Каталожный номер: 180846
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 4 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 3.24 mm |
| Reduction factor rAl | 0.49 |
| Reduction factor rCu | 0.47 |
| Reduction factor r304 | 0.76 |
| Nominal ratings |
|---|
| Operating voltage | 3.5 ... 30 V |
| Switching frequency | 0 ... 1000 Hz |
| Hysteresis | typ. 5 % |
| Reverse polarity protection | conducting |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3.5 V |
| Temperature drift | ± 15% |
| Operating current | 2 ... 100 mA |
| Off-state current | 0.4 ... 0.6 mA typ. 0.5 mA |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | brass, nickel-plated |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP67 |
Каталожный номер: 204742
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 4 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 3.24 mm |
| Reduction factor rAl | 0.45 |
| Reduction factor rCu | 0.35 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V |
| Switching frequency | 0 ... 800 Hz |
| Hysteresis | typ. 5% |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C |
| No-load supply current | &le 15 mA |
| Switching state indicator | Multihole-LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 990 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP67 |
| General information |
|---|
| Scope of delivery | 2 self locking nuts in scope of delivery |
Каталожный номер: 226330
| General specifications |
|---|
| Switching function | Normally open/closed (NO/NC) programmable |
| Output type | AS-Interface |
| Rated operating distance | 4 mm |
| Installation | flush |
| Assured operating distance | 0 ... 3.24 mm |
| Actual operating distance | 3.6 ... 4.4 mm typ. 4 mm |
| Reduction factor rAl | 0.23 |
| Reduction factor rCu | 0.21 |
| Reduction factor r304 | 0.7 |
| Slave type | Standard slave |
| AS-Interface specification | V2.1 |
| Required master specification | &ge V2.1 |
| Nominal ratings |
|---|
| Operating voltage | 26.5 ... 31.9 V via AS-i bus system |
| Switching frequency | 0 ... 500 Hz |
| Hysteresis | 1 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Voltage drop at IL | |
| Voltage drop IL = 20 mA, switching element on | 3.4 ... 5 V typ. 4.3 V |
| No-load supply current | &le 25 mA |
| Switching state indicator | dual-LED, yellow |
| Error indicator | dual-LED, red |
| Functional safety related parameters |
|---|
| MTTFd | 2140 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP67 |
Каталожный номер: 180330
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | NPN |
| Rated operating distance | 4 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 3.24 mm |
| Reduction factor rAl | 0.45 |
| Reduction factor rCu | 0.4 |
| Reduction factor r304 | 0.75 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V |
| Switching frequency | 0 ... 1000 Hz |
| Hysteresis | typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Rated insulation voltage | 60 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA |
| No-load supply current | &le 10 mA |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 1050 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| Protection class | II |
| Rated insulation voltage | 60 V |
| Rated impulse withstand voltage | 800 V |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| E1 Type approval | 10R-04 |
| Ambient conditions |
|---|
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 2 m |
| Core cross-section | 0.75 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP69K |
| Mass | 120 g |
Каталожный номер: 180331
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NPN |
| Rated operating distance | 4 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 3.24 mm |
| Reduction factor rAl | 0.45 |
| Reduction factor rCu | 0.4 |
| Reduction factor r304 | 0.75 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V |
| Switching frequency | 0 ... 1000 Hz |
| Hysteresis | typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Rated insulation voltage | 60 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA |
| No-load supply current | &le 10 mA |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 1090 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| Protection class | II |
| Rated insulation voltage | 60 V |
| Rated impulse withstand voltage | 800 V |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| E1 Type approval | 10R-04 |
| Ambient conditions |
|---|
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 2 m |
| Core cross-section | 0.75 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP69K |
| Mass | 120 g |
Каталожный номер: 180332
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 4 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 3.24 mm |
| Reduction factor rAl | 0.45 |
| Reduction factor rCu | 0.4 |
| Reduction factor r304 | 0.75 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V |
| Switching frequency | 0 ... 1000 Hz |
| Hysteresis | typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Rated insulation voltage | 60 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA |
| No-load supply current | &le 10 mA |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 1050 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| Protection class | II |
| Rated insulation voltage | 60 V |
| Rated impulse withstand voltage | 800 V |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| E1 Type approval | 10R-04 |
| Ambient conditions |
|---|
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 2 m |
| Core cross-section | 0.75 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP69K |
| Mass | 120 g |
Каталожный номер: 180333
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | PNP |
| Rated operating distance | 4 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 3.24 mm |
| Reduction factor rAl | 0.45 |
| Reduction factor rCu | 0.4 |
| Reduction factor r304 | 0.75 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V |
| Switching frequency | 0 ... 1000 Hz |
| Hysteresis | typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Rated insulation voltage | 60 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA typ. 0.1 µA |
| No-load supply current | &le 10 mA |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 1090 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| Protection class | II |
| Rated insulation voltage | 60 V |
| Rated impulse withstand voltage | 800 V |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| E1 Type approval | 10R-04 |
| Ambient conditions |
|---|
| Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 2 m |
| Core cross-section | 0.75 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP69K |
| Mass | 120 g |
Каталожный номер: 908485
| General specifications |
|---|
| Switching function | complementary |
| Output type | PNP |
| Rated operating distance | 40 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 32.4 mm |
| Reduction factor rAl | 0.25 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.85 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V DC |
| Switching frequency | 0 ... 80 Hz |
| Hysteresis | typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA |
| No-load supply current | &le 20 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 680 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | screw terminals |
| Core cross-section | up to 2.5 mm2 |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP68 |
Каталожный номер: 280550
| General specifications |
|---|
| Switching function | complementary |
| Output type | PNP |
| Rated operating distance | 40 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 32.4 mm |
| Reduction factor rAl | 0.25 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.85 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V |
| Switching frequency | 0 ... 80 Hz |
| Hysteresis | typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA |
| No-load supply current | &le 20 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 630 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | screw terminals |
| Information for connection | A maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 % |
| Core cross-section | up to 2.5 mm2 |
| Minimum core cross-section | without wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2 |
| Maximum core cross-section | without wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2 |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP68 |
Каталожный номер: 908802
| General specifications |
|---|
| Switching function | complementary |
| Output type | PNP |
| Rated operating distance | 40 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 32.4 mm |
| Reduction factor rAl | 0.25 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.85 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V DC |
| Switching frequency | 0 ... 80 Hz |
| Hysteresis | 3 ... 15 % 5 % typical |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA |
| No-load supply current | &le 20 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 680 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | screw terminals |
| Core cross-section | up to 2.5 mm2 |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP68 |
Каталожный номер: 129427
| General specifications |
|---|
| Switching function | complementary |
| Output type | PNP |
| Rated operating distance | 40 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 32.4 mm |
| Reduction factor rAl | 0.25 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.85 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V DC |
| Switching frequency | 0 ... 80 Hz |
| Hysteresis | typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA |
| No-load supply current | &le 20 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 630 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP68 |
Каталожный номер: 129428
| General specifications |
|---|
| Switching function | complementary |
| Output type | PNP |
| Rated operating distance | 40 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 32.4 mm |
| Actual operating distance | 36 ... 44 mm |
| Reduction factor rAl | 0.25 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.85 |
| Output type | 4-wire |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V |
| Switching frequency | 0 ... 80 Hz |
| Hysteresis | typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Voltage drop | &le 3 V |
| Temperature drift | -10 ... 15 % at < -25 °C |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA |
| No-load supply current | &le 20 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 554 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | screw terminals |
| Information for connection | A maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 % |
| Core cross-section | up to 2.5 mm2 |
| Minimum core cross-section | without wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2 |
| Maximum core cross-section | without wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2 |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP68 |
Каталожный номер: 181790
| General specifications |
|---|
| Switching function | complementary |
| Output type | PNP |
| Rated operating distance | 40 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 32.4 mm |
| Reduction factor rAl | 0.25 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.85 |
| Output type | 4-wire |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V |
| Switching frequency | 0 ... 80 Hz |
| Hysteresis | typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA |
| No-load supply current | &le 20 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 554 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP68 |
Каталожный номер: 180491
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 40 mm |
| Installation | flush |
| Assured operating distance | 0 ... 32 mm |
| Actual operating distance | 36 ... 44 mm typ. 40 mm |
| Reduction factor rAl | 0.35 |
| Reduction factor rCu | 0.35 |
| Reduction factor r304 | 0.8 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Installation conditions | |
| F | 100 mm |
| Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) |
| Switching frequency | 0 ... 80 Hz |
| Hysteresis | 0 ... 5 typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | yes |
| Current consumption | |
| Measuring plate not detected | &ge 3 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 2368 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Electromagnetic compatibility | NE 21:2007 |
| Approvals and certificates |
|---|
| FM approval | |
| Control drawing | 116-0165 |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP67 |
| General information |
|---|
| Use in the hazardous area | see instruction manuals |
| Category | 1G 2G 1D |
Каталожный номер: 123458
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 40 mm |
| Installation | flush |
| Assured operating distance | 0 ... 32 mm |
| Actual operating distance | 36 ... 44 mm typ. 40 mm |
| Reduction factor rAl | 0.35 |
| Reduction factor rCu | 0.35 |
| Reduction factor r304 | 0.8 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Installation conditions | |
| F | 100 mm |
| Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) |
| Switching frequency | 0 ... 80 Hz |
| Hysteresis | 0 ... 5 typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | yes |
| Current consumption | |
| Measuring plate not detected | &ge 3 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | LED, yellow |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Electromagnetic compatibility | NE 21:2007 |
| Approvals and certificates |
|---|
| FM approval | |
| Control drawing | 116-0165 |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | screw terminals |
| Core cross-section | &le 2.5 mm2 |
| Housing material | PBT/metal |
| Sensing face | PBT |
| Degree of protection | IP67 |
| General information |
|---|
| Use in the hazardous area | see instruction manuals |
| Category | 1G 2G 1D |
Каталожный номер: 130544
| General specifications |
|---|
| Switching function | Normally open/closed (NO/NC) |
| Output type | Two-wire |
| Rated operating distance | 40 mm |
| Installation | flush |
| Output polarity | AC |
| Assured operating distance | 0 ... 32.4 mm |
| Reduction factor rAl | 0.25 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.85 |
| Nominal ratings |
|---|
| Operating voltage | 20 ... 253 V |
| Switching frequency | 0 ... 20 Hz |
| Hysteresis | typ. 3 % |
| Short-circuit protection | no |
| Voltage drop | &le 5 V typ. 4V |
Momentary current (20 ms, 0.1 Hz) | max. 4000 mA |
| Operating current | 5 ... 500 mA |
| Off-state current | 0.3 ... 1 mA typ. 0.7 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | screw terminals |
| Core cross-section | up to 2.5 mm2 |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP68 |
| Note | 1) In the temperature range below 0 °C, permissible operating voltage Ub 80...253 V Safety fuse &le 2 A (quick-blow) according to IEC 60127-2 Sheet 1 Recommendation: after a short circuit, check that the device is functioning correctly. |
Каталожный номер: 130545
| General specifications |
|---|
| Switching function | Normally open/closed (NO/NC) |
| Output type | Two-wire |
| Rated operating distance | 40 mm |
| Installation | flush |
| Output polarity | AC |
| Assured operating distance | 0 ... 32.4 mm |
| Reduction factor rAl | 0.25 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.85 |
| Nominal ratings |
|---|
| Operating voltage AC | 20 ... 253 V |
| Switching frequency | 0 ... 20 Hz |
| Hysteresis | typ. 3 % |
| Voltage drop | &le 5 V typ. 4V |
Momentary current (20 ms, 0.1 Hz) | max. 4000 mA |
| Operating current | 5 ... 500 mA |
| Off-state current | 0.3 ... 1 mA typ. 0.7 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | screw terminals |
| Core cross-section | max. 2.5 mm2 |
| Housing material | PBT/base of metal |
| Sensing face | PBT |
| Degree of protection | IP68 |
| Note | 1) In the temperature range below 0 °C, permissible operating voltage Ub 80...253 V Safety fuse &le 2 A (quick-blow) according to IEC 60127-2 Sheet 1 Recommendation: after a short circuit, check that the device is functioning correctly. |
Каталожный номер: 180625
| General specifications |
|---|
| Switching function | Normally open/closed (NO/NC) |
| Output type | Two-wire |
| Rated operating distance | 40 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 32.4 mm |
| Actual operating distance | 36 ... 44 mm typ. 40 mm |
| Reduction factor rAl | 0.35 |
| Reduction factor rCu | 0.35 |
| Reduction factor r304 | 0.8 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V |
| Switching frequency | 0 ... 50 Hz |
| Hysteresis | 0 ... 20 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 6 V |
| Operating current | 2 ... 200 mA |
| Off-state current | 0.4 ... 1 mA typ. 0.6 mA |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | screw terminals |
| Information for connection | A maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 % |
| Core cross-section | up to 2.5 mm2 |
| Minimum core cross-section | without wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2 |
| Maximum core cross-section | without wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2 |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP67 |
Каталожный номер: 181113
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 5 mm |
| Installation | flush |
| Assured operating distance | 0 ... 4.05 mm |
| Actual operating distance | 4.5 ... 5.5 mm typ. 5 mm |
| Reduction factor rAl | 0.2 |
| Reduction factor rCu | 0.2 |
| Reduction factor r304 | 0.6 |
| Nominal ratings |
|---|
| Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) |
| Switching frequency | 0 ... 400 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | yes |
| Current consumption | |
| Measuring plate not detected | min. 3 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | all direction LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 2040 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Electromagnetic compatibility | NE 21:2007 |
| Approvals and certificates |
|---|
| FM approval | |
| Control drawing | 116-0165 |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PVC , 2 m |
| Core cross-section | 0.75 mm2 |
| Housing material | PBT |
| Sensing face | PBT |
| Housing diameter | 18 mm |
| Degree of protection | IP67 |
| Cable | |
| Bending radius | > 10 x cable diameter |
| General information |
|---|
| Use in the hazardous area | see instruction manuals |
| Category | 2G 1D |
Каталожный номер: 89258
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 5 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 4.05 mm |
| Actual operating distance | 4.5 ... 5.5 mm typ. 5 mm |
| Reduction factor rAl | 0.37 |
| Reduction factor rCu | 0.33 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 350 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | all direction LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 2 m |
| Core cross-section | 0.34 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 18 mm |
| Degree of protection | IP67 |
Каталожный номер: 131293
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 5 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 4.05 mm |
| Actual operating distance | 4.5 ... 5.5 mm typ. 5 mm |
| Reduction factor rAl | 0.37 |
| Reduction factor rCu | 0.33 |
| Reduction factor r304 | 0.7 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 350 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | all direction LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 10 m |
| Cable version | PA |
| Core cross-section | 0.34 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 18 mm |
| Degree of protection | IP67 |
Каталожный номер: 89262
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 5 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 4.05 mm |
| Actual operating distance | 4.5 ... 5.5 mm typ. 5 mm |
| Reduction factor rAl | 0.37 |
| Reduction factor rCu | 0.33 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 350 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | all direction LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 1730 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 2 m |
| Core cross-section | 0.34 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 18 mm |
| Degree of protection | IP67 |
Каталожный номер: 89263
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 5 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 4.05 mm |
| Actual operating distance | 4.5 ... 5.5 mm typ. 5 mm |
| Reduction factor rAl | 0.37 |
| Reduction factor rCu | 0.33 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 350 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | Multihole-LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 1730 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 18 mm |
| Degree of protection | IP67 |
Каталожный номер: 89259
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 5 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 4.05 mm |
| Actual operating distance | 4.5 ... 5.5 mm typ. 5 mm |
| Reduction factor rAl | 0.37 |
| Reduction factor rCu | 0.33 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 350 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | Multihole-LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 18 mm |
| Degree of protection | IP67 |
Каталожный номер: 226333
| General specifications |
|---|
| Switching function | Normally open/closed (NO/NC) programmable |
| Output type | AS-Interface |
| Rated operating distance | 5 mm |
| Installation | flush |
| Assured operating distance | 0 ... 4.05 mm |
| Actual operating distance | 4.5 ... 5.5 mm typ. 5 mm |
| Reduction factor rAl | 0.2 |
| Reduction factor rCu | 0.15 |
| Reduction factor r304 | 0.62 |
| Slave type | A/B slave |
| AS-Interface specification | V3.0 |
| Required master specification | &ge V2.1 |
| Nominal ratings |
|---|
| Operating voltage | 26.5 ... 31.9 V via AS-i bus system |
| Switching frequency | 0 ... 100 Hz |
| Hysteresis | 1 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Voltage drop at IL | |
| Voltage drop IL = 20 mA, switching element on | 3.4 ... 5 V typ. 4.3 V |
| No-load supply current | &le 25 mA |
| Operating voltage indicator | dual-LED, green |
| Switching state indicator | dual-LED, yellow |
| Error indicator | dual-LED, red |
| Functional safety related parameters |
|---|
| MTTFd | 926 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| Electromagnetic compatibility | EN 50295:1999-10
|
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F)
|
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 18 mm |
| Degree of protection | IP67 |
Каталожный номер: 127200
| General specifications |
|---|
| Switching function | complementary |
| Output type | PNP |
| Rated operating distance | 50 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 40.5 mm |
| Reduction factor rAl | 0.38 |
| Reduction factor rCu | 0.35 |
| Reduction factor r304 | 0.83 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V DC |
| Switching frequency | 0 ... 1 Hz |
| Hysteresis | typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA |
| No-load supply current | &le 20 mA |
| Tuning-out | &ge 50 ms |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 660 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | PBT/metal |
| Sensing face | PBT, active surface PTFE coated |
| Degree of protection | IP68 |
Каталожный номер: 910960
| General specifications |
|---|
| Switching function | complementary |
| Output type | PNP |
| Rated operating distance | 50 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 40.5 mm |
| Reduction factor rAl | 0.38 |
| Reduction factor rCu | 0.35 |
| Reduction factor r304 | 0.83 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V DC |
| Switching frequency | 0 ... 80 Hz |
| Hysteresis | typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA |
| No-load supply current | &le 20 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 680 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Standard conformity |
|---|
| Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | screw terminals |
| Core cross-section | up to 2.5 mm2 |
| Housing material | PBT/metal |
| Sensing face | PBT |
| Degree of protection | IP68 |
Каталожный номер: 908489
| General specifications |
|---|
| Switching function | complementary |
| Output type | PNP |
| Rated operating distance | 50 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 40.5 mm |
| Reduction factor rAl | 0.38 |
| Reduction factor rCu | 0.35 |
| Reduction factor r304 | 0.83 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V DC |
| Switching frequency | 0 ... 80 Hz |
| Hysteresis | typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA |
| No-load supply current | &le 20 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 680 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Standard conformity |
|---|
| Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | PBT/metal |
| Sensing face | PBT |
| Degree of protection | IP68 |
Каталожный номер: 915305
| General specifications |
|---|
| Switching function | Normally open/closed (NO/NC) |
| Output type | PNP |
| Rated operating distance | 50 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 40.5 mm |
| Reduction factor rAl | 0.38 |
| Reduction factor rCu | 0.35 |
| Reduction factor r304 | 0.83 |
| Output type | 4-wire |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V DC |
| Switching frequency | 0 ... 80 Hz |
| Hysteresis | typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA |
| No-load supply current | &le 20 mA |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 680 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Standard conformity |
|---|
| Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | 5 m, Black PUR cable with Cable gland ( resin filled Base ) |
| Core cross-section | 0.34 mm2 |
| Housing material | PBT/metal |
| Sensing face | PBT |
| Degree of protection | IP68 |
Каталожный номер: 132412
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | PNP |
| Rated operating distance | 50 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 40.5 mm |
| Reduction factor rAl | 0.38 |
| Reduction factor rCu | 0.35 |
| Reduction factor r304 | 0.83 |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 60 V DC |
| Switching frequency | 0 ... 1 Hz |
| Hysteresis | typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA |
| No-load supply current | &le 20 mA |
| Tuning-out | &ge 50 ms |
| Operating voltage indicator | LED, green |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 960 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | PBT/metal |
| Sensing face | PBT, active surface PTFE coated |
| Degree of protection | IP68 |
Pepperl+Fuchs — ориентир в промышленной автоматизации и взрывозащите
Pepperl+Fuchs — немецкий бренд с более чем 75-летней историей инженерного превосходства. Основанная в 1945 году в Мангейме, компания стала пионером бесконтактных датчиков и одним из мировых лидеров в области intrinsically safe решений для опасных сред. Сегодня Pepperl+Fuchs объединяет два направления — Factory Automation и Process Automation — предлагая датчики, интерфейсную электронику, системы взрывозащиты и HMI, которые повышают надежность, безопасность и эффективность производственных процессов.
Ключевые преимущества Pepperl+Fuchs
- Инженерное качество: стабильные измерения, высокая повторяемость и минимальные ошибки в жестких условиях эксплуатации.
- Безопасность и соответствие: решения с сертификатами ATEX, IECEx, UL и соответствием SIL/PL для критически важных применений.
- Готовность к IIoT: поддержка IO-Link, AS-Interface, промышленного Ethernet и современных протоколов для прозрачности данных и предиктивного обслуживания.
- Устойчивость к среде: широкий температурный диапазон, стойкость к вибрациям, влаге, пыли и химическим воздействиям (включая IP-защиту).
- Совместимость и интеграция: бесшовная работа с ведущими ПЛК и системами управления, унифицированные интерфейсы и аксессуары.
- Глобальная поддержка: доступность документации, сервисной сети и запасных частей для надежной долгосрочной эксплуатации.
Продуктовые направления
- Датчики и системы распознавания: индуктивные, емкостные, магнитные, ультразвуковые и фотоэлектрические датчики; датчики расстояния, уплотнения контуров и позиционирования; энкодеры, 2D-ридеры и сканеры кода, RFID (HF/UHF), а также интеллектуальные решения с IO-Link. Для задач объемного контроля — лидарные сенсоры и визион-системы.
- Интерфейсная техника и искробезопасность: гальванические изоляторы и барьеры (K-System, H-System, Zener), модули ввода/вывода, защита от перенапряжений, источники питания и диагностика шины FieldConnex для Foundation Fieldbus и PROFIBUS PA.
- Оборудование для взрывоопасных зон: корпуса и клеммные коробки Ex e/Ex d из нержавеющей стали, алюминия и GRP; станции управления; системы продувки и наддува Bebco EPS; HMI и операторские панели для зон 1/21 и 2/22; мобильные устройства ecom для безопасной работы на площадках.
- Связь и подключение: мастера и хабы IO-Link, компоненты AS-Interface, распределительные блоки, коннекторы и кабельная арматура для быстрого и чистого монтажа.
- Функциональная безопасность: датчики и модули с подтвержденными уровнями SIL/PL, включая решения AS-i Safety at Work для защиты персонала и оборудования.
Области применения
Решения Pepperl+Fuchs используются в автомобильной промышленности, машиностроении, пищевой и фармацевтической отраслях, логистике и складской автоматизации, а также в нефтегазовом, химическом и горнодобывающем секторах, на объектах энергетики, водоснабжения и очистки стоков. Бренд одинаково эффективен для модернизации отдельных участков и для комплексной автоматизации линий и установок.
Почему это выгодно
- Минимум простоев: надежная диагностика и предсказуемое обслуживание снижают незапланированные остановки.
- Точность и качество: стабильные показания повышают выпуск и уменьшают брак.
- Масштабируемость: широкий ассортимент позволяет развивать систему без смены платформы.
- Долгий жизненный цикл: продуманная номенклатура и преемственность серий упрощают поставки и ремонт.
- Полный комплект: от датчика и интерфейсных модулей до взрывозащищенных корпусов и операторских панелей.
Как выбрать решение Pepperl+Fuchs
Определите среду (включая наличие взрывоопасных зон), необходимые интерфейсы и уровень безопасности, диапазон измерений и точность, а также условия монтажа. Сверьте каталожные номера с требуемыми сертификатами и аксессуарами. При сложных задачах стоит привлечь инженера для подбора комплекта устройств с учетом специфики технологического процесса.
Pepperl+Fuchs — это инвестиция в надежность, безопасность и предсказуемые результаты. Выбирайте оригинальные решения бренда для уверенной работы оборудования сегодня и готовности к задачам завтрашнего дня.