Товаров: 0
На сумму: 0
| General specifications | ||
|---|---|---|
| Signal type | Digital Input | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 9+, 10- | |
| Rated voltage | 19 ... 30 V DC | |
| Ripple | &le 10 % | |
| Rated current | 18 ... 14 mA | |
| Power dissipation | &le 500 mW | |
| Input | ||
| Connection side | field side | |
| Connection | terminals 1+, 2- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
| Line fault detection | breakage I &le 0.1 mA , short-circuit I &ge 6.5 mA | |
| Pulse/Pause ratio | min. 100 µs / min. 100 µs | |
| Output | ||
| Connection side | control side | |
| Connection | output I: terminals 5, 6 output II: terminals 7, 8 | |
| Rated voltage | typ. 8 V max. 20 V DC | |
| Response time | &le 200 µs | |
| Output I, II | signal or error message, passive transistor output (resistive) 0-signal: 14 k&Omega ± 10 % 1-signal: 1.8 k&Omega ± 10 % fault: > 100 k&Omega | |
| Collective error message | Power Rail | |
| Transfer characteristics | ||
| Switching frequency | &le 5 kHz | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2011 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | spring terminals | |
| Mass | approx. 100 g | |
| Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BASEEFA 13 ATEX 0080 | |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
| Certificate | PF 13 CERT 2760 X | |
| Marking | II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | ||
| Control drawing | 116-0374 (cULus) | |
| IECEx approval | IECEx BAS 13.0046 | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| Производитель | Pepperl+Fuchs |
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках Дискретный вход Switch Amplifier KCD2-SON-Ex1.SP Pepperl+Fuchs.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цена Дискретный вход Switch Amplifier KCD2-SON-Ex1.SP Pepperl+Fuchs на сайте имеет информационный характер и может отличаться от цены в коммерческом предложении.