Запасные части Pepperl+Fuchs
Каталожный номер: 232395
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 10 mm |
| Installation | flush |
| Assured operating distance | 0 ... 8.1 mm |
| Actual operating distance | 9 ... 11 mm typ. |
| Reduction factor rAl | 0.32 |
| Reduction factor rCu | 0.32 |
| Reduction factor r304 | 0.72 |
| Nominal ratings |
|---|
| Nominal voltage | 8 V |
| Switching frequency | 0 ... 650 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | yes |
| Suitable for 2:1 technology | yes , Reverse polarity protection diode not required |
| Current consumption | |
| Measuring plate not detected | min. 3 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 1870 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 80 °C (-13 ... 176 °F) |
| Storage temperature | -40 ... 80 °C (-40 ... 176 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR (halogen-free) , 15 m , screened , Oil resistant , Flame-retardant as per IEC 60332-1 |
| Core cross-section | 2x 0.5 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 30 mm |
| Degree of protection | IP66 / IP67 |
| Cable | |
| Bending radius | > 7.5 x cable diameter |
| Note | The shield is not connected to the sensor. |
| General information |
|---|
| Use in the hazardous area | see instruction manuals |
| Category | 1G 2G 3G 1D |
Каталожный номер: 208595
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 10 mm |
| Installation | flush |
| Assured operating distance | 0 ... 8.1 mm |
| Actual operating distance | 9 ... 11 mm typ. |
| Reduction factor rAl | 0.32 |
| Reduction factor rCu | 0.32 |
| Reduction factor r304 | 0.72 |
| Nominal ratings |
|---|
| Nominal voltage | 8 V |
| Switching frequency | 0 ... 650 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | yes |
| Current consumption | |
| Measuring plate not detected | min. 3 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | LED, yellow |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 15 m |
| Core cross-section | 0.75 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 30 mm |
| Degree of protection | IP66 / IP67 |
| Cable | |
| Bending radius | > 10 x cable diameter |
| General information |
|---|
| Use in the hazardous area | see instruction manuals |
| Category | 1G 2G 3G 1D |
Каталожный номер: 89266
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 10 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actual operating distance | 9 ... 11 mm typ. |
| Reduction factor rAl | 0.32 |
| Reduction factor rCu | 0.28 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 150 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | all direction LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 1830 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 2 m |
| Core cross-section | 0.34 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 30 mm |
| Degree of protection | IP67 |
Каталожный номер: 126073
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 10 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm ( -25 ... 70 °C (-13 ... 158 °F) ) 0 ... 7.6 mm ( -40 ... -25 °C (-40 ... -13 °F) ) |
| Actual operating distance | 9 ... 11 mm typ. 10 mm |
| Reduction factor rAl | 0.32 |
| Reduction factor rCu | 0.28 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 150 Hz |
| Hysteresis | 1 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Voltage drop at IL | |
| Voltage drop IL = 20 mA, switching element on | 3.4 ... 5 V typ. 4.3 V |
| Operating current | 2 ... 100 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | Multihole-LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 1830 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 30 mm |
| Degree of protection | IP67 |
Каталожный номер: 89270
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 10 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actual operating distance | 9 ... 11 mm typ. |
| Reduction factor rAl | 0.32 |
| Reduction factor rCu | 0.28 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 150 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | all direction LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 2 m |
| Core cross-section | 0.34 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 30 mm |
| Degree of protection | IP67 |
Каталожный номер: 89271
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 10 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actual operating distance | 9 ... 11 mm typ. |
| Reduction factor rAl | 0.32 |
| Reduction factor rCu | 0.28 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 150 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | Multihole-LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 30 mm |
| Degree of protection | IP67 |
Каталожный номер: 293464
| General specifications |
|---|
| Switching function | complementary |
| Output type | PNP |
| Rated operating distance | 10 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 8.1 mm |
| Actual operating distance | 9 ... 11 mm typ. 10 mm |
| Reduction factor rAl | 0.32 |
| Reduction factor rCu | 0.32 |
| Reduction factor r304 | 0.72 |
| Reduction factor rBrass | 0.43 |
| Output type | 3-wire |
| Nominal ratings |
|---|
| Operating voltage | 10 ... 30 V |
| Switching frequency | 300 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 2.8 V |
| Voltage drop at IL | |
| Voltage drop IL = 10 mA, switching element on | 0.9 ... 2.4 V typ. 1.7 V |
| Voltage drop IL = 20 mA, switching element on | 0.9 ... 2.4 V typ. 1.7 V |
| Voltage drop IL = 50 mA, switching element on | 0.9 ... 2.5 V typ. 1.7 V |
| Voltage drop IL = 100 mA, switching element on | 1 ... 2.6 V typ. 1.8 V |
| Voltage drop IL = 200 mA, switching element on | 1.2 ... 2.8 V typ. 2 V |
| Operating current | 0 ... 200 mA |
| Off-state current | 0 ... 0.5 mA typ. 0.01 mA |
| No-load supply current | &le 20 mA |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | flexible leads LiYV , 200 mm |
| Core cross-section | 0.5 mm2 |
| Housing material | Crastin (PBTB) |
| Sensing face | PBT |
| Degree of protection | IP67 |
Каталожный номер: 184673
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 15 mm |
| Installation | flush |
| Assured operating distance | 0 ... 12.15 mm |
| Actual operating distance | 13.5 ... 16.5 mm typ. |
| Reduction factor rAl | 0.28 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.75 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) |
| Switching frequency | 0 ... 400 Hz |
| Hysteresis | 1 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | yes |
| Current consumption | |
| Measuring plate not detected | min. 3 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 5128 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Electromagnetic compatibility | NE 21:2007 |
| Approvals and certificates |
|---|
| FM approval | |
| Control drawing | 116-0165 |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | screw terminals |
| Core cross-section | &le 2.5 mm2 |
| Housing material | PBT/metal |
| Sensing face | PBT |
| Degree of protection | IP68 |
| General information |
|---|
| Use in the hazardous area | see instruction manuals |
| Category | 1G 2G 1D |
Каталожный номер: 184674
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 15 mm |
| Installation | flush |
| Assured operating distance | 0 ... 12.15 mm |
| Actual operating distance | 13.5 ... 16.5 mm typ. |
| Reduction factor rAl | 0.28 |
| Reduction factor rCu | 0.25 |
| Reduction factor r304 | 0.75 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) |
| Switching frequency | 0 ... 400 Hz |
| Hysteresis | 1 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | yes |
| Current consumption | |
| Measuring plate not detected | min. 3 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 5128 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Electromagnetic compatibility | NE 21:2007 |
| Approvals and certificates |
|---|
| FM approval | |
| Control drawing | 116-0165 |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | PBT/metal |
| Sensing face | PBT |
| Degree of protection | IP68 |
| General information |
|---|
| Use in the hazardous area | see instruction manuals |
| Category | 1G 2G 1D |
Каталожный номер: 127392
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 15 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 12 mm |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.4 |
| Reduction factor r304 | 0.7 |
| Reduction factor rBrass | 0.5 |
| Nominal ratings |
|---|
| Operating voltage | 3.5 ... 30 V |
| Switching frequency | 500 Hz |
| Hysteresis | typ. 5% |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3.5 V |
| Temperature drift | ± 15% |
| Operating current | 2 ... 100 mA |
| Off-state current | typ. 0.8 mA |
| Switching state indicator | LED, yellow |
| Pre-fault indicator | LED, red |
| Stability control-switch point | 0,8 sr ... 0,9 sr |
| Functional safety related parameters |
|---|
| MTTFd | 1390 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PVC , 2 m |
| Core cross-section | 0.34 mm2 |
| Housing material | brass, nickel-plated |
| Sensing face | PBT |
| Housing diameter | 30 mm |
| Degree of protection | IP67 |
Каталожный номер: 131622
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 15 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 12 mm |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.4 |
| Reduction factor r304 | 0.7 |
| Reduction factor rBrass | 0.5 |
| Nominal ratings |
|---|
| Operating voltage | 3.5 ... 30 V |
| Switching frequency | 500 Hz |
| Hysteresis | typ. 5% |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3.5 V |
| Temperature drift | ± 15% |
| Operating current | 2 ... 100 mA |
| Off-state current | typ. 0.8 mA |
| Switching state indicator | LED, yellow |
| Pre-fault indicator | LED, red |
| Stability control-switch point | 0,8 sr ... 0,9 sr |
| Functional safety related parameters |
|---|
| MTTFd | 1390 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | brass, nickel-plated |
| Sensing face | PBT |
| Housing diameter | 30 mm |
| Degree of protection | IP67 |
Каталожный номер: 182912
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 15 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 12 mm |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.4 |
| Reduction factor r304 | 0.7 |
| Reduction factor rBrass | 0.5 |
| Nominal ratings |
|---|
| Operating voltage | 3.5 ... 30 V |
| Switching frequency | 500 Hz |
| Reverse polarity protection | reverse polarity-conductive |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3.5 V |
| Temperature drift | ± 15% |
| Operating current | 2 ... 100 mA |
| Off-state current | typ. 0.8 mA |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PVC , 2 m |
| Core cross-section | 0.34 mm2 |
| Housing material | brass, nickel-plated |
| Sensing face | PBT |
| Housing diameter | 30 mm |
| Degree of protection | IP67 |
Каталожный номер: 182913
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 15 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 12 mm |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.4 |
| Reduction factor r304 | 0.7 |
| Reduction factor rBrass | 0.5 |
| Nominal ratings |
|---|
| Operating voltage | 3.5 ... 30 V |
| Switching frequency | 500 Hz |
| Reverse polarity protection | reverse polarity-conductive |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3.5 V |
| Temperature drift | ± 15% |
| Operating current | 2 ... 100 mA |
| Off-state current | typ. 0.8 mA |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | brass, nickel-plated |
| Sensing face | PBT |
| Housing diameter | 30 mm |
| Degree of protection | IP67 |
Каталожный номер: 182914
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 15 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 12 mm |
| Reduction factor rAl | 0.4 |
| Reduction factor rCu | 0.4 |
| Reduction factor r304 | 0.7 |
| Reduction factor rBrass | 0.5 |
| Nominal ratings |
|---|
| Operating voltage | 3.5 ... 30 V |
| Switching frequency | 500 Hz |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3.5 V |
| Temperature drift | ± 15% |
| Operating current | 2 ... 100 mA |
| Off-state current | typ. 0.8 mA |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | brass, nickel-plated |
| Sensing face | PBT |
| Housing diameter | 30 mm |
| Degree of protection | IP67 |
Каталожный номер: 181096
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 2 mm |
| Installation | flush |
| Assured operating distance | 0 ... 1.62 mm |
| Actual operating distance | 1.8 ... 2.2 mm typ. |
| Reduction factor rAl | 0.23 |
| Reduction factor rCu | 0.21 |
| Reduction factor r304 | 0.7 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) |
| Switching frequency | 0 ... 1000 Hz |
| Hysteresis | 1 ... 10 typ. 3 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | yes |
| Suitable for 2:1 technology | yes , Reverse polarity protection diode not required |
| Current consumption | |
| Measuring plate not detected | min. 3 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | all direction LED, yellow |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Electromagnetic compatibility | NE 21:2007 |
| Approvals and certificates |
|---|
| FM approval | |
| Control drawing | 116-0165 |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PVC , 5 m |
| Core cross-section | 0.34 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Degree of protection | IP67 |
| Cable | |
| Bending radius | > 12 x cable diameter |
| General information |
|---|
| Scope of delivery | 2 self locking nuts in scope of delivery |
| Use in the hazardous area | see instruction manuals |
| Category | 1G 2G 3G 1D 3D |
Каталожный номер: 89250
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 2 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.62 mm |
| Actual operating distance | 1.8 ... 2.2 mm typ. |
| Reduction factor rAl | 0.28 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 800 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | all direction LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 2090 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 2 m |
| Core cross-section | 0.14 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP67 |
Каталожный номер: 126075
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 2 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.62 mm |
| Actual operating distance | 1.8 ... 2.2 mm typ. |
| Reduction factor rAl | 0.28 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 800 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | all direction LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 2090 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 10 m |
| Cable version | PA |
| Core cross-section | 0.14 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP67 |
Каталожный номер: 126069
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 2 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.62 mm |
| Actual operating distance | 1.8 ... 2.2 mm typ. |
| Reduction factor rAl | 0.28 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 800 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | Multihole-LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 2090 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP67 |
Каталожный номер: 89254
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 2 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.62 mm |
| Actual operating distance | 1.8 ... 2.2 mm typ. |
| Reduction factor rAl | 0.28 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 800 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | all direction LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PUR , 2 m |
| Core cross-section | 0.14 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP67 |
Каталожный номер: 89255
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 2 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 1.62 mm |
| Actual operating distance | 1.8 ... 2.2 mm typ. |
| Reduction factor rAl | 0.28 |
| Reduction factor rCu | 0.23 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Operating voltage | 5 ... 60 V |
| Switching frequency | 0 ... 800 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity tolerant |
| Short-circuit protection | pulsing |
| Voltage drop | &le 5 V |
| Operating current | 2 ... 100 mA |
| Lowest operating current | 2 mA |
| Off-state current | 0 ... 0.5 mA typ. |
| Switching state indicator | Multihole-LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | Certified by China Compulsory Certification (CCC) |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP67 |
Каталожный номер: 226332
| General specifications |
|---|
| Switching function | Normally open/closed (NO/NC) programmable |
| Output type | AS-Interface |
| Rated operating distance | 2 mm |
| Installation | flush |
| Assured operating distance | 0 ... 1.62 mm |
| Actual operating distance | 1.8 ... 2.2 mm typ. |
| Reduction factor rAl | 0.23 |
| Reduction factor rCu | 0.21 |
| Reduction factor r304 | 0.7 |
| Slave type | Standard slave |
| AS-Interface specification | V2.1 |
| Required master specification | &ge V2.1 |
| Nominal ratings |
|---|
| Operating voltage | 26.5 ... 31.9 V via AS-i bus system |
| Switching frequency | 0 ... 500 Hz |
| Hysteresis | 1 ... 10 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| No-load supply current | &le 25 mA |
| Switching state indicator | dual-LED, yellow |
| Error indicator | dual-LED, red |
| Functional safety related parameters |
|---|
| MTTFd | 2140 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP67 |
Каталожный номер: 243198
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 2 mm |
| Installation | flush |
| Assured operating distance | 0 ... 1.62 mm |
| Reduction factor rAl | 0.3 |
| Reduction factor rCu | 0.2 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) |
| Switching frequency | 0 ... 2000 Hz |
| Hysteresis | typ. 5 % |
| Current consumption | |
| Measuring plate not detected | &ge 3 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | LED, yellow |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Electromagnetic compatibility | NE 21:2007 |
| Approvals and certificates |
|---|
| FM approval | |
| Control drawing | 116-0165F |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PVC , 2 m |
| Core cross-section | 0.14 mm2 |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP67 |
| Cable | |
| Bending radius | > 10 x cable diameter |
| General information |
|---|
| Use in the hazardous area | see instruction manuals |
| Category | 1G 2G 1D |
Каталожный номер: 244943
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 2 mm |
| Installation | flush |
| Assured operating distance | 0 ... 1.62 mm |
| Reduction factor rAl | 0.3 |
| Reduction factor rCu | 0.2 |
| Reduction factor r304 | 0.7 |
| Output type | 2-wire |
| Nominal ratings |
|---|
| Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) |
| Switching frequency | 0 ... 2000 Hz |
| Hysteresis | typ. 5 % |
| Current consumption | |
| Measuring plate not detected | &ge 3 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 2180 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Electromagnetic compatibility | NE 21:2007 |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PVC , 130 mm Insulated wire end ferrule with 8 mm pin length |
| Core cross-section | 0.14 mm2 |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP67 |
| Cable | |
| Bending radius | > 10 x cable diameter |
| General information |
|---|
| Use in the hazardous area | see instruction manuals |
| Category | 1G 2G 1D |
Каталожный номер: 276438
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 2 mm |
| Installation | flush |
| Assured operating distance | 0 ... 1.62 mm |
| Reduction factor rAl | 0.3 |
| Reduction factor rCu | 0.2 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) |
| Switching frequency | 0 ... 2000 Hz |
| Hysteresis | typ. 1.5 % |
| Current consumption | |
| Measuring plate not detected | &ge 3 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | LED, green |
| Functional safety related parameters |
|---|
| MTTFd | 2260 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Electromagnetic compatibility | NE 21:2007 |
| Approvals and certificates |
|---|
| FM approval | |
| Control drawing | 116-0165 |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PVC , 130 mm |
| Core cross-section | 0.14 mm2 |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP67 |
| General information |
|---|
| Use in the hazardous area | see instruction manuals |
| Category | 1G 2G 1D |
Каталожный номер: 276468
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | NAMUR |
| Rated operating distance | 2 mm |
| Installation | flush |
| Assured operating distance | 0 ... 1.62 mm |
| Reduction factor rAl | 0.3 |
| Reduction factor rCu | 0.2 |
| Reduction factor r304 | 0.7 |
| Nominal ratings |
|---|
| Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) |
| Switching frequency | 0 ... 2000 Hz |
| Hysteresis | typ. 1.5 % |
| Current consumption | |
| Measuring plate not detected | &ge 3 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | LED, red |
| Functional safety related parameters |
|---|
| MTTFd | 2160 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Compliance with standards and directives |
|---|
| Standard conformity | |
| NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 |
| Electromagnetic compatibility | NE 21:2007 |
| Approvals and certificates |
|---|
| FM approval | |
| Control drawing | 116-0165 |
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PVC , 130 mm |
| Core cross-section | 0.14 mm2 |
| Housing material | PBT |
| Sensing face | PBT |
| Degree of protection | IP67 |
| General information |
|---|
| Use in the hazardous area | see instruction manuals |
| Category | 1G 2G 1D |
Каталожный номер: 121008
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 4 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 3.24 mm |
| Reduction factor rAl | 0.49 |
| Reduction factor rCu | 0.47 |
| Reduction factor r304 | 0.76 |
| Nominal ratings |
|---|
| Operating voltage | 3.5 ... 30 V |
| Switching frequency | 0 ... 1000 Hz |
| Reverse polarity protection | conducting |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3.5 V |
| Temperature drift | ± 15% |
| Operating current | 2 ... 100 mA |
| Off-state current | 0.4 ... 0.6 mA typ. 0.5 mA |
| Switching state indicator | LED, yellow |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PVC , 2 m |
| Core cross-section | 0.34 mm2 |
| Housing material | brass, nickel-plated |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP67 |
Каталожный номер: 299271
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 4 mm |
| Installation | flush |
| Assured operating distance | 0 ... 3.24 mm |
| Actual operating distance | 3.6 ... 4.4 mm typ. |
| Reduction factor rAl | 0.41 |
| Reduction factor rCu | 0.39 |
| Reduction factor r304 | 0.78 |
| Nominal ratings |
|---|
| Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) |
| Switching frequency | 0 ... 1500 Hz |
| Hysteresis | 1 ... 15 typ. 5 % |
| Reverse polarity protection | reverse polarity protected |
| Short-circuit protection | yes |
| Suitable for 2:1 technology | yes , Reverse polarity protection diode not required |
| Current consumption | |
| Measuring plate not detected | min. 2.2 mA |
| Measuring plate detected | &le 1 mA |
| Switching state indicator | all direction LED, yellow |
| Functional safety related parameters |
|---|
| MTTFd | 3010 a |
| Mission Time (TM) | 20 a |
| Diagnostic Coverage (DC) | 0 % |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) |
| Storage temperature | -40 ... 100 °C (-40 ... 212 °F) |
| Mechanical specifications |
|---|
| Connection type | cable PVC , L = 2.5 m Molex plug 39-01-2040 Molex contact 39-00-0046 |
| Core cross-section | 0.34 mm2 |
| Housing material | Stainless steel 1.4305 / AISI 303 |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP66 / IP67 |
| Cable | |
| Bending radius | > 10 x cable diameter |
| General information |
|---|
| Scope of delivery | Supplied with 2 nuts Supplied with 2 toothed lock washers |
Каталожный номер: 121009
| General specifications |
|---|
| Switching function | Normally open (NO) |
| Output type | Two-wire |
| Rated operating distance | 4 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 3.24 mm |
| Reduction factor rAl | 0.49 |
| Reduction factor rCu | 0.47 |
| Reduction factor r304 | 0.76 |
| Nominal ratings |
|---|
| Operating voltage | 3.5 ... 30 V |
| Switching frequency | 0 ... 1000 Hz |
| Hysteresis | typ. 5 % |
| Reverse polarity protection | conducting |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3.5 V |
| Temperature drift | ± 15% |
| Operating current | 2 ... 100 mA |
| Off-state current | 0.4 ... 0.6 mA typ. 0.5 mA |
| Switching state indicator | LED, yellow |
| Pre-fault indicator | LED, red |
| Stability control-switch point | 0,8 sr ... 0,9 sr |
| Approvals and certificates |
|---|
| UL approval | cULus Listed, General Purpose |
| CSA approval | cCSAus Listed, General Purpose |
| CCC approval | CCC approval / marking not required for products rated &le36 V |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Mechanical specifications |
|---|
| Connection type | Connector M12 x 1 , 4-pin |
| Housing material | brass, nickel-plated |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP67 |
Каталожный номер: 121010
| General specifications |
|---|
| Switching function | Normally closed (NC) |
| Output type | Two-wire |
| Rated operating distance | 4 mm |
| Installation | flush |
| Output polarity | DC |
| Assured operating distance | 0 ... 3.06 mm |
| Reduction factor rAl | 0.49 |
| Reduction factor rCu | 0.47 |
| Reduction factor r304 | 0.76 |
| Nominal ratings |
|---|
| Operating voltage | 3.5 ... 30 V |
| Switching frequency | 0 ... 1000 Hz |
| Reverse polarity protection | conducting |
| Short-circuit protection | pulsing |
| Voltage drop | &le 3.5 V |
| Temperature drift | ± 15% |
| Operating current | 2 ... 100 mA |
| Off-state current | 0.4 ... 0.6 mA typ. 0.5 mA |
| Switching state indicator | LED, yellow |
| Ambient conditions |
|---|
| Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) |
| Mechanical specifications |
|---|
| Housing material | brass, nickel-plated |
| Sensing face | PBT |
| Housing diameter | 12 mm |
| Degree of protection | IP67 |
Каталожный номер: 226322
| Описание оборудования |
|---|
| Valve positioner and valve control module |
Pepperl+Fuchs — ориентир в промышленной автоматизации и взрывозащите
Pepperl+Fuchs — немецкий бренд с более чем 75-летней историей инженерного превосходства. Основанная в 1945 году в Мангейме, компания стала пионером бесконтактных датчиков и одним из мировых лидеров в области intrinsically safe решений для опасных сред. Сегодня Pepperl+Fuchs объединяет два направления — Factory Automation и Process Automation — предлагая датчики, интерфейсную электронику, системы взрывозащиты и HMI, которые повышают надежность, безопасность и эффективность производственных процессов.
Ключевые преимущества Pepperl+Fuchs
- Инженерное качество: стабильные измерения, высокая повторяемость и минимальные ошибки в жестких условиях эксплуатации.
- Безопасность и соответствие: решения с сертификатами ATEX, IECEx, UL и соответствием SIL/PL для критически важных применений.
- Готовность к IIoT: поддержка IO-Link, AS-Interface, промышленного Ethernet и современных протоколов для прозрачности данных и предиктивного обслуживания.
- Устойчивость к среде: широкий температурный диапазон, стойкость к вибрациям, влаге, пыли и химическим воздействиям (включая IP-защиту).
- Совместимость и интеграция: бесшовная работа с ведущими ПЛК и системами управления, унифицированные интерфейсы и аксессуары.
- Глобальная поддержка: доступность документации, сервисной сети и запасных частей для надежной долгосрочной эксплуатации.
Продуктовые направления
- Датчики и системы распознавания: индуктивные, емкостные, магнитные, ультразвуковые и фотоэлектрические датчики; датчики расстояния, уплотнения контуров и позиционирования; энкодеры, 2D-ридеры и сканеры кода, RFID (HF/UHF), а также интеллектуальные решения с IO-Link. Для задач объемного контроля — лидарные сенсоры и визион-системы.
- Интерфейсная техника и искробезопасность: гальванические изоляторы и барьеры (K-System, H-System, Zener), модули ввода/вывода, защита от перенапряжений, источники питания и диагностика шины FieldConnex для Foundation Fieldbus и PROFIBUS PA.
- Оборудование для взрывоопасных зон: корпуса и клеммные коробки Ex e/Ex d из нержавеющей стали, алюминия и GRP; станции управления; системы продувки и наддува Bebco EPS; HMI и операторские панели для зон 1/21 и 2/22; мобильные устройства ecom для безопасной работы на площадках.
- Связь и подключение: мастера и хабы IO-Link, компоненты AS-Interface, распределительные блоки, коннекторы и кабельная арматура для быстрого и чистого монтажа.
- Функциональная безопасность: датчики и модули с подтвержденными уровнями SIL/PL, включая решения AS-i Safety at Work для защиты персонала и оборудования.
Области применения
Решения Pepperl+Fuchs используются в автомобильной промышленности, машиностроении, пищевой и фармацевтической отраслях, логистике и складской автоматизации, а также в нефтегазовом, химическом и горнодобывающем секторах, на объектах энергетики, водоснабжения и очистки стоков. Бренд одинаково эффективен для модернизации отдельных участков и для комплексной автоматизации линий и установок.
Почему это выгодно
- Минимум простоев: надежная диагностика и предсказуемое обслуживание снижают незапланированные остановки.
- Точность и качество: стабильные показания повышают выпуск и уменьшают брак.
- Масштабируемость: широкий ассортимент позволяет развивать систему без смены платформы.
- Долгий жизненный цикл: продуманная номенклатура и преемственность серий упрощают поставки и ремонт.
- Полный комплект: от датчика и интерфейсных модулей до взрывозащищенных корпусов и операторских панелей.
Как выбрать решение Pepperl+Fuchs
Определите среду (включая наличие взрывоопасных зон), необходимые интерфейсы и уровень безопасности, диапазон измерений и точность, а также условия монтажа. Сверьте каталожные номера с требуемыми сертификатами и аксессуарами. При сложных задачах стоит привлечь инженера для подбора комплекта устройств с учетом специфики технологического процесса.
Pepperl+Fuchs — это инвестиция в надежность, безопасность и предсказуемые результаты. Выбирайте оригинальные решения бренда для уверенной работы оборудования сегодня и готовности к задачам завтрашнего дня.