Slots | ||
---|---|---|
Occupied slots | 1 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 0.4 W | |
Power consumption | 1 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Analog input | ||
Number of channels | 1 | |
Suitable field devices | ||
Field device | pressure converter | |
Field device [2] | flow converter | |
Field device [3] | level converter | |
Field device [4] | Temperature Converter | |
Field device interface | ||
Connection | 2-wire transmitter | |
Connection | 2-wire transmitter (HART): supply circuit: 2/3+, 4/5- | |
Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
Input resistance | 15 &Omega (terminals 5, 6) 236 &Omega (terminals 1, 6) HART | |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
Short-circuit | factory setting: > 22 mA configurable between 0 ... 26 mA | |
Open-circuit | factory setting: < 1 mA configurable between 0 ... 26 mA | |
HART communication | yes | |
HART secondary variable | yes | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
Resolution | 12 Bit (0 ... 26 mA) | |
Refresh time | 100 ms | |
Indicators/settings | ||
LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) Status LED (2) yellow: Live Zero monitoring | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
Mass | approx. 350 g | |
Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 12 ATEX E 015 X | |
Marking | II 2(1) G Ex d [ia Ga] IIC T4 Gb II (1) D [Ex ia Da] IIIC | |
Supply | ||
Voltage | 27 V | |
Current | 87 mA | |
Power | 575 mW (linear characteristic) | |
Galvanic isolation | ||
Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 | |
International approvals | ||
ATEX approval | BVS 12 ATEX E 015 X | |
INMETRO | Brazil: TÜV 14.1595X | |
Marine approval | ||
Bureau Veritas Marine | 22449/B0 BV |
Производитель | Pepperl+Fuchs |
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Основная валюта на сайте указана в долларах. Счета выставляются в рублях по курсу ЦБ РФ +3% на дату выставления счета.
Минимальный счет на запчасти (без учета доставки):
Наличие и срок поставки запчастей уточняйте у Вашего менеджера. Если Ваш заказ получается меньше суммы минимального счета, то цена на запчасти может быть увеличена. Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Условия платежа - 100% предоплата, если иное не оговорено в договоре.
Оплата по счету
Мы выставляем счёт на вашу организацию и отправляем его по электронной почте. Если вы в первый раз покупаете через нашу компанию, то присылайте реквизиты на почту info@zipstore.ru. Как только мы увидим деньги на нашем расчетном счете и подготовим груз к отправке - мы с Вами свяжемся по электронной почте, на которую выставлен счет.
Перед получением товара, убедитесь в его готовности к отгрузке у Вашего менеджера.
1) Самовывоз из Москвы
Необходимо заранее согласовать время получение товара с менеджером и иметь при себе доверенность от организации установленного образца или круглую печать.
Склад находится по адресу: 127282, г. Москва, ул. Полярная, д. 33, стр. 3, 2-ой этаж, помещение 3
Чтобы не заблудиться, можете распечатать схему проезда.
2) Доставка транспортной компанией
Товары отгружаются покупателю в течение недели после поступления денежных средств на расчетный счет Продавца, если иное не оговорено в счете. Мы бесплатно доставляем Ваш заказ до транспортной компании "Деловые Линии" в г. Москве при заказе от 50 000 рублей за запчасти. Услуги межтерминальной перевозки Вы оплачиваете самостоятельно при получении груза. Найти ближайший к Вам терминал "Деловых линий" для выдачи посылок можно здесь.
3) Самовывоз из 118 пунктов выдачи в других городах России
Оплата за доставку при получении. Найдите ближайший терминал выдачи посылок на карте.
4) Доставка по Москве
Минимальная стоимость доставки курьером по г. Москве составляет 600 рублей.
В нашей компании Вы можете выбрать удобный для Вас способ доставки груза:
1) Организация доставки силами Zipstore.ru
Мы самостоятельно вызываем для Вас ТК "Деловые Линии". Груз передается водителю или курьеру ТК, при наличии у него транспортной накладной на товар. Для заказа транспортной компании нашими силами, Вам необходимо написать письмо на электронную почту Вашего менеджера, в котором указать:
2) Организация доставки Вашими силами
Через любую Транспортную компанию (далее ТК), которую Вы вызываете к нам своими силами. Груз передается водителю или курьеру ТК, при наличии у него транспортной накладной на товар.
3) Отправка через ЕМS почту силами Zipstore.ru
Если Вы выбрали этот вариант, то стоимость услуги за перевозку включается в счет за товар, так как оплата курьеру ЕМS почты осуществляется наличными и только при отправке груза. Таким образом, в дальнейшем Вам не придется оплачивать отдельные счета ТК.
Для заказа EMS нашими силами, Вам необходимо написать письмо на электронную почту Вашего менеджера, в котором указать:
1. Качество Оборудования должно соответствовать техническим характеристикам, изложенным в инструкции по эксплуатации Оборудования.
2. Продавец гарантирует отсутствие производственных дефектов в поставленном Оборудовании в течение гарантийного периода.
3. Гарантийный период на Оборудование составляет 12 месяцев, на оригинальные запасные части 3 месяца, на аналоги 1 месяц, если иное не предусмотрено Спецификацией.
4. Претензии к внешнему виду товара принимаются в течение 2-х недель, с момента отгрузки товара.
5. Гарантия не распространяется на запчасти для технологического и ресторанного оборудования, интерфейсы (последовательного и Ethernet), материнские платы Godex, расходные материалы.
6. Если в течение гарантийного периода (п.3) Оборудование или его часть, указанные в Счете, окажутся дефектными, Продавец обязуется произвести ремонт или замену Оборудования или его части без оплаты Покупателем при соблюдении следующих условий:
6.1. Диагностика неисправности была проведена авторизованными специалистами производителя оборудования.
6.2. Покупатель письменно извещает Продавца об обнаруженных дефектах с их подробным описанием. Рекламация подписывается авторизованным специалистом.
6.3. Если дефекты не вызваны существенными нарушениями технических требований, оговоренных в инструкции по эксплуатации (в том числе нестабильностью параметров питающей электрической сети и отсутствием или ненадлежащим выполнением заземления Оборудования).
6.4. Если дефекты не вызваны вскрытием, ремонтом, модификацией или неправильным запуском Оборудования.
6.5. Если дефекты не вызваны повреждением вследствие действия на нее других неисправных частей.
6.6. Если отсутствуют видимые механические повреждения, в т.ч. сколы и царапины на нагревательной поверхности печатающих термоголовок (см. документ "Гарантийные обязательства на печатающие термоголовки").
6.7. Если дефекты не вызваны пожаром или затоплением помещения и не являются следствием неправильной эксплуатации Оборудования.
6.8. Если Специалистами Покупателя регулярно проводилось обслуживание Оборудования согласно инструкции по эксплуатации.
6.9. Если регулировка и настройка Оборудования проводилась Покупателем согласно инструкции по эксплуатации.
6.10. Если дефект не является следствием нормального износа быстроизнашивающихся деталей.
6.11. Если применялись расходные материалы, одобренные производителем.
6.12. Если оплата за товар произведена полностью.
7. При несоблюдении Покупателем условий, указанных в пп. 6.1.-6.12. , гарантия истекает немедленно.
8. Доставка гарантийного Оборудования производится силами и за счет Покупателя.
9. При невозможности замены бракованных Запчастей, неисправного Оборудования или неисправных частей Оборудования, возврат денежных средств производится в течении 14 рабочих дней, с момента заключения специалистами Продавца и оформления письма о возврате денежных средств Покупателем.
10. В случаях обнаружения брака (товара ненадлежащего качества) сразу необходимо упаковать товар, не пользоваться им, в течение ближайшего времени связаться с нами. Отправка товара ненадлежащего качества должна быть произведена в течении 5 дней с момента подтверждения брака Продавцом.
11. Возврат или обмен товара надлежащего качества остается на усмотрение Продавца, если иное не предусмотрено договором поставки (Закон о Защите Прав Потребителей не распространяется на взаимоотношения юридических лиц).
12. Должны быть сохранены упаковка товара (в чистом виде), товарный вид, потребительские свойства, пломбы, фабричные ярлыки, а также все полученные от продавца документы (чеки, бухгалтерские документы, инструкция по эксплуатации).
13. Денежные средства возвращаются тем же способом, которым был оплачен заказ.
14. Запчасти и расходные материалы для торгового, складского ресторанного и технологического оборудования не подлежат сертификации, по этой причине отказные письма не выдаются.
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
В случае возникновения вопросов, касающихся свойств и характеристик товара, перед оформлением счета обратитесь к нашим сотрудникам. Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Slots | ||
---|---|---|
Occupied slots | 2 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 1.5 W | |
Power consumption | 3 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Analog input | ||
Number of channels | 4 | |
Suitable field devices | ||
Field device | pressure converter | |
Field device [2] | flow converter | |
Field device [3] | level converter | |
Field device [4] | Temperature Converter | |
Field device interface | ||
Connection | 2-wire transmitter | |
Connection [2] | 3-wire transmitter | |
Connection [3] | 4-wire transmitter | |
Connection | 2-wire transmitter (HART):Supply circuit: channel I 1+, 2-, channel II 5+, 6-, channel III 9+, 10-, channel IV 13+, 14-3-wire transmitter:Supply circuit: channel I 1+, 4-, channel II 5+, 8-, channel III 9+, 12-, channel IV 13+, 16-Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-4-wire transmitter (powered externally):Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16- | |
Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
Input resistance | 15 &Omega | |
Conversion time | max. 100 ms | |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
Short-circuit | factory setting: > 22 mA configurable between 0 ... 26 mA | |
Open-circuit | factory setting: < 1 mA configurable between 0 ... 26 mA | |
HART communication | yes | |
HART secondary variable | yes | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
Resolution | 12 Bit (0 ... 26 mA) | |
Refresh time | 100 ms | |
Indicators/settings | ||
LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | Ex e spring terminal with protective cover | |
Mass | approx. 750 g | |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 11 ATEX E 093 X | |
Marking | II 2 G Ex db eb IIC T4 | |
Galvanic isolation | ||
Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007 | |
International approvals | ||
ATEX approval | BVS 11 ATEX E 093X | |
INMETRO | Brazil: TÜV 14.1599X | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |
Slots | ||
---|---|---|
Occupied slots | 1 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 0.4 W | |
Power consumption | 1 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Analog input | ||
Number of channels | 1 | |
Suitable field devices | ||
Field device | pressure converter | |
Field device [2] | flow converter | |
Field device [3] | level converter | |
Field device [4] | Temperature Converter | |
Field device interface | ||
Connection | 2-wire transmitter | |
Connection [2] | 3-wire transmitter | |
Connection [3] | 4-wire transmitter | |
Connection | 2-wire transmitter (HART): supply circuit: 2/3+, 4/5- 3-wire transmitter (HART): supply circuit: 2/3+, 6- measuring circuit: 4/5+, 6- 4-wire transmitter (separately powered): measuring circuit: 4/5+, 6- HART measuring circuit: 1+, 6- | |
Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
Input resistance | 15 &Omega (terminals 5, 6) 236 &Omega (terminals 1, 6) HART | |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
Short-circuit | factory setting: > 22 mA configurable between 0 ... 26 mA | |
Open-circuit | factory setting: < 1 mA configurable between 0 ... 26 mA | |
HART communication | yes | |
HART secondary variable | yes | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
Resolution | 12 Bit (0 ... 26 mA) | |
Refresh time | 100 ms | |
Indicators/settings | ||
LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) Status LED (2) yellow: Live Zero monitoring | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | Ex e spring terminal with protective cover | |
Mass | approx. 350 g | |
Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 11 ATEX E 093 X | |
Marking | II 2 G Ex db eb IIC T4 | |
Galvanic isolation | ||
Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007 | |
International approvals | ||
ATEX approval | BVS 11 ATEX E 093X | |
INMETRO | Brazil: TÜV 14.1599X | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |
Slots | ||
---|---|---|
Occupied slots | 1 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 0.5 W | |
Power consumption | 1 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Analog output | ||
Number of channels | 1 | |
Suitable field devices | ||
Field device | Proportional Valve | |
Field device [2] | I/P converters | |
Field device [3] | on-site display | |
Connection | channel I: 2/3+, 4/5- | |
Current | 0 ... 25 mA short-circuit protected | |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
Short-circuit | factory setting: < 50 &Omega configurable between 0 ... 26 mA | |
Open-circuit | deviation of preset output value > 0.5 mA | |
Load | 750 &Omega max. | |
HART communication | yes | |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
Refresh time | 100 ms | |
Indicators/settings | ||
LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
Mass | approx. 350 g | |
Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 12 ATEX E 015 X | |
Marking | II 2(1) G Ex d [ia Ga] IIC T4 Gb II (1) D [Ex ia Da] IIIC | |
Galvanic isolation | ||
Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 | |
International approvals | ||
ATEX approval | BVS 12 ATEX E 015 X | |
INMETRO | Brazil: TÜV 14.1595X | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |
Slots | ||
---|---|---|
Occupied slots | 1 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 0.4 W | |
Power consumption | 1 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Analog input | ||
Number of channels | 1 | |
Suitable field devices | ||
Field device | pressure converter | |
Field device [2] | flow converter | |
Field device [3] | level converter | |
Field device [4] | Temperature Converter | |
Field device interface | ||
Connection | 2-wire transmitter | |
Connection [2] | 3-wire transmitter | |
Connection [3] | 4-wire transmitter | |
Connection | 2-wire transmitter (HART): supply circuit: 2/3+, 4/5- 3-wire transmitter (HART): supply circuit: 2/3+, 6- measuring circuit: 4/5+, 6- 4-wire transmitter (separately powered): measuring circuit: 4/5+, 6- HART measuring circuit: 1+, 6- | |
Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
Input resistance | 15 &Omega (terminals 5, 6) 236 &Omega (terminals 1, 6) HART | |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
Short-circuit | factory setting: > 22 mA configurable between 0 ... 26 mA | |
Open-circuit | factory setting: < 1 mA configurable between 0 ... 26 mA | |
HART communication | yes | |
HART secondary variable | yes | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
Resolution | 12 Bit (0 ... 26 mA) | |
Refresh time | 100 ms | |
Indicators/settings | ||
LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) Status LED (2) yellow: Live Zero monitoring | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
Mass | approx. 350 g | |
Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 13 ATEX E 050 X | |
Marking | II 2(1) G Ex d [ia Ga] IIC T4 Gb II (1) D [Ex ia Da] IIIC | |
Supply | ||
Voltage | 27 V | |
Current | 92 mA | |
Power | 619 mW (linear characteristic) | |
Connection 1-6 | ||
Voltage | 8.9 V | |
Current | 4 mA | |
Power | 24 mW (trapezoid characteristic curve) | |
Input | ||
Voltage | 0.7 V | |
Current | 7 mA | |
Power | 5 mW (trapezoid characteristic curve) | |
Internal capacitance | 242 nF | |
Internal inductance | 0 mH | |
Galvanic isolation | ||
Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2012 EN 60079-26:2007 | |
International approvals | ||
ATEX approval | BVS 13 ATEX E 050 X | |
INMETRO | Brazil: TÜV 14.1596X | |
Marine approval | ||
Bureau Veritas Marine | 22449/B0 BV |
Slots | ||
---|---|---|
Occupied slots | 2 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 1.5 W | |
Power consumption | 3 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Analog output | ||
Number of channels | 4 | |
Suitable field devices | ||
Field device | Proportional Valve | |
Field device [2] | I/P converters | |
Field device [3] | on-site display | |
Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
Current | 0 ... 25 mA short-circuit protected | |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
Short-circuit | factory setting: < 50 &Omega configurable between 0 ... 26 mA | |
Open-circuit | deviation of preset output value > 0.5 mA | |
Load | 750 &Omega max. | |
HART communication | yes | |
HART secondary variable | yes | |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
Refresh time | 100 ms | |
Indicators/settings | ||
LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
Mass | approx. 750 g | |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 12 ATEX E 015 X | |
Marking | II 2(1) G Ex d [ia Ga] IIC T4 Gb II (1) D [Ex ia Da] IIIC | |
Galvanic isolation | ||
Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 | |
International approvals | ||
ATEX approval | BVS 12 ATEX E 015 X | |
INMETRO | Brazil: TÜV 14.1595X | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |
Slots | ||
---|---|---|
Occupied slots | 2 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 1.5 W | |
Power consumption | 3 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Analog output | ||
Number of channels | 4 | |
Suitable field devices | ||
Field device | Proportional Valve | |
Field device [2] | I/P converters | |
Field device [3] | on-site display | |
Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
Current | 0 ... 25 mA short-circuit protected | |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
Short-circuit | factory setting: < 50 &Omega configurable between 0 ... 26 mA | |
Open-circuit | deviation of preset output value > 0.5 mA | |
Load | 750 &Omega max. | |
HART communication | yes | |
HART secondary variable | yes | |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
Refresh time | 100 ms | |
Indicators/settings | ||
LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
Mass | approx. 750 g | |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 12 ATEX E 015 X | |
Marking | II 2(1) G Ex d [ia Ga] IIC T4 Gb II (1) D [Ex ia Da] IIIC | |
Galvanic isolation | ||
Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 | |
International approvals | ||
ATEX approval | BVS 12 ATEX E 015 X | |
INMETRO | Brazil: TÜV 14.1595X | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |
Slots | ||
---|---|---|
Occupied slots | 1 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 0.4 W | |
Power consumption | 1 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Analog input | ||
Number of channels | 1 | |
Suitable field devices | ||
Field device | pressure converter | |
Field device [2] | flow converter | |
Field device [3] | level converter | |
Field device [4] | Temperature Converter | |
Field device interface | ||
Connection | 2-wire transmitter | |
Connection [2] | 3-wire transmitter | |
Connection [3] | 4-wire transmitter | |
Connection | 2-wire transmitter: supply circuit: 2/3+, 4/5- 3-wire transmitter: supply circuit: 2/3+, 6- measuring circuit: 4/5+, 6- 4-wire transmitter (separately powered): measuring circuit: 4/5+, 6- | |
Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
Input resistance | 15 &Omega (terminals 5, 6) | |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
Short-circuit | factory setting: > 22 mA configurable between 0 ... 26 mA | |
Open-circuit | factory setting: < 1 mA configurable between 0 ... 26 mA | |
HART communication | no | |
HART secondary variable | no | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
Resolution | 12 Bit (0 ... 26 mA) | |
Refresh time | 100 ms | |
Indicators/settings | ||
LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) Status LED (2) yellow: Live Zero monitoring | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
Mass | approx. 350 g | |
Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 13 ATEX E 050 X | |
Marking | II 2(1) G Ex d [ia Ga] IIC T4 Gb II (1) D [Ex ia Da] IIIC | |
Supply | ||
Voltage | 23.8 V | |
Current | 90 mA | |
Power | 533 mW (linear characteristic) | |
Input | ||
Voltage | 0.7 V | |
Current | 7 mA | |
Power | 5 mW (trapezoid characteristic curve) | |
Internal capacitance | 242 nF | |
Internal inductance | 0 mH | |
Galvanic isolation | ||
Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2012 EN 60079-26:2007 | |
International approvals | ||
INMETRO | Brazil: TÜV 14.1596X | |
Marine approval | ||
Bureau Veritas Marine | 22449/B0 BV |
Slots | ||
---|---|---|
Occupied slots | 1 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 0.4 W | |
Power consumption | 1 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Analog input | ||
Number of channels | 1 | |
Suitable field devices | ||
Field device | pressure converter | |
Field device [2] | flow converter | |
Field device [3] | level converter | |
Field device [4] | Temperature Converter | |
Field device interface | ||
Connection | 2-wire transmitter | |
Connection [2] | 3-wire transmitter | |
Connection [3] | 4-wire transmitter | |
Connection | 2-wire transmitter (HART): supply circuit: 2/3+, 4/5- 3-wire transmitter (HART): supply circuit: 2/3+, 6- measuring circuit: 4/5+, 6- 4-wire transmitter (separately powered): measuring circuit: 4/5+, 6- HART measuring circuit: 1+, 6- | |
Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
Input resistance | 15 &Omega (terminals 5, 6) 236 &Omega (terminals 1, 6) HART | |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
Short-circuit | factory setting: > 22 mA configurable between 0 ... 26 mA | |
Open-circuit | factory setting: < 1 mA configurable between 0 ... 26 mA | |
HART communication | yes | |
HART secondary variable | yes | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
Resolution | 12 Bit (0 ... 26 mA) | |
Refresh time | 100 ms | |
Indicators/settings | ||
LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) Status LED (2) yellow: Live Zero monitoring | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
Mass | approx. 350 g | |
Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 13 ATEX E 050 X | |
Marking | II 2(1) G Ex d [ia Ga] IIC T4 Gb II (1) D [Ex ia Da] IIIC | |
Supply | ||
Voltage | 24.9 V | |
Current | 77 mA | |
Power | 478 mW (linear characteristic) | |
Connection 1-6 | ||
Voltage | 8.9 V | |
Current | 4 mA | |
Power | 24 mW (trapezoid characteristic curve) | |
Input | ||
Voltage | 0.7 V | |
Current | 7 mA | |
Power | 5 mW (trapezoid characteristic curve) | |
Internal capacitance | 242 nF | |
Internal inductance | 0 mH | |
Galvanic isolation | ||
Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2012 EN 60079-26:2007 | |
International approvals | ||
INMETRO | Brazil: TÜV 14.1596X | |
Marine approval | ||
Bureau Veritas Marine | 22449/B0 BV |
Slots | ||
---|---|---|
Occupied slots | 2 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 1.5 W | |
Power consumption | 3 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Analog input | ||
Number of channels | 4 | |
Suitable field devices | ||
Field device | pressure converter | |
Field device [2] | flow converter | |
Field device [3] | level converter | |
Field device [4] | Temperature Converter | |
Field device interface | ||
Connection | 2-wire transmitter | |
Connection [2] | 3-wire transmitter | |
Connection [3] | 4-wire transmitter | |
Connection | 2-wire transmitter (HART):Supply circuit: channel I 1+, 2-, channel II 5+, 6-, channel III 9+, 10-, channel IV 13+, 14-3-wire transmitter:Supply circuit: channel I 1+, 4-, channel II 5+, 8-, channel III 9+, 12-, channel IV 13+, 16-Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16-4-wire transmitter (powered externally):Measurement loop: channel I 3+, 4-, channel II 7+, 8-, channel III 11+, 12-, channel IV 15+, 16- | |
Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
Input resistance | 15 &Omega | |
Conversion time | max. 100 ms | |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
Short-circuit | factory setting: > 22 mA configurable between 0 ... 26 mA | |
Open-circuit | factory setting: < 1 mA configurable between 0 ... 26 mA | |
HART communication | yes | |
HART secondary variable | yes | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
Resolution | 12 Bit (0 ... 26 mA) | |
Refresh time | 100 ms | |
Indicators/settings | ||
LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
Mass | approx. 750 g | |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 12 ATEX E 101 X | |
Marking | II 2(1) G Ex d [ia Ga] IIC T4 Gb II (1) D [Ex ia Da] IIIC | |
Supply | ||
Voltage | 27 V | |
Current | 90 mA | |
Power | 588 mW (linear characteristic) | |
Input | ||
Voltage | 0.7 V | |
Current | 2.78 mA | |
Power | 2 mW (trapezoid characteristic curve) | |
Internal capacitance | 242 nF | |
Internal inductance | 0 mH | |
Galvanic isolation | ||
Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2012 EN 60079-26:2007 | |
International approvals | ||
ATEX approval | BVS 12 ATEX E 101 X | |
INMETRO | Brazil: TÜV 14.1597X | |
Marine approval | ||
Bureau Veritas Marine | 22449/B0 BV |
Slots | ||
---|---|---|
Occupied slots | 2 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 1.5 W | |
Power consumption | 3 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Analog output | ||
Number of channels | 4 | |
Suitable field devices | ||
Field device | Proportional Valve | |
Field device [2] | I/P converters | |
Field device [3] | on-site display | |
Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
Current | 0 ... 25 mA short-circuit protected | |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
Short-circuit | factory setting: < 50 &Omega configurable between 0 ... 26 mA | |
Open-circuit | deviation of preset output value > 0.5 mA | |
Load | 750 &Omega max. | |
HART communication | yes | |
HART secondary variable | yes | |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
Refresh time | 100 ms | |
Indicators/settings | ||
LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
Mass | approx. 750 g | |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 12 ATEX E 015 X | |
Marking | II 2(1) G Ex d [ia Ga] IIC T4 Gb II (1) D [Ex ia Da] IIIC | |
Galvanic isolation | ||
Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 | |
International approvals | ||
ATEX approval | BVS 12 ATEX E 015 X | |
INMETRO | Brazil: TÜV 14.1595X | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |
Slots | ||
---|---|---|
Occupied slots | 1 | |
Supply | ||
Connection | backplane bus | |
Rated voltage | 12 V DC , only in connection with the power supplies FB92** | |
Power dissipation | 0.5 W | |
Power consumption | 1 W | |
Internal bus | ||
Connection | backplane bus | |
Interface | manufacturer-specific bus to standard com unit | |
Analog output | ||
Number of channels | 1 | |
Suitable field devices | ||
Field device | Proportional Valve | |
Field device [2] | I/P converters | |
Field device [3] | on-site display | |
Connection | channel I: 2/3+, 4/5- | |
Current | 0 ... 25 mA short-circuit protected | |
Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
Short-circuit | factory setting: < 50 &Omega configurable between 0 ... 26 mA | |
Open-circuit | deviation of preset output value > 0.5 mA | |
Load | 750 &Omega max. | |
HART communication | yes | |
Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
Transfer characteristics | ||
Deviation | ||
After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
Refresh time | 100 ms | |
Indicators/settings | ||
LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1) red: line fault (lead breakage or short circuit) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2000 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | Ex e spring terminal with protective cover | |
Mass | approx. 350 g | |
Dimensions | 28 x 107 x 132 mm (1.1 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 11 ATEX E 093 X | |
Marking | II 2 G Ex db eb IIC T4 | |
Galvanic isolation | ||
Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11:2007 , voltage peak value 375 V | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-7:2007 | |
International approvals | ||
ATEX approval | BVS 11 ATEX E 093X | |
INMETRO | Brazil: TÜV 14.1599X | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |