Supply | ||
---|---|---|
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power consumption | 0.65 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Output | ||
Number of channels | 2 | |
Connection | wire ends 1 (white), 2 (brown), 3 (green), 4 (yellow), 5 (grey), 6 (pink) | |
Minimum load | 1 V , 1 mA | |
Relay | ||
Switching voltage | 24 V DC / 230 V AC | |
Switching current | 1 A DC / AC resistive load | |
Switching power | 30 W , 230 VA resistive load | |
Electrical life | 0.5 Mio. cycles | |
Response time | 20 ms (depending on bus cycle time) | |
Contact Material | AgPd gold plated | |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
Indicators/settings | ||
LED indicator | LED green: supply LED yellow: signal (status) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1 | |
Low voltage | ||
Directive 2006/95/EC | EN 61010-1 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100 | |
Vibration resistance | frequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | wire ends or shielded cable tail wiring connection: separately covered Ex e terminals required | |
Mass | approx. 350 g | |
Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | PTB 97 ATEX 1074 U | |
Group, category, type of protection | II 2 G Ex d IIC Gb | |
Galvanic isolation | ||
Output/power supply, internal bus | safe electrical isolation acc. to EN 61010-1 | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
International approvals | ||
ATEX approval | BVS 11 ATEX E 093X | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
DNV GL Marine | TAA0000034 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |
Supply | ||
---|---|---|
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power consumption | 1.2 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Output | ||
Number of channels | 4 | |
Connection | wire ends 1/9 (white), 2/10 (brown), 3/11 (green), 4/12 (yellow), 5/13 (grey), 6/14 (pink), 7/15 (blue), 8/16 (red) | |
Minimum load | 1 V , 1 mA | |
Relay | ||
Switching voltage | DC: 30 V , AC: 230 V | |
Switching current | 1 A DC / AC resistive load | |
Switching power | 30 W , AC: 250 VA | |
Electrical life | 0.1 mio. cycles | |
Response time | 20 ms (depending on bus cycle time) | |
Contact Material | AgPd gold plated | |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
Indicators/settings | ||
LED indicator | LED green: supply LED red: communication fault | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1 | |
Low voltage | ||
Directive 2006/95/EC | EN 61010-1 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 50 m/s2, number of shock directions 6, number of shocks per direction 100 | |
Vibration resistance | frequency range 5 ... 500 Hz, amplitude 5 ... 13.2 Hz ± 1.5 mm, 13.2 ... 100 Hz 1g, sweep rate 1 octave/min, duration 10 sweeps 5 Hz - 100 Hz - 5 Hz | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | wire ends or shielded cable tail wiring connection: separately covered Ex e terminals required | |
Mass | approx. 750 g | |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | PTB 97 ATEX 1074 U | |
Group, category, type of protection | II 2 G Ex d IIC Gb | |
Galvanic isolation | ||
Output/power supply, internal bus | safe electrical isolation acc. to EN 61010-1 | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
International approvals | ||
ATEX approval | BVS 11 ATEX E 093X | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
DNV GL Marine | TAA0000034 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |
Slots | ||
---|---|---|
Occupied slots | 2 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power consumption | 1.6 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Digital output | ||
Number of channels | 2 | |
Field device interface | ||
Connection | Relay output | |
Connection | channel I: 1-2 NO channel II: 3-4 NO channel III: 5-6 NO channel IV: 7-8 NO channel V: 9-10 NO channel VI: 11-12 NO channel VII: 13-14 NO channel VIII: 15-16 NO | |
Relay | ||
Switching voltage | 24 V DC / AC | |
Switching current | 1 A DC / AC resistive load | |
Switch power | 30 VA / 30 W | |
Minimum load | 1 V 1 mA | |
Electrical life | 0.1 mio. cycles | |
Contact Material | AgPd gold plated | |
Response time | 20 ms (depending on bus cycle time) | |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
Indicators/settings | ||
LED indicator | LED green: supply LED red: communication fault | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | Ex e spring terminal with protective cover | |
Mass | approx. 750 g | |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 11 ATEX E 093 X | |
Marking | II 2 G Ex db eb IIC T4 | |
Galvanic isolation | ||
Output/power supply, internal bus | safe electrical isolation acc. to EN 61010-1:2010 | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007 | |
International approvals | ||
ATEX approval | BVS 11 ATEX E 093X | |
INMETRO | Brazil: TÜV 14.1599X | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |