and screw terminal | |
| Core cross-section | ||
| Bus | up to 2.5 mm2 | |
| Inputs | up to 2.5 mm2 | |
| Housing material | Polycarbonate | |
| Degree of protection | IP20 | |
| Mass | approx. 290 g | |
| Mounting | mounting on DIN rail in cabinet | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BVS 16 ATEX E 075 X | |
| Marking | II 2 (1) G Ex ib [ia Ga] IIC T4 Gb , II 3 (1) G Ex ic [ia Ga] IIC T4 Gc , II 3 (1) G Ex ec [ia Ga] IIC T4 Gc , I (M1) [Ex ia Ma] I , II (1) D [Ex ia Da] IIIC | |
| PROFIBUS PA | ||
| Maximum safe voltage | 253 V | |
| Voltage | 24 V | |
| Current | 380 mA | |
| Power | 5.32 W | |
| Field-side | ||
| Voltage | 9 V | |
| Current | 43 mA | |
| Power | 96 mW | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-7:2015 | |
| International approvals | ||
| IECEx approval | IECEx BVS 16.0051X | |
| Approved for | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ec [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I | |
| Certificates and approvals | ||
| Marine approval | pending | |
| General specifications | ||
|---|---|---|
| Design / Mounting | Cabinet installation | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS PA | |
| Firmware update | via separate plug connection | |
| FDE (Fault Disconnect Equipment) | 6.7 mA | |
| Polarity | not polarity sensitive | |
| Rated voltage | 9 ... 32 V | |
| Rated current | max. 23 mA | |
| PROFIBUS PA | ||
| Profile | 3.02 | |
| Indicators/operating means | ||
| LED PWR | green: on, bus voltage existent | |
| LED COM ERR | red, continuous lightning: hardware error red, flashing: no bus activities or bus fault off: no error | |
| LED CHANNEL ERROR | red: 2 Hz flashing: lead breakage, overrange off: no error | |
| Input | ||
| Number | 8 | |
| Sensor types | see table 1 | |
| Grounding | grounding of thermoelements possible | |
| Error detection | lead breakage, wiring error, hardware device error | |
| Common mode voltage | Input to Input 600 Vpeak | |
| Transfer characteristics | ||
| Deviation | ||
| Influence of ambient temperature | see table 3 | |
| Linearization | T/C input 0.1°C RTD input 0.03°C | |
| Internal measurement cycle | for all sensor types max. 1 s | |
| Galvanic isolation | ||
| Fieldbus/inputs | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Standard conformity | ||
| Galvanic isolation | EN 60079-11 | |
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529 | |
| Fieldbus standard | IEC 61158-2 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area -40 ... 85 °C (-40 ... 185 °F) safe area | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g , 11 ms | |
| Vibration resistance | 5 g , 10 ... 150 Hz | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Connection type | plug-in terminals , spring terminal and screw terminal | |
| Core cross-section | ||
| Bus | up to 2.5 mm2 | |
| Inputs | up to 2.5 mm2 | |
| Housing material | Polycarbonate | |
| Degree of protection | IP20 | |
| Mass | 360 g | |
| Mounting | mounting on DIN rail in cabinet | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2237 | |
| Marking | II 2 (1) G Ex ia [ia Ga] IIC T4 Gb , II (1) G [Ex ia Ga] IIC , II (1) D [Ex ia Da] IIIC , II 3 G Ex ic IIC T4 Gc | |
| Bus | FISCO see EC-Type Examination Certificate | |
| Voltage | 24 V | |
| Inputs | see EC-Type Examination Certificate | |
| Certificate | PTB 03 ATEX 2238 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Bus | see Statement of Conformity | |
| Input | see EC-Type Examination Certificate | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | CoC 3025732 | |
| CSA approval | CoC 3025732C | |
| IECEx approval | IECEx PTB 05.0001 , IECEx PTB 05.0002X | |
| Approved for | Ex ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc | |
| Certificates and approvals | ||
| Marine approval | DNV A-14038 | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 5 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 4.05 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.25 | |
| Reduction factor r304 | 0.7 | |
| Reduction factor rSt37 | 1 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 1000 Hz | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 10 m | |
| Core cross-section | 0.34 mm2 | |
| Housing material | PBT | |
| Sensing face | PBT | |
| Housing diameter | 18 mm | |
| Degree of protection | IP68 / IP69K | |
| Note | use only delivered nuts | |
| Supply | ||
|---|---|---|
| Rated voltage | 19.2 ... 35 V DC | |
| Rated current | 150 ... 100 mA | |
| Power dissipation | 3 W | |
| Ethernet Interface | ||
| Intrinsically safe port | 10 BASE-T/100 BASE-TX | |
| Non-intrinsically safe port | 10 BASE-T/100 BASE-TX | |
| Connection type | 2 x RJ-45 , IEC 60603-7 | |
| Connector pinout | socket TIA/EIA-568-B | |
| Transfer rate | 10/100 Mbit/s , Auto-Negotiation | |
| Operating mode | Half/Full Duplex | |
| Cable type | CAT5e S/FTP AWG 24, Installation cable, L/R ratio max. 10 µH/&Omega of all strand combinations | |
| I.S. cable length | typ. 100 m/20 °C | |
| Total cable length | typ. 200 m/20 °C | |
| Number of isolators | max. 2 in series connection | |
| Indicators/operating means | ||
| LED PWR | green: Power on | |
| LED ACT | yellow: communication active | |
| LED 10/100 | yellow ON: Transfer rate 100 MBit/s , OFF: 10 MBit/s | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Standard conformity | ||
| Galvanic isolation | EN 50020 | |
| Degree of protection | IEC 60529 | |
| Climatic conditions | DIN IEC 721 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ethernet | IEEE 802.3 , IEEE 802.3u | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g 11 ms | |
| Vibration resistance | 1 g 10 ... 150 Hz | |
| Pollution degree | max. 2, according to IEC 60664 | |
| Mechanical specifications | ||
| Connection type | Terminals | |
| Core cross-section | up to 2.5 mm2 | |
| Housing material | Polyamide PA 66 | |
| Degree of protection | IP20 according to EN 60529 | |
| Mass | 195 g | |
| Mounting | DIN rail mounting | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 07 ATEX 2025 X | |
| Marking | II (1) G [Ex ia Ga] IIB , II (1) D [Ex ia Da] IIIC , II 3(1)G Ex nA [ia Ga] IIB T4 Gc II 3 (1D) G Ex nA [ia IIIC Da] IIB T4 Gc I (M1) [Ex ia Ma] I | |
| Supply | ||
| Maximum safe voltage | 253 V AC | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| CSA approval | CSA 15.70016295 | |
| Control drawing | 116-B032 | |
| Approved for | Class I, Zone 2, AEx/Ex nA [ia Ga] IIB T4 Gc Class I, Zone 2, AEx/Ex nA [ia Da IIIC] IIB T4 Gc | |
| IECEx approval | IECEx PTB 09.0053X | |
| Approved for | [Ex ia Ga] IIB [Ex ia Da] IIIC Ex nA [ia Ga] IIB T4 Gc Ex nA [ia IIIC Da] IIB T4 Gc [Ex ia Ma] I | |
| Certificates and approvals | ||
| Patents | This product may be covered by the following patent: US7,687,791 | |
| Supply | ||
|---|---|---|
| Rated voltage | 19.2 ... 35 V DC | |
| Rated current | 150 ... 100 mA | |
| Power dissipation | 3 W | |
| Ethernet Interface | ||
| Intrinsically safe port | 10 BASE-T/100 BASE-TX | |
| Non-intrinsically safe port | 10 BASE-T/100 BASE-TX | |
| Connection type | 2 x RJ-45 , IEC 60603-7 | |
| Connector pinout | socket TIA/EIA-568-B | |
| Transfer rate | 10/100 Mbit/s , Auto-Negotiation | |
| Operating mode | Half/Full Duplex | |
| Cable type | CAT5e S/FTP AWG 24, Installation cable, L/R ratio max. 10 µH/&Omega of all strand combinations | |
| I.S. cable length | typ. 100 m/20 °C | |
| Total cable length | typ. 200 m/20 °C | |
| Number of isolators | max. 2 in series connection | |
| Indicators/operating means | ||
| LED PWR | green: Power on | |
| LED ACT | yellow: communication active | |
| LED 10/100 | yellow ON: Transfer rate 100 MBit/s , OFF: 10 MBit/s | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Standard conformity | ||
| Galvanic isolation | EN 50020 | |
| Degree of protection | IEC 60529 | |
| Climatic conditions | DIN IEC 721 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ethernet | IEEE 802.3 , IEEE 802.3u | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Relative humidity | &le 95 % non-condensing | |
| Shock resistance | 15 g 11 ms | |
| Vibration resistance | 1 g 10 ... 150 Hz | |
| Pollution degree | max. 2, according to IEC 60664 | |
| Mechanical specifications | ||
| Connection type | Terminals | |
| Core cross-section | up to 2.5 mm2 | |
| Housing material | Polyamide PA 66 | |
| Degree of protection | IP20 according to EN 60529 | |
| Mass | 195 g | |
| Mounting | DIN rail mounting | |
| Data for application in connection with hazardous areas | ||
| EC-Type Examination Certificate | PTB 07 ATEX 2025 X | |
| Group, category, type of protection, temperature class | II (1) GD [Ex ia] IIB , II 3 (1GD) G Ex nA [ia IIB] II T4 , I (M1) [Ex ia] I | |
| Supply | ||
| Maximum safe voltage | 253 V AC | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
| Certificates and approvals | ||
| Patents | This product may be covered by the following patent: US7,687,791 | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
| Power dissipation | 1.5 W | |
| Power consumption | 3 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Analog input | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | pressure converter | |
| Field device [2] | flow converter | |
| Field device [3] | level converter | |
| Field device [4] | Temperature Converter | |
| Field device interface | ||
| Connection | 2-wire transmitter | |
| Connection [2] | 3-wire transmitter | |
| Connection [3] | 4-wire transmitter | |
| Connection | 2-wire transmitter (HART):Supply circuit: channel I 1+, 2-, channel II 5+, 6-, channel III 9+, 10-, channel IV 13+, 14-3-wire transmitter:Supply circuit: channel I 1+, 4-, channel II 5+, 8-, channel III 9+, 12-, channel IV 13+, 16-Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-4-wire transmitter (powered externally):Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16- | |
| Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
| Input resistance | 15 &Omega | |
| Conversion time | max. 100 ms | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: > 22 mA configurable between 0 ... 26 mA | |
| Open-circuit | factory setting: < 1 mA configurable between 0 ... 26 mA | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Transfer characteristics | ||
| Deviation | ||
| After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
| Resolution | 12 Bit (0 ... 26 mA) | |
| Refresh time | 100 ms | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2000 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Relative humidity | 95 % non-condensing | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
| Connection | Ex e spring terminal with protective cover | |
| Mass | approx. 750 g | |
| Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BVS 11 ATEX E 093 X | |
| Marking | II 2 G Ex db eb IIC T4 | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007 | |
| International approvals | ||
| ATEX approval | BVS 11 ATEX E 093X | |
| INMETRO | Brazil: TÜV 14.1599X | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
Компания Zipstore.ru поставляет оптом и в розницу запчасти Pepperl+Fuchs.
В каталоге сайта представлено 13440 запчастей Pepperl+Fuchs. Также вы можете приобрести опции и аксессуары для расширения функциональных возможностей, транспортировки и эксплуатации оборудования. Запчасти в каталоге могут иметь полное название, каталожный номер, фотографию, краткое описание, а также модели принтеров, с которыми они совместимы.
Для оформления заказа вы можете воспользоваться одним из следующих способов:
Мы осуществляем поставки запчастей Pepperl+Fuchs во все города России, а также в Республику Беларусь, Казахстан и другие страны СНГ.
Продажа осуществляется за наличный и безналичный расчет. На сайте указаны розничные цены в рублях и долларах, с учетом НДС. Чтобы узнать оптовые цены на запчасти Pepperl+Fuchs, нужно отправить запрос по электронной почте. Подробнее о способах доставки и оплаты можно узнать в разделе сайта «Оплата и доставка». В разделе «%Скидки и акции» Вы можете найти наиболее выгодные предложения по продаже запчастей, а также сезонные скидки и акции.
При возникновении вопросов по обслуживанию, эксплуатации, ремонту Pepperl+Fuchs, Вы можете проконсультироваться со специалистами на форуме сайта.