| Supply | ||
|---|---|---|
| Connection | backplane bus | |
| Rated voltage | 5 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 2 W | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1 | |
| PROFIBUS DP | ||
| Connection | 9-pin Sub-D socket via backplane | |
| Baud rate | up to 1.5 MBit/s | |
| Protocol | PROFIBUS DP/DP V1 read/write services | |
| Number of stations per bus line | max. 125 (PROFIBUS), max. 119 (service bus) | |
| Cyclic process data | 240 bytes in total, either input or output data | |
| Number of stations per bus segment | max. 31 (RS-485 standard) | |
| Number of repeaters between Master and Slave | max. 3 | |
| Supported I/O modules | all LB remote I/O modules | |
| Bus length | max. 1000 m (FOL, 1.5 MBaud), max. 1000 m (copper cable, 187.5 kBd), max. 200 m (copper cable, 1.5 MBd) | |
| Addressing | via configuration software | |
| PROFIBUS address | 0 ... 126 (factory standard setting: 126) | |
| GSE file | CGV61712.gsd/gse | |
| HART communication | via PROFIBUS or service bus | |
| Time stamping (10 ms) | 1000 events via LB1007 | |
| Internal bus | ||
| Connection | backplane bus | |
| Redundancy | via backplane | |
| Indicators/settings | ||
| LED indicator | LED 1 (power supply): On = operating, fast flash = cold start, slow flash = HCIR loading active LED 2 (collective alarm): On = internal fault, flashing = no PROFIBUS connection LED 3 (status process bus): flashing = PROFIBUS receive channel active LED 4 (status service bus): flashing = service bus receive channel active LED 5 (operating mode): flashing 1 (1:1 ratio) = active, normal operation flashing 2 (7:1 ratio) = active, simulation LED 6 (status process bus): flashing = PROFIBUS response channel active LED 7 (status servicebus): flashing = service bus response channel active | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , mounted on backplane | |
| Connection | via backplane | |
| Mass | approx. 120 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Supply | ||
|---|---|---|
| Connection | backplane bus | |
| Rated voltage | 5 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 2 W | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1 | |
| PROFIBUS DP | ||
| Connection | 9-pin Sub-D socket via backplane | |
| Baud rate | up to 1.5 MBit/s | |
| Protocol | PROFIBUS DP/DP V1 read/write services | |
| Number of stations per bus line | max. 125 (PROFIBUS), max. 119 (service bus) | |
| Cyclic process data | 240 bytes input and (simultaneously) 240 bytes output | |
| Number of stations per bus segment | max. 31 (RS-485 standard) | |
| Number of repeaters between Master and Slave | max. 3 | |
| Supported I/O modules | all LB remote I/O modules | |
| Configuration (240 bytes I/O) | Standard: 80 analog, 184 digital Universal 2I2O: 48 analog, 184 digital Universal 4I4O: 60 analog, 120 digital | |
| Bus length | max. 1000 m (FOL, 1.5 MBaud), max. 1000 m (copper cable, 187.5 kBd), max. 200 m (copper cable, 1.5 MBd) | |
| Addressing | via configuration software | |
| PROFIBUS address | 0 ... 126 (factory standard setting: 126) | |
| GSE file | CGV61710.gsd/gse | |
| HART communication | via PROFIBUS or service bus | |
| Internal bus | ||
| Connection | backplane bus | |
| Redundancy | via backplane | |
| Indicators/settings | ||
| LED indicator | LED 1 (power supply): On = operating, fast flash = cold start, slow flash = HCIR loading active LED 2 (collective alarm): On = internal fault, flashing = no PROFIBUS connection LED 3 (status process bus): flashing = PROFIBUS receive channel active LED 4 (status service bus): flashing = service bus receive channel active LED 5 (operating mode): flashing 1 (1:1 ratio) = active, normal operation flashing 2 (7:1 ratio) = active, simulation LED 6 (status process bus): flashing = PROFIBUS response channel active LED 7 (status servicebus): flashing = service bus response channel active | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , mounted on backplane | |
| Connection | via backplane | |
| Mass | approx. 120 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | NPN | |
| Rated operating distance | 5 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 4.05 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.6 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 500 Hz | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 150 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Functional safety related parameters | ||
| MTTFd | 3170 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector 8 mm 3-pin , with snap locking | |
| Housing material | PBT | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| Supply | ||
|---|---|---|
| Connection | backplane bus | |
| Rated voltage | 5 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 2 W | |
| Auxiliary energy | 24 V DC Trunk load 20 mA | |
| Fieldbus interface | ||
| Fieldbus type | FOUNDATION Fieldbus H1 | |
| FOUNDATION Fieldbus | ||
| Connection | plug-in screw connector on the backplane | |
| Baud rate | 31.25 kBit/s , MBP | |
| Protocol | H1 to IEC 1158-2 | |
| Station connection | directly at the trunk or via spur protector | |
| Number of stations per bus line | 1 or 2, depending on the required response times | |
| Number of channels per station | max. 20 analog, max. 40 digital | |
| Supported I/O modules | 5 slots, to be filled with (combinations possible): 1*08 digital input, 8-channel, NAMUR 3*05 analog input, 4-channel, 20 mA (HART via service bus) 4*05 analog output, 4-channel, 20 mA (HART via service bus) 5*04 Pt100 RTD input, 4-channel 5*05 thermocouple input, 4-channel 6005 relay output, 4-channel, 230 V 6006 relay output, 8-channel, 24 V 6*08 digital output, 8-channel, Ex i 6*10-6*15 digital output, 4-channel, Ex i power * = variable (0=non-IS, 1=IS) | |
| Bus length | max. 1900 m (must not be exceeded by the sum of all trunk and spur lines) | |
| Spur length | max. 120 m (depending on the number of field devices. Modular I/O station = 1 field device) | |
| Addressing | via PCS (software) | |
| Internal bus | ||
| Connection | backplane bus | |
| Indicators/settings | ||
| LED indicator | LED 1 (power supply): On = operating, fast flash = cold start LED 2 (collective alarm): On = internal fault, flashing = no fieldbus LED 3 (operating mode): Flashing = active | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , mounted on backplane | |
| Connection | via backplane | |
| Mass | approx. 150 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15-20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Supply | ||
|---|---|---|
| Connection | backplane bus | |
| Rated voltage | 5 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 2.5 W | |
| Fieldbus interface | ||
| Fieldbus type | MODBUS TCP | |
| Ethernet Interface | ||
| Connection type | RJ-45 , via backplane | |
| Transfer rate | 100 MBit/s | |
| Station connection | directly to PCS or PLC or via hubs or switches | |
| Bus length | max. 100 m (CAT 7 cable) | |
| Addressing | IP address assigned via Ethernet | |
| Ethernet address | IP V4 address (ex works standard: 0.0.0.0, auto IP, DHCP) | |
| Number of channels per station | max. 80 analog, max. 184 digital | |
| Supported I/O modules | all LB remote I/O modules | |
| HART communication | via Ethernet or service bus | |
| Internal bus | ||
| Connection | backplane bus | |
| Redundancy | via backplane | |
| Service interface | ||
| Connection | 9-pole to RS 485 standard , Sub-D | |
| Indicators/settings | ||
| LED indicator | LED P: (power supply): On = operating, fast flash = cold start LED 1: (collective alarm): On = internal fault, flashing = no MODBUS TCP connection LED 2: (status fieldbus): On = Network link OK LED 3: (status service bus): flashing = service bus receive channel active LED 4: (operating mode): flashing 1 (1:1 ratio) = active, normal operation flashing 2 (7:1 ratio) = active, simulation LED 5: (status fieldbus): flashing = MODBUS response channel active LED 6: (status service bus): flashing = service bus response channel active | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100 | |
| Vibration resistance | frequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , mounted on backplane | |
| Connection | via backplane | |
| Mass | approx. 150 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Statement of conformity | PF 08 CERT 1234 X | |
| Group, category, type of protection, temperature class | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| UL approval | E106378 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| General specifications | ||
|---|---|---|
| Suitable components | backplane LB9024S , LB8105* , LB8106* , LB8108* , LB8109* , LB8107* | |
| Slots | ||
| Bus coupler | 2 | |
| Supply | 3 | |
| Output shut-down | 5 SIL2 output shutdown segments slots 3 ... 5, 6 ... 10, 11 ... 15, 16 ... 20, 21 ... 24 | |
| I/O modules (single width) | max. 22 | |
| I/O modules (dual width) | max. 11 | |
| Supply | ||
| Maximum safe voltage | 60 V DC (SELV/PELV) | |
| Input voltage range | 18 ... 32 V DC (SELV/PELV) | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1 or MODBUS RTU , depends on bus coupler | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 2170 g | |
| Dimensions | (W x H x D) 605 x 127 x 80 mm (23.8 x 5 x 3.15 inch) , without modules | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 5 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 4.05 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.6 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 500 Hz | |
| Hysteresis | typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 150 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.14 mm2 | |
| Housing material | PBT | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| General specifications | ||
|---|---|---|
| Suitable components | backplane LB9022E , backplane LB9022S , LB8111A2* , LB8105* , LB8106* , LB8108* , LB8109* , LB8107* | |
| Slots | ||
| Supply | 3 | |
| Output shut-down | 5 SIL2 output shutdown segments slots 25 ... 29, 30 ... 34, 35 ... 39, 40 ... 44, 45 ... 48 | |
| I/O modules (single width) | max. 24 | |
| I/O modules (dual width) | max. 12 | |
| Supply | ||
| Maximum safe voltage | 60 V DC (SELV/PELV) | |
| Input voltage range | 18 ... 32 V DC (SELV/PELV) | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1, MODBUS RTU, or MODBUS TCP , depending on the base backplane | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 1800 g | |
| Dimensions | (W x H x D) 605 x 127 x 80 mm (23.8 x 5 x 3.15 inch) , without modules | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Suitable components | backplane LB9027A , LB8105* , LB8106* , LB8108* , LB8109* , LB8107* | |
| Slots | ||
| Bus coupler | 1 | |
| Supply | 2 | |
| I/O modules (single width) | max. 16 | |
| I/O modules (dual width) | max. 8 | |
| Supply | ||
| Maximum safe voltage | 60 V DC (SELV/PELV) | |
| Input voltage range | 18 ... 32 V DC (SELV/PELV) | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1 or MODBUS RTU , depends on bus coupler | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 1370 g | |
| Dimensions | (W x H x D) 440 x 127 x 80 mm (17.3 x 5 x 3.15 inch) , without modules | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Suitable components | LB8110* | |
| Slots | ||
| Bus coupler | 1 | |
| Supply | 1 | |
| I/O modules (dual width) | max. 5 | |
| Supply | ||
| Maximum safe voltage | 60 V DC (SELV/PELV) | |
| Input voltage range | 18 ... 32 V DC (SELV/PELV) | |
| Fieldbus interface | ||
| Fieldbus type | FOUNDATION Fieldbus H1 | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 1120 g | |
| Dimensions | (W x H x D) 275 x 127 x 80 mm (10.8 x 5 x 3.15 inch) , without modules | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Suitable components | backplane LB9024A , backplane LB9024S , LB8111A2* | |
| Slots | ||
| Bus coupler | 2 | |
| Supply | 3 | |
| I/O modules (single width) | max. 22 | |
| I/O modules (dual width) | max. 11 | |
| Supply | ||
| Maximum safe voltage | 60 V DC (SELV/PELV) | |
| Input voltage range | 18 ... 32 V DC (SELV/PELV) | |
| Fieldbus interface | ||
| Fieldbus type | MODBUS TCP | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 2170 g | |
| Dimensions | (W x H x D) 605 x 127 x 80 mm (23.8 x 5 x 3.15 inch) , without modules | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 5 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 4.05 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.6 | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 500 Hz | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 150 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector 8 mm 3-pin , with snap locking | |
| Housing material | PBT | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| General specifications | ||
|---|---|---|
| Suitable components | backplane LB9025A , LB8105* , LB8106* , LB8108* , LB8109* , LB8107* | |
| Slots | ||
| Bus coupler | 1 | |
| Supply | 1 | |
| I/O modules (single width) | max. 8 | |
| I/O modules (dual width) | max. 4 | |
| Supply | ||
| Maximum safe voltage | 60 V DC (SELV/PELV) | |
| Input voltage range | 18 ... 32 V DC (SELV/PELV) | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1 or MODBUS RTU , depends on bus coupler | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 1010 g | |
| Dimensions | (W x H x D) 275 x 127 x 80 mm (10.8 x 5 x 3.15 inch) , without modules | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Suitable components | backplane LB9025A , LB8111A2* | |
| Slots | ||
| Bus coupler | 1 | |
| Supply | 1 | |
| I/O modules (single width) | max. 8 | |
| I/O modules (dual width) | max. 4 | |
| Supply | ||
| Maximum safe voltage | 60 V DC (SELV/PELV) | |
| Input voltage range | 18 ... 32 V DC (SELV/PELV) | |
| Fieldbus interface | ||
| Fieldbus type | MODBUS TCP | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 1010 g | |
| Dimensions | (W x H x D) 275 x 127 x 80 mm (10.8 x 5 x 3.15 inch) , without modules | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Suitable components | backplane LB9023A , backplane LB9023E , LB8111A2* , LB8105* , LB8106* , LB8108* , LB8109* , LB8107* | |
| Slots | ||
| Supply | 1 | |
| I/O modules (single width) | max. 8 | |
| I/O modules (dual width) | max. 4 | |
| Supply | ||
| Maximum safe voltage | 60 V DC (SELV/PELV) | |
| Input voltage range | 18 ... 32 V DC (SELV/PELV) | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1 or MODBUS RTU , depending on the base backplane | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 980 g | |
| Dimensions | (W x H x D) 275 x 127 x 80 mm (10.8 x 5 x 3.15 inch) , without modules | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Suitable components | backplane LB9027A , LB8111A2* | |
| Slots | ||
| Bus coupler | 1 | |
| Supply | 2 | |
| I/O modules (single width) | max. 16 | |
| I/O modules (dual width) | max. 8 | |
| Supply | ||
| Maximum safe voltage | 60 V DC (SELV/PELV) | |
| Input voltage range | 18 ... 32 V DC (SELV/PELV) | |
| Fieldbus interface | ||
| Fieldbus type | MODBUS TCP | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 1370 g | |
| Dimensions | (W x H x D) 440 x 127 x 80 mm (17.3 x 5 x 3.15 inch) , without modules | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open/closed (NO/NC) programmable | |
| Output type | AS-Interface | |
| Rated operating distance | 6 mm | |
| Installation | flush | |
| Assured operating distance | 0 ... 4.86 mm | |
| Reduction factor rAl | 0.28 | |
| Reduction factor rCu | 0.25 | |
| Reduction factor r304 | 0.75 | |
| Slave type | A/B slave | |
| AS-Interface specification | V3.0 | |
| Required master specification | &ge V2.1 | |
| Output type | 2-wire | |
| Nominal ratings | ||
| Operating voltage | 26.5 ... 31.9 V via AS-i bus system | |
| Switching frequency | &ge 500 (P3=0), &ge 100 (P3=1) | |
| Hysteresis | typ. 5 % | |
| Operating current | 20 mA | |
| Functional safety related parameters | ||
| MTTFd | 532 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Indicators/operating means | ||
| LED POWER | AS-Interface voltage LED green | |
| LED IN | switching state (input) LED yellow | |
| LED OUT | Dual LED yellow/red yellow: switching state red: error mode | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.34 mm2 | |
| Housing material | PBT | |
| Degree of protection | IP67 | |
| Mass | 90 g | |
| General specifications | ||
|---|---|---|
| Suitable components | backplane LB9026A , backplane LB9026E , LB8111A2* , LB8105* , LB8106* , LB8108* , LB8109* , LB8107* | |
| Slots | ||
| Supply | 2 | |
| I/O modules (single width) | max. 16 | |
| I/O modules (dual width) | max. 8 | |
| Supply | ||
| Maximum safe voltage | 60 V DC (SELV/PELV) | |
| Input voltage range | 18 ... 32 V DC (SELV/PELV) | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1, MODBUS RTU, or MODBUS TCP , depending on the base backplane | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 1340 g | |
| Dimensions | (W x H x D) 440 x 127 x 80 mm (17.3 x 5 x 3.15 inch) , without modules | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Suitable components | backplane LB9024S , LB8105* , LB8106* , LB8108* , LB8109* , LB8107* | |
| Slots | ||
| Bus coupler | 2 | |
| Supply | 3 | |
| I/O modules (single width) | max. 12 | |
| I/O modules (dual width) | max. 6 | |
| Supply | ||
| Maximum safe voltage | 60 V DC (SELV/PELV) | |
| Input voltage range | 18 ... 32 V DC (SELV/PELV) | |
| Fieldbus interface | ||
| Fieldbus type | PROFIBUS DP/DP-V1 or MODBUS RTU , depends on bus coupler | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | EN 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 1380 g | |
| Dimensions | (W x H x D) 440 x 127 x 80 mm (17.3 x 5 x 3.15 inch) , without modules | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | NPN | |
| Rated operating distance | 7 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 5.67 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.6 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 100 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.34 mm2 | |
| Housing material | PBT | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Rail or terminals 23+, 24- | |
| Rated voltage | 19 ... 30 V DC | |
| Rated current | approx. 120 mA at 24 V DC | |
| Power dissipation | 2.3 W | |
| Power consumption | 2.9 W | |
| HART signal channels (intrinsically safe) | ||
| Conformity | HART field device input (revision 5 to 7) | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3, 4, 5, 6 | |
| Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
| Input resistance | 250 &Omega , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
| Available voltage | &ge 15.5 V at 20 mA, short-circuit protected | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 7, 8, 9 , output II: terminals 13, 14, 15 , output III: terminals 19, 20, 21 | |
| Output signal | analog | |
| Current range | 4 ... 20 mA , (source or sink mode) | |
| Load | max. 650 &Omega , source mode | |
| Voltage range | 5 ... 30 V , sink mode from external supply | |
| Fault signal | downscale I &le 2 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
| Other outputs | HART communicator on terminals 22, 24 | |
| Collective error message | Power Rail and LED red | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 | |
| Marking | II (1)GD [Ex ia] IIC, [Ex iaD] | |
| Certificate | PF 07 CERT 1142 X | |
| Marking | II 3G Ex nA II T4 X | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 | |
| IECEx approval | ||
| IECEx certificate | IECEx BAS 07.0047 | |
| IECEx marking | [Ex ia] IIC , [Ex iaD] | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Rail or terminals 23+, 24- | |
| Rated voltage | 19 ... 30 V DC | |
| Rated current | approx. 130 mA at 24 V DC | |
| Power dissipation | 2.5 W | |
| Power consumption | 3.1 W | |
| HART signal channels (intrinsically safe) | ||
| Conformity | HART field device input (revision 5 to 7) | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3, 4, 5, 6 | |
| Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
| Input resistance | 250 &Omega , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
| Available voltage | &ge 15.5 V at 20 mA, short-circuit protected | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, 12, output II: terminals 16, 17, 18 output III: terminals 7, 8, 9, output IV: terminals 13, 14, 15, output V: terminals 19, 20, 21 | |
| Output I, II | ||
| Output signal | relay and LED yellow | |
| Mechanical life | 107 switching cycles | |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
| Output III, IV, V | ||
| Output signal | analog | |
| Current range | 4 ... 20 mA , (source or sink mode) | |
| Load | max. 650 &Omega , source mode | |
| Voltage range | 5 ... 30 V , sink mode from external supply | |
| Fault signal | downscale I &le 2 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
| Other outputs | HART communicator on terminals 22, 24 | |
| Collective error message | Power Rail and LED red | |
| Transfer characteristics | ||
| Relay | programmable either for fault or trip value (with direction, hysteresis and delay) | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 | |
| Marking | II (1)GD [Ex ia] IIC, [Ex iaD] | |
| Certificate | PF 07 CERT 1141 X | |
| Marking | II 3G Ex nA nC II T4 X | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 | |
| IECEx approval | ||
| IECEx certificate | IECEx BAS 07.0047 | |
| IECEx marking | [Ex ia] IIC , [Ex iaD] | |
| General specifications | ||
|---|---|---|
| Signal type | Analog input | |
| Supply | ||
| Connection | Power Rail or terminals 23+, 24- | |
| Rated voltage | 19 ... 30 V | |
| Rated current | approx. 140 mA at 24 V DC | |
| Power dissipation | 2.7 W | |
| Power consumption | 3.3 W | |
| HART signal channels (intrinsically safe) | ||
| Conformity | HART field device input (revision 5 to 7) | |
| Interface | ||
| Programming interface | programming socket | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1, 2, 3, 4, 5, 6 | |
| Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
| Input resistance | 250 &Omega , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
| Available voltage | &ge 15.5 V at 20 mA, short-circuit protected | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 10, 11, output II: terminals 11, 12, output III: terminals 16, 17, output IV: terminals 17, 18 output V: terminals 7, 8, 9, output VI: terminals 13, 14, 15, output VII: terminals 19, 20, 21 | |
| Output I, II, III, IV | ||
| Output signal | relay and LED yellow | |
| Mechanical life | 107 switching cycles | |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
| Output V, VI, VII | ||
| Output signal | analog | |
| Current range | 4 ... 20 mA , (source or sink mode) | |
| Load | max. 650 &Omega , source mode | |
| Voltage range | 5 ... 30 V , sink mode from external supply | |
| Fault signal | downscale I &le 2 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
| Other outputs | HART communicator on terminals 22, 24 | |
| Collective error message | Power Rail and LED red | |
| Transfer characteristics | ||
| Relay | programmable either for fault or trip value (with direction, hysteresis and delay) | |
| Indicators/settings | ||
| Display elements | LEDs , display | |
| Control elements | Control panel | |
| Configuration | via operating buttons via PACTware | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Low voltage | ||
| Directive 2014/35/EU | EN 61010-1:2010 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | 300 g | |
| Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 | |
| Marking | II (1)GD [Ex ia] IIC, [Ex iaD] | |
| Certificate | PF 07 CERT 1141 X | |
| Marking | II 3G Ex nA nC II T4 X | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 | |
| IECEx approval | ||
| IECEx certificate | IECEx BAS 07.0047 | |
| IECEx marking | [Ex ia] IIC , [Ex iaD] | |
| Functional safety related parameters | ||
|---|---|---|
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Connection | via 14-channel flat cable form master KFD2-HMM-16 | |
| HART signal channels (non-intrinsically safe) | ||
| Conformity | HART field device input (revision 5 to 7) | |
| Connection | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 | |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
| Terminating resistor | external 230 ... 500 &Omega standard (up to 1000 &Omega possible) | |
| Output voltage | &ge 400 mV ss (with the terminator resistance specified above) | |
| Output resistance | 100 &Omega or smaller, capacitive coupling | |
| Input impedance | according to HART specification | |
| Input voltage range | 0.08 ... 4 V ss typ. ± 5.2 V as local reference | |
| Indicators/settings | ||
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 100 g | |
| Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) , housing type B1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 07 CERT 1143 X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | NPN | |
| Rated operating distance | 7 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 5.67 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.6 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 100 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M12 x 1 , 4-pin | |
| Housing material | PBT | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| Functional safety related parameters | ||
|---|---|---|
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Connection | terminals 17+, 18- | |
| Rated voltage | 20 ... 32 V DC typical at 100 mA | |
| Power consumption | max. 3 W | |
| HART signal channels (non-intrinsically safe) | ||
| Conformity | HART field device input (revision 5 to 7) | |
| Connection | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 | |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
| Terminating resistor | external 230 ... 500 &Omega standard (up to 1000 &Omega possible) | |
| Output voltage | &ge 400 mV ss (with the terminator resistance specified above) | |
| Output resistance | 100 &Omega or smaller, capacitive coupling | |
| Input impedance | according to HART specification | |
| Input voltage range | 0.08 ... 4 V ss typ. ± 5.2 V as local reference | |
| Interface | ||
| Transfer rate | 9600, 19200, or 38400 Bit/s (selectable with DIL switch (2 and 3) by the user) | |
| Type | RS-485 , 2-wire multidrop | |
| Address selection | One of 31 possible addresses selectable per DIL switch (4 ... 8) | |
| Indicators/settings | ||
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 250 g | |
| Dimensions | 40 x 107 x 115 mm (1.6 x 4.2 x 4.5 inch) , housing type C1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 07 CERT 1143 X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| HART signal channels (non-intrinsically safe) | ||
|---|---|---|
| Load resistor | 220 &Omega , switchable on | |
| Interface | ||
| Type | multiplexer connection : 26-pin NFP-26A (Yamaichi) | |
| Signal lines | ||
| Rated current | max. 30 mA per channel | |
| Indicators/settings | ||
| DIP switch | selection of operating mode: - ON: without load resistor - OFF: with load resistor | |
| Factory setting | DIP switches S1 and S2: ON | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 50 °C (32 ... 122 °F) | |
| Storage temperature | -15 ... 50 °C (5 ... 122 °F) | |
| Relative humidity | &le 93 % non-condensing | |
| Shock resistance | 15 g , 11 ms | |
| Vibration resistance | 1 g , 10 ... 150 Hz | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | ||
| Field side | screw terminals , green | |
| Control side | screw terminals , green HART : 1 x IDC plug, 26-pin | |
| Core cross-section | screw terminals: 0.25 ... 1.5 mm2 (24 ... 16 AWG) | |
| Mass | approx. 200 g | |
| Dimensions | 110 x 125 x 67 mm (4.3 x 4.9 x 2.6 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| Supply | ||
|---|---|---|
| Rated voltage | 20.4 ... 27.6 V DC SELV/PELV | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Fusing | 1 A | |
| Redundancy | ||
| Supply | yes | |
| Signal lines | ||
| Rated current | max. 30 mA per channel | |
| Indicators/settings | ||
| Display elements | - LED PS-A (Termination Board power supply), green LED - LED PS-B (Termination Board power supply), green LED | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Shock resistance | EN 60068-2-27 | |
| Vibration resistance | EN 60068-2-6 | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 50 °C (32 ... 122 °F) | |
| Storage temperature | -15 ... 50 °C (5 ... 122 °F) | |
| Relative humidity | &le 93 % non-condensing | |
| Shock resistance | 15 g , 11 ms | |
| Vibration resistance | 1 g , 10 ... 150 Hz | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | field side connection: screw terminals, green control side connection: ELCO socket, 56-pin | |
| Core cross-section | 0.5 ... 2.5 mm2 (20 ... 12 AWG) | |
| Mass | approx. 400 g | |
| Dimensions | 123 x 126 x 67 mm (4.9 x 5.0 x 2.6 inch) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| Functional safety related parameters | ||
|---|---|---|
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Connection | SL1: 1a, 1b(-) 2a, 2b(+) | |
| Rated voltage | 20.4 ... 30 V DC via Termination Board | |
| Rated current | 28 mA at 24 V , RS-485, quiescent current | |
| Power dissipation | 0.7 W at 24 V | |
| HART signal channels (non-intrinsically safe) | ||
| Number of channels | 32 | |
| Conformity | HART field device input (revision 5 to 7) | |
| Signal range | 0.12 Vpp < signal < 1.5 Vpp | |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
| Terminating resistor | external 230 ... 500 &Omega standard (up to 1000 &Omega possible) | |
| Output voltage | &ge 400 mV ss (with the terminator resistance specified above) | |
| Output resistance | 100 &Omega or smaller, capacitive coupling | |
| DC isolation | dual capacitor each channel | |
| Common mode voltage | up to 30 V | |
| Input impedance | > 5 k&Omega , according to HART specification | |
| Input voltage range | 0.12 ... 1.5 V ss | |
| Common mode voltage | max. 30 V | |
| Differential mode clamping | ± 5.2 V , for transient or AC signals | |
| Common mode clamping | ± 10 V , for transient or AC signals | |
| Carrier detect level | signal > 0.12 Vpp, carrier detection activated signal < 0.08 Vpp, carrier detection not activated | |
| Transmit amplitude | 200 &Omega load, 0.43 Vpp < signal < 0.49 Vpp 500 &Omega load, 1.1 Vpp < signal < 1.2 Vpp | |
| Device type | DC isolated bus device | |
| Impedance | high impedance | |
| Data link type | HART primary and secondary | |
| Field multi point support | option available upon request | |
| Interface | ||
| Transfer rate | 9600 MBit/s, 19200 MBit/s or 38400 MBit/s, selectable via switch | |
| Address | 1 ... 31 , adjustable via DIP switch | |
| Type | RS-485 , differential pair and grounding | |
| Topology | multi point, master/slave connection | |
| Indicators/settings | ||
| Display elements | LEDs LED PWR ON (power supply), one green LED LED HART TX (HART transmission), one yellow LED LED FAULT (lead fault), one red LED | |
| Control elements | DIP switches at the housing side for: - unit slave address - baud rate - test mode on/off | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 140 g | |
| Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) | |
| Mounting | on Termination Board | |
| Data for application in connection with hazardous areas | ||
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| CSA approval | 1256050 | |
| Approved for | Class I, Division 2, Groups A, B, C, D Class I, Zone 2, IIC | |
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | NPN | |
| Rated operating distance | 7 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 5.67 mm | |
| Reduction factor rAl | 0.3 | |
| Reduction factor rCu | 0.2 | |
| Reduction factor r304 | 0.6 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 100 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.34 mm2 | |
| Housing material | PBT | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
Компания Zipstore.ru поставляет оптом и в розницу запчасти Pepperl+Fuchs.
В каталоге сайта представлено 13440 запчастей Pepperl+Fuchs. Также вы можете приобрести опции и аксессуары для расширения функциональных возможностей, транспортировки и эксплуатации оборудования. Запчасти в каталоге могут иметь полное название, каталожный номер, фотографию, краткое описание, а также модели принтеров, с которыми они совместимы.
Для оформления заказа вы можете воспользоваться одним из следующих способов:
Мы осуществляем поставки запчастей Pepperl+Fuchs во все города России, а также в Республику Беларусь, Казахстан и другие страны СНГ.
Продажа осуществляется за наличный и безналичный расчет. На сайте указаны розничные цены в рублях и долларах, с учетом НДС. Чтобы узнать оптовые цены на запчасти Pepperl+Fuchs, нужно отправить запрос по электронной почте. Подробнее о способах доставки и оплаты можно узнать в разделе сайта «Оплата и доставка». В разделе «%Скидки и акции» Вы можете найти наиболее выгодные предложения по продаже запчастей, а также сезонные скидки и акции.
При возникновении вопросов по обслуживанию, эксплуатации, ремонту Pepperl+Fuchs, Вы можете проконсультироваться со специалистами на форуме сайта.