| General specifications | ||
|---|---|---|
| Switching function | complementary | |
| Output type | PNP | |
| Rated operating distance | 8 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 6.48 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.4 | |
| Reduction factor r304 | 0.7 | |
| Output type | 4-wire | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V DC | |
| Switching frequency | 0 ... 500 Hz | |
| Hysteresis | typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 25 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector M12 x 1 , 4-pin | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| General information | ||
| Use in the hazardous area | see instruction manuals | |
| Category | 3G 3D | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Function | pushbutton | |
| Color | green | |
| Contact configuration | 1x NO / 1x NC | |
| Usage category | AC12 - 12 ... 250 V AC - 16 A AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 110 V DC - 1 A DC13 - 12 ... 24 V DC - 1A | |
| Number of poles | 2 | |
| Labeling | I | |
| Mechanical specifications | ||
| Height | 110 mm (A) | |
| Width | 110 mm (B) | |
| Depth | 101 mm (C) | |
| External dimension | 116 mm with operators (C1) 125 mm with mounting brackets (K) | |
| Fixing holes distance, height | 110 mm (G) | |
| Fixing holes distance, width | 78 mm (H) | |
| Enclosure cover | fully detachable | |
| Cover fixing | M6 stainless steel socket cap head screws | |
| Fixing holes diameter | 7 mm (J) | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M25 in face B fitted with polyamide Ex e cable gland | |
| Defined entry area | face B | |
| Material | ||
| Enclosure | carbon loaded, antistatic glass fiber reinforced polyester (GRP) | |
| Finish | inherent color black | |
| Seal | one piece solid silicone rubber | |
| Mass | 1.5 kg | |
| Mounting | 7 mm slots moulded into base | |
| Grounding | 2.5 mm2 grounding terminal | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 55 °C (-40 ... 131 °F) @ T4 -40 ... 40 °C (-40 ... 104 °F) @ T6 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3009 X | |
| Marking | II 2 GD Ex db eb mb IIC T* Gb Ex tb IIIC T** °C Db T6/T80 °C @ Ta +40 °C T4/T130 °C @ Ta +55 °C | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0008X | |
| EAC approval | TC RU C-DE.GB06.B.00567 | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Accessories | ||
| Optional accessories | Engraved traffolyte tag label Engraved AISI 316L stainless steel tag label Color in-fill stainless steel tag label | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Function | pushbutton | |
| Color | red | |
| Contact configuration | 1x NO / 1x NC | |
| Usage category | AC12 - 12 ... 250 V AC - 16 A AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 110 V DC - 1 A DC13 - 12 ... 24 V DC - 1A | |
| Number of poles | 2 | |
| Labeling | 0 | |
| Mechanical specifications | ||
| Height | 110 mm (A) | |
| Width | 110 mm (B) | |
| Depth | 101 mm (C) | |
| External dimension | 116 mm with operators (C1) 125 mm with mounting brackets (K) | |
| Fixing holes distance, height | 110 mm (G) | |
| Fixing holes distance, width | 78 mm (H) | |
| Enclosure cover | fully detachable | |
| Cover fixing | M6 stainless steel socket cap head screws | |
| Fixing holes diameter | 7 mm (J) | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 in face B fitted with polyamide Ex e cable gland | |
| Defined entry area | face B | |
| Material | ||
| Enclosure | carbon loaded, antistatic glass fiber reinforced polyester (GRP) | |
| Finish | inherent color black | |
| Seal | one piece solid silicone rubber | |
| Mass | 1.5 kg | |
| Mounting | 7 mm slots moulded into base | |
| Grounding | 2.5 mm2 grounding terminal | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 55 °C (-40 ... 131 °F) @ T4 -40 ... 40 °C (-40 ... 104 °F) @ T6 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3009 X | |
| Marking | II 2 GD Ex db eb mb IIC T* Gb Ex tb IIIC T** °C Db T6/T80 °C @ Ta +40 °C T4/T130 °C @ Ta +55 °C | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0008X | |
| EAC approval | TC RU C-DE.GB06.B.00567 | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Accessories | ||
| Optional accessories | Engraved traffolyte tag label Engraved AISI 316L stainless steel tag label Color in-fill stainless steel tag label | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Function | pushbutton | |
| Color | red | |
| Contact configuration | 1x NO / 1x NC | |
| Usage category | AC12 - 12 ... 250 V AC - 16 A AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 110 V DC - 1 A DC13 - 12 ... 24 V DC - 1A | |
| Number of poles | 2 | |
| Labeling | 0 | |
| Mechanical specifications | ||
| Height | 110 mm (A) | |
| Width | 110 mm (B) | |
| Depth | 101 mm (C) | |
| External dimension | 116 mm with operators (C1) 125 mm with mounting brackets (K) | |
| Fixing holes distance, height | 110 mm (G) | |
| Fixing holes distance, width | 78 mm (H) | |
| Enclosure cover | fully detachable | |
| Cover fixing | M6 stainless steel socket cap head screws | |
| Fixing holes diameter | 7 mm (J) | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M25 in face B fitted with polyamide Ex e cable gland | |
| Defined entry area | face B | |
| Material | ||
| Enclosure | carbon loaded, antistatic glass fiber reinforced polyester (GRP) | |
| Finish | inherent color black | |
| Seal | one piece solid silicone rubber | |
| Mass | 1.5 kg | |
| Mounting | 7 mm slots moulded into base | |
| Grounding | 2.5 mm2 grounding terminal | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 55 °C (-40 ... 131 °F) @ T4 -40 ... 40 °C (-40 ... 104 °F) @ T6 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3009 X | |
| Marking | II 2 GD Ex db eb mb IIC T* Gb Ex tb IIIC T** °C Db T6/T80 °C @ Ta +40 °C T4/T130 °C @ Ta +55 °C | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0008X | |
| EAC approval | TC RU C-DE.GB06.B.00567 | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Accessories | ||
| Optional accessories | Engraved traffolyte tag label Engraved AISI 316L stainless steel tag label Color in-fill stainless steel tag label | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open/closed (NO/NC) programmable | |
| Output type | AS-Interface | |
| Rated operating distance | 8 mm | |
| Installation | flush | |
| Assured operating distance | 0 ... 6.48 mm | |
| Reduction factor rAl | 0.4 | |
| Reduction factor rCu | 0.4 | |
| Reduction factor r304 | 0.7 | |
| Reduction factor rBrass | 0.5 | |
| Slave type | Standard slave | |
| AS-Interface specification | V2.1 | |
| Required master specification | &ge V2.0 | |
| Nominal ratings | ||
| Operating voltage | 26.5 ... 31.9 V via AS-i bus system | |
| Switching frequency | 0 ... 200 Hz | |
| Hysteresis | 1 ... 15 typ. 5 % | |
| Reverse polarity protection | reverse polarity protected | |
| No-load supply current | &le 25 mA | |
| Switching state indicator | dual-LED, yellow | |
| Error indicator | dual-LED, red | |
| Functional safety related parameters | ||
| MTTFd | 926 a | |
| Mission Time (TM) | 20 a | |
| Diagnostic Coverage (DC) | 0 % | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | 4-pin, M12 x 1 connector | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Housing diameter | 18 mm | |
| Degree of protection | IP67 | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Function | control switch, large | |
| Color | black | |
| Shroud | yes | |
| Contact configuration | 2x NO | |
| Switching configuration | 2 position changeover with left OFF | |
| Usage category | AC12 - 12 ... 250 V AC - 16 A AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 110 V DC - 1 A DC13 - 12 ... 24 V DC - 1A | |
| Number of poles | 2 | |
| Operator action | engage - engage | |
| Lockable | padlockable in '0' | |
| Labeling | 0 - l | |
| Mechanical specifications | ||
| Height | 110 mm (A) | |
| Width | 110 mm (B) | |
| Depth | 101 mm (C) | |
| External dimension | 131 mm with operators (C1) 125 mm with mounting brackets (K) | |
| Fixing holes distance, height | 110 mm (G) | |
| Fixing holes distance, width | 78 mm (H) | |
| Enclosure cover | fully detachable | |
| Cover fixing | M6 stainless steel socket cap head screws | |
| Fixing holes diameter | 7 mm (J) | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 in face B fitted with polyamide Ex e cable gland | |
| Defined entry area | face B | |
| Material | ||
| Enclosure | carbon loaded, antistatic glass fiber reinforced polyester (GRP) | |
| Finish | inherent color black | |
| Seal | one piece solid silicone rubber | |
| Mass | 1.5 kg | |
| Mounting | 7 mm slots moulded into base | |
| Grounding | 2.5 mm2 grounding terminal | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 55 °C (-40 ... 131 °F) @ T4 -40 ... 40 °C (-40 ... 104 °F) @ T6 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3009 X | |
| Marking | II 2 GD Ex db eb mb IIC T* Gb Ex tb IIIC T** °C Db T6/T80 °C @ Ta +40 °C T4/T130 °C @ Ta +55 °C | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0008X | |
| EAC approval | TC RU C-DE.GB06.B.00567 | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Accessories | ||
| Optional accessories | Engraved traffolyte tag label Engraved AISI 316L stainless steel tag label Color in-fill stainless steel tag label | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Function | control switch, large | |
| Color | black | |
| Shroud | yes | |
| Contact configuration | 2x NO | |
| Switching configuration | 2 position changeover with left OFF | |
| Usage category | AC12 - 12 ... 250 V AC - 16 A AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 110 V DC - 1 A DC13 - 12 ... 24 V DC - 1A | |
| Number of poles | 2 | |
| Operator action | engage - engage | |
| Lockable | padlockable in '0' | |
| Labeling | 0 - l | |
| Mechanical specifications | ||
| Height | 110 mm (A) | |
| Width | 110 mm (B) | |
| Depth | 101 mm (C) | |
| External dimension | 131 mm with operators (C1) 125 mm with mounting brackets (K) | |
| Fixing holes distance, height | 110 mm (G) | |
| Fixing holes distance, width | 78 mm (H) | |
| Enclosure cover | fully detachable | |
| Cover fixing | M6 stainless steel socket cap head screws | |
| Fixing holes diameter | 7 mm (J) | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M25 in face B fitted with polyamide Ex e cable gland | |
| Defined entry area | face B | |
| Material | ||
| Enclosure | carbon loaded, antistatic glass fiber reinforced polyester (GRP) | |
| Finish | inherent color black | |
| Seal | one piece solid silicone rubber | |
| Mass | 1.5 kg | |
| Mounting | 7 mm slots moulded into base | |
| Grounding | 2.5 mm2 grounding terminal | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 55 °C (-40 ... 131 °F) @ T4 -40 ... 40 °C (-40 ... 104 °F) @ T6 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3009 X | |
| Marking | II 2 GD Ex db eb mb IIC T* Gb Ex tb IIIC T** °C Db T6/T80 °C @ Ta +40 °C T4/T130 °C @ Ta +55 °C | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0008X | |
| EAC approval | TC RU C-DE.GB06.B.00567 | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Accessories | ||
| Optional accessories | Engraved traffolyte tag label Engraved AISI 316L stainless steel tag label Color in-fill stainless steel tag label | |
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | Two-wire | |
| Rated operating distance | 8 mm | |
| Installation | flush | |
| Output polarity | AC/DC | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.4 | |
| Reduction factor r304 | 0.7 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 20 ... 250 V AC/20 ... 300 V DC | |
| Switching frequency | 30 Hz | |
| Hysteresis | 3 ... 15 typ. 5 % | |
| Reverse polarity protection | yes | |
| Short-circuit protection | yes | |
| Voltage drop | &le 8 V | |
| Operating current | 4 ... 300 mA AC/DC | |
| Off-state current | &le 0.8 mA | |
| Operating voltage indicator | LED, green | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | cable PUR , 2 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Function | pushbutton | |
| Color | green | |
| Contact configuration | 1x NO / 1x NC | |
| Usage category | AC12 - 12 ... 250 V AC - 16 A AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 110 V DC - 1 A DC13 - 12 ... 24 V DC - 1A | |
| Number of poles | 2 | |
| Labeling | I | |
| Function 2 | mushroom button | |
| Color | red | |
| Contact configuration | 1x NO / 1x NC | |
| Usage category | AC12 - 12 ... 250 V AC - 16 A AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 110 V DC - 1 A DC13 - 12 ... 24 V DC - 1A | |
| Number of poles | 2 | |
| Operator action | latching , pull to release | |
| Labeling | EMERGENCY STOP / NOT AUS | |
| Mechanical specifications | ||
| Height | 220 mm (A) | |
| Width | 110 mm (B) | |
| Depth | 101 mm (C) | |
| External dimension | 142 mm with operators (C1) 235 mm with mounting brackets (K) | |
| Fixing holes distance, height | 220 mm (G) | |
| Fixing holes distance, width | 78 mm (H) | |
| Enclosure cover | fully detachable | |
| Cover fixing | M6 stainless steel socket cap head screws | |
| Fixing holes diameter | 7 mm (J) | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M25 in face B fitted with polyamide Ex e cable gland | |
| Defined entry area | face B | |
| Material | ||
| Enclosure | carbon loaded, antistatic glass fiber reinforced polyester (GRP) | |
| Finish | inherent color black | |
| Seal | one piece solid silicone rubber | |
| Mass | 3 kg | |
| Mounting | 7 mm slots moulded into base | |
| Grounding | 2.5 mm2 grounding terminal | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 55 °C (-40 ... 131 °F) @ T4 -40 ... 40 °C (-40 ... 104 °F) @ T6 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3009 X | |
| Marking | II 2 GD Ex db eb mb IIC T* Gb Ex tb IIIC T** °C Db T6/T80 °C @ Ta +40 °C T4/T130 °C @ Ta +55 °C | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0008X | |
| EAC approval | TC RU C-DE.GB06.B.00567 | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Accessories | ||
| Optional accessories | Engraved traffolyte tag label Engraved AISI 316L stainless steel tag label Color in-fill stainless steel tag label | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Function | pushbutton | |
| Color | green | |
| Contact configuration | 1x NO / 1x NC | |
| Usage category | AC12 - 12 ... 250 V AC - 16 A AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 110 V DC - 1 A DC13 - 12 ... 24 V DC - 1A | |
| Number of poles | 2 | |
| Labeling | I | |
| Function 2 | pushbutton | |
| Color | red | |
| Contact configuration | 1x NO / 1x NC | |
| Usage category | AC12 - 12 ... 250 V AC - 16 A AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 110 V DC - 1 A DC13 - 12 ... 24 V DC - 1A | |
| Number of poles | 2 | |
| Labeling | O | |
| Mechanical specifications | ||
| Height | 220 mm (A) | |
| Width | 110 mm (B) | |
| Depth | 101 mm (C) | |
| External dimension | 116 mm with operators (C1) 235 mm with mounting brackets (K) | |
| Fixing holes distance, height | 220 mm (G) | |
| Fixing holes distance, width | 78 mm (H) | |
| Enclosure cover | fully detachable | |
| Cover fixing | M6 stainless steel socket cap head screws | |
| Fixing holes diameter | 7 mm (J) | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M25 in face B fitted with polyamide Ex e cable gland | |
| Defined entry area | face B | |
| Material | ||
| Enclosure | carbon loaded, antistatic glass fiber reinforced polyester (GRP) | |
| Finish | inherent color black | |
| Seal | one piece solid silicone rubber | |
| Mass | 3 kg | |
| Mounting | 7 mm slots moulded into base | |
| Grounding | 2.5 mm2 grounding terminal | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 55 °C (-40 ... 131 °F) @ T4 -40 ... 40 °C (-40 ... 104 °F) @ T6 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3009 X | |
| Marking | II 2 GD Ex db eb mb IIC T* Gb Ex tb IIIC T** °C Db T6/T80 °C @ Ta +40 °C T4/T130 °C @ Ta +55 °C | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0008X | |
| EAC approval | TC RU C-DE.GB06.B.00567 | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Accessories | ||
| Optional accessories | Engraved traffolyte tag label Engraved AISI 316L stainless steel tag label Color in-fill stainless steel tag label | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Function | illuminated pushbutton | |
| Color | green | |
| Contact configuration | 1x NO | |
| Usage category | AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 24 V DC - 1 A | |
| Number of poles | 1 | |
| Mechanical specifications | ||
| Height | 102 mm (A) | |
| Width | 116 mm (B) | |
| Depth | 85.5 mm (C) | |
| External dimension | 100 mm with operators (C1) 92.2 mm with screws (C2) 145 mm with mounting brackets (K) | |
| Fixing holes distance, height | 41 mm (G) | |
| Fixing holes distance, width | 130 mm (H) | |
| Enclosure cover | fully detachable | |
| Cover fixing | M6 stainless steel hexagon head screws | |
| Fixing holes diameter | 6.1 mm (J) | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1 x M20 in face A fitted with polyamide Ex e stopping plug 1x M20 in face B fitted with polyamide Ex e cable gland | |
| Defined entry area | face A and face B | |
| Material | ||
| Enclosure | 1.5 mm 316L, (1.4404) stainless steel | |
| Finish | electropolished | |
| Seal | one piece closed cell neoprene | |
| Mass | 1.5 kg | |
| Mounting | mouting brackets with 6.1 mm screw holes | |
| Grounding | M6 internal/external brass grounding bolt | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 55 °C (-40 ... 131 °F) @ T4 -40 ... 40 °C (-40 ... 104 °F) @ T6 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3009 X | |
| Marking | II 2 GD Ex db eb mb IIC T* Gb Ex tb IIIC T** °C Db T6/T80 °C @ Ta +40 °C T4/T130 °C @ Ta +55 °C | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0008X | |
| EAC approval | TC RU C-DE.GB06.B.00567 | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Accessories | ||
| Optional accessories | Engraved traffolyte tag label Engraved AISI 316L stainless steel tag label Color in-fill stainless steel tag label | |
| General specifications | ||
|---|---|---|
| Switching function | Normally closed (NC) | |
| Output type | Two-wire | |
| Rated operating distance | 8 mm | |
| Installation | flush | |
| Output polarity | AC/DC | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.4 | |
| Reduction factor r304 | 0.7 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 20 ... 250 V AC/20 ... 300 V DC | |
| Switching frequency | 30 Hz | |
| Hysteresis | 3 ... 15 typ. 5 % | |
| Reverse polarity protection | yes | |
| Short-circuit protection | yes | |
| Voltage drop | &le 8 V | |
| Operating current | 4 ... 300 mA AC/DC | |
| Off-state current | &le 0.8 mA | |
| Operating voltage indicator | LED, green | |
| Switching state indicator | LED, yellow | |
| Standard conformity | ||
| Standards | IEC / EN 60947-5-2:2004 | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | Connector 1/2"-20 UN , 3-pin | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Function | illuminated pushbutton | |
| Color | red | |
| Contact configuration | 1x NC | |
| Usage category | AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 24 V DC - 1 A | |
| Number of poles | 1 | |
| Mechanical specifications | ||
| Height | 102 mm (A) | |
| Width | 116 mm (B) | |
| Depth | 85.5 mm (C) | |
| External dimension | 100 mm with operators (C1) 92.2 mm with screws (C2) 145 mm with mounting brackets (K) | |
| Fixing holes distance, height | 41 mm (G) | |
| Fixing holes distance, width | 130 mm (H) | |
| Enclosure cover | fully detachable | |
| Cover fixing | M6 stainless steel hexagon head screws | |
| Fixing holes diameter | 6.1 mm (J) | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1 x M20 in face A fitted with polyamide Ex e stopping plug 1x M20 in face B fitted with polyamide Ex e cable gland | |
| Defined entry area | face A and face B | |
| Material | ||
| Enclosure | 1.5 mm 316L, (1.4404) stainless steel | |
| Finish | electropolished | |
| Seal | one piece closed cell neoprene | |
| Mass | 1.5 kg | |
| Mounting | mouting brackets with 6.1 mm screw holes | |
| Grounding | M6 internal/external brass grounding bolt | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 55 °C (-40 ... 131 °F) @ T4 -40 ... 40 °C (-40 ... 104 °F) @ T6 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3009 X | |
| Marking | II 2 GD Ex db eb mb IIC T* Gb Ex tb IIIC T** °C Db T6/T80 °C @ Ta +40 °C T4/T130 °C @ Ta +55 °C | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0008X | |
| EAC approval | TC RU C-DE.GB06.B.00567 | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Accessories | ||
| Optional accessories | Engraved traffolyte tag label Engraved AISI 316L stainless steel tag label Color in-fill stainless steel tag label | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Terminal torque | 0.8 Nm | |
| Function | illuminated pushbutton | |
| Color | green | |
| Contact configuration | 1x NC | |
| Usage category | AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 24 V DC - 1 A | |
| Number of poles | 2 | |
| Mechanical specifications | ||
| Cable type | non-armored cables | |
| Clamping range | 5.5 ... 13 mm (D) | |
| Covering | Protective cover fully detachable | |
| Cover fixing | Phillips head screw | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 cable gland in protective cover | |
| Material | ||
| Housing | Polyamide (PA) | |
| Finish | inherent color black | |
| Seal | silicone | |
| Washer gasket | silicone | |
| Mass | 150 g max. | |
| Dimensions | ||
| Height | 77 mm (A) | |
| Width | 44 mm (B) | |
| Depth | 105 mm (C) | |
| Actuator head diameter | 39 mm (D2) | |
| Panel wall thickness | 1 ... 6 mm (PT) | |
| Diameter thru-hole | 30.6 mm (DT) | |
| Length outside enclosure | 17.5 mm (H) | |
| Width across flats | 24 mm (SW1) | |
| Total length | 130 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 2 Nm (SW1) | |
| Mounting | via actuator head | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16ATEX3106X | |
| Marking | II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0046X | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Terminal torque | 0.8 Nm | |
| Function | illuminated pushbutton | |
| Color | green | |
| Contact configuration | 1x NO | |
| Usage category | AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 24 V DC - 1 A | |
| Number of poles | 2 | |
| Mechanical specifications | ||
| Cable type | non-armored cables | |
| Clamping range | 5.5 ... 13 mm (D) | |
| Covering | Protective cover fully detachable | |
| Cover fixing | Phillips head screw | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 cable gland in protective cover | |
| Material | ||
| Housing | Polyamide (PA) | |
| Finish | inherent color black | |
| Seal | silicone | |
| Washer gasket | silicone | |
| Mass | 150 g max. | |
| Dimensions | ||
| Height | 77 mm (A) | |
| Width | 44 mm (B) | |
| Depth | 105 mm (C) | |
| Actuator head diameter | 39 mm (D2) | |
| Panel wall thickness | 1 ... 6 mm (PT) | |
| Diameter thru-hole | 30.6 mm (DT) | |
| Length outside enclosure | 17.5 mm (H) | |
| Width across flats | 24 mm (SW1) | |
| Total length | 130 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 2 Nm (SW1) | |
| Mounting | via actuator head | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16ATEX3106X | |
| Marking | II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0046X | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | Two-wire | |
| Rated operating distance | 8 mm | |
| Installation | flush | |
| Output polarity | AC/DC | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.4 | |
| Reduction factor r304 | 0.7 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 20 ... 250 V AC/20 ... 300 V DC | |
| Switching frequency | 30 Hz | |
| Hysteresis | 3 ... 15 typ. 5 % | |
| Reverse polarity protection | reverse polarity tolerant | |
| Short-circuit protection | yes | |
| Voltage drop | &le 8 V | |
| Operating current | 4 ... 300 mA AC/DC | |
| Off-state current | &le 0.8 mA | |
| Operating voltage indicator | LED, green | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | cable PUR , 10 m | |
| Core cross-section | 0.5 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Terminal torque | 0.8 Nm | |
| Function | illuminated pushbutton | |
| Color | red | |
| Contact configuration | 1x NC | |
| Usage category | AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 24 V DC - 1 A | |
| Number of poles | 2 | |
| Mechanical specifications | ||
| Cable type | non-armored cables | |
| Clamping range | 5.5 ... 13 mm (D) | |
| Covering | Protective cover fully detachable | |
| Cover fixing | Phillips head screw | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 cable gland in protective cover | |
| Material | ||
| Housing | Polyamide (PA) | |
| Finish | inherent color black | |
| Seal | silicone | |
| Washer gasket | silicone | |
| Mass | 150 g max. | |
| Dimensions | ||
| Height | 77 mm (A) | |
| Width | 44 mm (B) | |
| Depth | 105 mm (C) | |
| Actuator head diameter | 39 mm (D2) | |
| Panel wall thickness | 1 ... 6 mm (PT) | |
| Diameter thru-hole | 30.6 mm (DT) | |
| Length outside enclosure | 17.5 mm (H) | |
| Width across flats | 24 mm (SW1) | |
| Total length | 130 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 2 Nm (SW1) | |
| Mounting | via actuator head | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16ATEX3106X | |
| Marking | II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0046X | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2.5 mm2 | |
| Terminal torque | 0.8 Nm | |
| Function | illuminated pushbutton | |
| Color | red | |
| Contact configuration | 1x NO | |
| Usage category | AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 24 V DC - 1 A | |
| Number of poles | 2 | |
| Mechanical specifications | ||
| Cable type | non-armored cables | |
| Clamping range | 5.5 ... 13 mm (D) | |
| Covering | Protective cover fully detachable | |
| Cover fixing | Phillips head screw | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 cable gland in protective cover | |
| Material | ||
| Housing | Polyamide (PA) | |
| Finish | inherent color black | |
| Seal | silicone | |
| Washer gasket | silicone | |
| Mass | 150 g max. | |
| Dimensions | ||
| Height | 77 mm (A) | |
| Width | 44 mm (B) | |
| Depth | 105 mm (C) | |
| Actuator head diameter | 39 mm (D2) | |
| Panel wall thickness | 1 ... 6 mm (PT) | |
| Diameter thru-hole | 30.6 mm (DT) | |
| Length outside enclosure | 17.5 mm (H) | |
| Width across flats | 24 mm (SW1) | |
| Total length | 130 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 2 Nm (SW1) | |
| Mounting | via actuator head | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16ATEX3106X | |
| Marking | II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0046X | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2x 2.5 mm2 | |
| Terminal torque | 1.1 Nm | |
| Function | LED indicator | |
| Color | blue | |
| Rated operating voltage | 12 ... 250 V AC/DC | |
| Mechanical specifications | ||
| Cable type | non-armored cables | |
| Clamping range | 5.5 ... 13 mm (D) | |
| Covering | Protective cover fully detachable | |
| Cover fixing | Phillips head screw | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 cable gland in protective cover | |
| Material | ||
| Housing | Polyamide (PA) | |
| Finish | inherent color black | |
| Seal | silicone | |
| Washer gasket | silicone | |
| Mass | 150 g max. | |
| Dimensions | ||
| Height | 77 mm (A) | |
| Width | 44 mm (B) | |
| Depth | 105 mm (C) | |
| Actuator head diameter | 39 mm (D2) | |
| Panel wall thickness | 1 ... 6 mm (PT) | |
| Diameter thru-hole | 30.6 mm (DT) | |
| Length outside enclosure | 23.6 mm (H) | |
| Width across flats | 24 mm (SW1) | |
| Total length | 136.1 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 2 Nm (SW1) | |
| Mounting | via actuator head | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3106 X | |
| Marking | II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0046X | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | Two-wire | |
| Rated operating distance | 8 mm | |
| Installation | flush | |
| Output polarity | AC/DC | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.4 | |
| Reduction factor r304 | 0.7 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 20 ... 250 V AC/20 ... 300 V DC | |
| Switching frequency | 30 Hz | |
| Hysteresis | 3 ... 15 typ. 5 % | |
| Reverse polarity protection | reverse polarity tolerant | |
| Short-circuit protection | yes | |
| Voltage drop | &le 8 V | |
| Operating current | 4 ... 300 mA AC/DC | |
| Off-state current | &le 0.8 mA | |
| Operating voltage indicator | LED, green | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | Certified by China Compulsory Certification (CCC) | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Mechanical specifications | ||
| Connection type | Connector 1/2"-20 UN , 3-pin | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2x 2.5 mm2 | |
| Terminal torque | 1.1 Nm | |
| Function | LED indicator | |
| Color | green | |
| Rated operating voltage | 12 ... 250 V AC/DC | |
| Mechanical specifications | ||
| Cable type | non-armored cables | |
| Clamping range | 5.5 ... 13 mm (D) | |
| Covering | Protective cover fully detachable | |
| Cover fixing | Phillips head screw | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 cable gland in protective cover | |
| Material | ||
| Housing | Polyamide (PA) | |
| Finish | inherent color black | |
| Seal | silicone | |
| Washer gasket | silicone | |
| Mass | 150 g max. | |
| Dimensions | ||
| Height | 77 mm (A) | |
| Width | 44 mm (B) | |
| Depth | 105 mm (C) | |
| Actuator head diameter | 39 mm (D2) | |
| Panel wall thickness | 1 ... 6 mm (PT) | |
| Diameter thru-hole | 30.6 mm (DT) | |
| Length outside enclosure | 23.6 mm (H) | |
| Width across flats | 24 mm (SW1) | |
| Total length | 136.1 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 2 Nm (SW1) | |
| Mounting | via actuator head | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3106 X | |
| Marking | II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0046X | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2x 2.5 mm2 | |
| Terminal torque | 1.1 Nm | |
| Function | LED indicator | |
| Color | amber | |
| Rated operating voltage | 12 ... 250 V AC/DC | |
| Mechanical specifications | ||
| Cable type | non-armored cables | |
| Clamping range | 5.5 ... 13 mm (D) | |
| Covering | Protective cover fully detachable | |
| Cover fixing | Phillips head screw | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 cable gland in protective cover | |
| Material | ||
| Housing | Polyamide (PA) | |
| Finish | inherent color black | |
| Seal | silicone | |
| Washer gasket | silicone | |
| Mass | 150 g max. | |
| Dimensions | ||
| Height | 77 mm (A) | |
| Width | 44 mm (B) | |
| Depth | 105 mm (C) | |
| Actuator head diameter | 39 mm (D2) | |
| Panel wall thickness | 1 ... 6 mm (PT) | |
| Diameter thru-hole | 30.6 mm (DT) | |
| Length outside enclosure | 23.6 mm (H) | |
| Width across flats | 24 mm (SW1) | |
| Total length | 136.1 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 2 Nm (SW1) | |
| Mounting | via actuator head | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3106 X | |
| Marking | II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0046X | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2x 2.5 mm2 | |
| Terminal torque | 1.1 Nm | |
| Function | LED indicator | |
| Color | red | |
| Rated operating voltage | 12 ... 250 V AC/DC | |
| Mechanical specifications | ||
| Cable type | non-armored cables | |
| Clamping range | 5.5 ... 13 mm (D) | |
| Covering | Protective cover fully detachable | |
| Cover fixing | Phillips head screw | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 cable gland in protective cover | |
| Material | ||
| Housing | Polyamide (PA) | |
| Finish | inherent color black | |
| Seal | silicone | |
| Washer gasket | silicone | |
| Mass | 150 g max. | |
| Dimensions | ||
| Height | 77 mm (A) | |
| Width | 44 mm (B) | |
| Depth | 105 mm (C) | |
| Actuator head diameter | 39 mm (D2) | |
| Panel wall thickness | 1 ... 6 mm (PT) | |
| Diameter thru-hole | 30.6 mm (DT) | |
| Length outside enclosure | 23.6 mm (H) | |
| Width across flats | 24 mm (SW1) | |
| Total length | 136.1 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 2 Nm (SW1) | |
| Mounting | via actuator head | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3106 X | |
| Marking | II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0046X | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| General specifications | ||
|---|---|---|
| Switching function | Normally open (NO) | |
| Output type | PNP | |
| Rated operating distance | 8 mm | |
| Installation | flush | |
| Output polarity | DC | |
| Assured operating distance | 0 ... 6.48 mm | |
| Reduction factor rAl | 0.45 | |
| Reduction factor rCu | 0.4 | |
| Reduction factor r304 | 0.7 | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 10 ... 30 V | |
| Switching frequency | 0 ... 500 Hz | |
| Hysteresis | typ. 5% | |
| Reverse polarity protection | reverse polarity protected | |
| Short-circuit protection | pulsing | |
| Voltage drop | &le 3 V | |
| Operating current | 0 ... 200 mA | |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
| No-load supply current | &le 15 mA | |
| Switching state indicator | LED, yellow | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CSA approval | cCSAus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | Connector 7/8 inch-16 UN , 4-pin | |
| Core cross-section | 0.34 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2x 2.5 mm2 | |
| Terminal torque | 1.1 Nm | |
| Function | LED indicator | |
| Color | white | |
| Rated operating voltage | 12 ... 250 V AC/DC | |
| Mechanical specifications | ||
| Cable type | non-armored cables | |
| Clamping range | 5.5 ... 13 mm (D) | |
| Covering | Protective cover fully detachable | |
| Cover fixing | Phillips head screw | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 cable gland in protective cover | |
| Material | ||
| Housing | Polyamide (PA) | |
| Finish | inherent color black | |
| Seal | silicone | |
| Washer gasket | silicone | |
| Mass | 150 g max. | |
| Dimensions | ||
| Height | 77 mm (A) | |
| Width | 44 mm (B) | |
| Depth | 105 mm (C) | |
| Actuator head diameter | 39 mm (D2) | |
| Panel wall thickness | 1 ... 6 mm (PT) | |
| Diameter thru-hole | 30.6 mm (DT) | |
| Length outside enclosure | 23.6 mm (H) | |
| Width across flats | 24 mm (SW1) | |
| Total length | 136.1 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 2 Nm (SW1) | |
| Mounting | via actuator head | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16 ATEX 3106 X | |
| Marking | II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0046X | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2x 2.5 mm2 | |
| Terminal torque | 0.8 Nm | |
| Function | double pushbutton | |
| Color | choice of red, green, amber, white, blue, black | |
| Contact configuration | 2x NC | |
| Usage category | AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 24 V DC - 1 A | |
| Number of poles | 2 | |
| Operator action | momentary | |
| Labeling | various, see features | |
| Mechanical specifications | ||
| Cable type | non-armored cables | |
| Clamping range | 5.5 ... 13 mm (D) | |
| Covering | Protective cover fully detachable | |
| Cover fixing | Phillips head screw | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 cable gland in protective cover | |
| Material | ||
| Housing | Polyamide (PA) | |
| Finish | inherent color black | |
| Seal | silicone | |
| Washer gasket | silicone | |
| Mass | 150 g max. | |
| Dimensions | ||
| Height | 77 mm (A) | |
| Width | 44 mm (B) | |
| Depth | 105 mm (C) | |
| Actuator head diameter | 39 mm (D2) | |
| Panel wall thickness | 1 ... 6 mm (PT) | |
| Diameter thru-hole | 30.6 mm (DT) | |
| Length outside enclosure | 15.5 mm (H) | |
| Width across flats | 24 mm (SW1) | |
| Total length | 128 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 2 Nm (SW1) | |
| Mounting | via actuator head | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16ATEX3106X | |
| Marking | II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0046X | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2x 2.5 mm2 | |
| Terminal torque | 0.8 Nm | |
| Function | double pushbutton | |
| Color | choice of red, green, amber, white, blue, black | |
| Contact configuration | 1x NO / 1x NC | |
| Usage category | AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 24 V DC - 1 A | |
| Number of poles | 2 | |
| Operator action | momentary | |
| Labeling | various, see features | |
| Mechanical specifications | ||
| Cable type | non-armored cables | |
| Clamping range | 5.5 ... 13 mm (D) | |
| Covering | Protective cover fully detachable | |
| Cover fixing | Phillips head screw | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 cable gland in protective cover | |
| Material | ||
| Housing | Polyamide (PA) | |
| Finish | inherent color black | |
| Seal | silicone | |
| Washer gasket | silicone | |
| Mass | 150 g max. | |
| Dimensions | ||
| Height | 77 mm (A) | |
| Width | 44 mm (B) | |
| Depth | 105 mm (C) | |
| Actuator head diameter | 39 mm (D2) | |
| Panel wall thickness | 1 ... 6 mm (PT) | |
| Diameter thru-hole | 30.6 mm (DT) | |
| Length outside enclosure | 15.5 mm (H) | |
| Width across flats | 24 mm (SW1) | |
| Total length | 128 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 2 Nm (SW1) | |
| Mounting | via actuator head | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16ATEX3106X | |
| Marking | II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0046X | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
| General specifications | ||
|---|---|---|
| Output type | Analog current output | |
| Installation | flush | |
| Output polarity | DC | |
| Measurement range | 3 ... 8 mm | |
| Output type | 3-wire | |
| Nominal ratings | ||
| Operating voltage | 15 ... 30 V DC | |
| Repeat accuracy | 0 ... 200 µm | |
| Recovery time | 1 ... 10 ms typ. 5 ms | |
| No-load supply current | &le 12 mA | |
| Analog output | ||
| Output type | 0 ... 20 mA | |
| Linearity error | &le ± 5 % of full-scale value | |
| Load resistor | &le 500 &Omega | |
| Temperature drift | &le ± 0.15 %/K of the measured value | |
| Approvals and certificates | ||
| UL approval | cULus Listed, General Purpose | |
| CCC approval | CCC approval / marking not required for products rated &le36 V | |
| Ambient conditions | ||
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
| Mechanical specifications | ||
| Connection type | cable PVC , 2 m | |
| Core cross-section | 0.75 mm2 | |
| Housing material | brass, nickel-plated | |
| Sensing face | PBT | |
| Degree of protection | IP67 | |
| Описание оборудования | ||
|---|---|---|
| Valve positioner and valve control module | ||
| Electrical specifications | ||
|---|---|---|
| Operating voltage | 250 V max. | |
| Operating current | 16 A max. | |
| Terminal capacity | 2x 2.5 mm2 | |
| Terminal torque | 0.8 Nm | |
| Function | double pushbutton | |
| Color | choice of red, green, amber, white, blue, black | |
| Contact configuration | 2x NO | |
| Usage category | AC15 - 12 ... 250 V AC - 10 A DC13 - 12 ... 24 V DC - 1 A | |
| Number of poles | 2 | |
| Operator action | momentary | |
| Labeling | various, see features | |
| Mechanical specifications | ||
| Cable type | non-armored cables | |
| Clamping range | 5.5 ... 13 mm (D) | |
| Covering | Protective cover fully detachable | |
| Cover fixing | Phillips head screw | |
| Degree of protection | IP66 | |
| Cable entry | ||
| Number of cable entries | 1x M20 cable gland in protective cover | |
| Material | ||
| Housing | Polyamide (PA) | |
| Finish | inherent color black | |
| Seal | silicone | |
| Washer gasket | silicone | |
| Mass | 150 g max. | |
| Dimensions | ||
| Height | 77 mm (A) | |
| Width | 44 mm (B) | |
| Depth | 105 mm (C) | |
| Actuator head diameter | 39 mm (D2) | |
| Panel wall thickness | 1 ... 6 mm (PT) | |
| Diameter thru-hole | 30.6 mm (DT) | |
| Length outside enclosure | 15.5 mm (H) | |
| Width across flats | 24 mm (SW1) | |
| Total length | 128 mm (L) | |
| Tightening torque | ||
| Nut torque at enclosure | 2 Nm (SW1) | |
| Mounting | via actuator head | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 50 °C (-40 ... 122 °F) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CML 16ATEX3106X | |
| Marking | II 2 GD Ex de IIC T6 Gb Ex tb IIIC T80 °C Db | |
| International approvals | ||
| IECEx approval | IECEx CML 16.0046X | |
| Conformity | ||
| Degree of protection | EN 60529 | |
| General information | ||
| Supplementary information | EC-Type Examination Certificate, Statement of Conformity, Declaration of Conformity, Attestation of Conformity and instructions have to be observed where applicable. For information see www.pepperl-fuchs.com. | |
Pepperl+Fuchs — немецкий бренд с более чем 75-летней историей инженерного превосходства. Основанная в 1945 году в Мангейме, компания стала пионером бесконтактных датчиков и одним из мировых лидеров в области intrinsically safe решений для опасных сред. Сегодня Pepperl+Fuchs объединяет два направления — Factory Automation и Process Automation — предлагая датчики, интерфейсную электронику, системы взрывозащиты и HMI, которые повышают надежность, безопасность и эффективность производственных процессов.
Решения Pepperl+Fuchs используются в автомобильной промышленности, машиностроении, пищевой и фармацевтической отраслях, логистике и складской автоматизации, а также в нефтегазовом, химическом и горнодобывающем секторах, на объектах энергетики, водоснабжения и очистки стоков. Бренд одинаково эффективен для модернизации отдельных участков и для комплексной автоматизации линий и установок.
Определите среду (включая наличие взрывоопасных зон), необходимые интерфейсы и уровень безопасности, диапазон измерений и точность, а также условия монтажа. Сверьте каталожные номера с требуемыми сертификатами и аксессуарами. При сложных задачах стоит привлечь инженера для подбора комплекта устройств с учетом специфики технологического процесса.
Pepperl+Fuchs — это инвестиция в надежность, безопасность и предсказуемые результаты. Выбирайте оригинальные решения бренда для уверенной работы оборудования сегодня и готовности к задачам завтрашнего дня.