General specifications | ||
---|---|---|
Switching function | Normally open (NO) | |
Output type | PNP | |
Rated operating distance | 6 mm | |
Installation | flush | |
Assured operating distance | 0 ... 4.86 mm | |
Actuating element | Nonferrous targets | |
Reduction factor rAl | 1 | |
Reduction factor rCu | 1.1 | |
Reduction factor r304 | 0 | |
Reduction factor rSt37 | 0 | |
Reduction factor rBrass | 0.9 | |
Output type | 3-wire | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V DC | |
Switching frequency | 2 Hz | |
Hysteresis | 5 ... 15 typ. 10 % | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | yes | |
Voltage drop | &le 2 V | |
Operating current | &le 100 mA | |
Current consumption | &le 22 mA | |
Off-state current | &le 10 µA | |
Indicators/operating means | ||
Operation indicator | Dual LED | |
Standard conformity | ||
Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 | |
Approvals and certificates | ||
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | Cable connector M8 x 1 , 3-pin with orange POC cable 200 mm | |
Core cross-section | 0.34 mm2 | |
Housing material | Xylan coated , Stainless steel 1.4305 / AISI 303 | |
Degree of protection | IP67 |
Производитель | Pepperl+Fuchs |
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Основная валюта на сайте указана в долларах. Счета выставляются в рублях по курсу ЦБ РФ +3% на дату выставления счета.
Минимальный счет на запчасти (без учета доставки):
Наличие и срок поставки запчастей уточняйте у Вашего менеджера. Если Ваш заказ получается меньше суммы минимального счета, то цена на запчасти может быть увеличена. Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Условия платежа - 100% предоплата, если иное не оговорено в договоре.
Оплата по счету
Мы выставляем счёт на вашу организацию и отправляем его по электронной почте. Если вы в первый раз покупаете через нашу компанию, то присылайте реквизиты на почту info@zipstore.ru. Как только мы увидим деньги на нашем расчетном счете и подготовим груз к отправке - мы с Вами свяжемся по электронной почте, на которую выставлен счет.
Перед получением товара, убедитесь в его готовности к отгрузке у Вашего менеджера.
1) Самовывоз из Москвы
Необходимо заранее согласовать время получение товара с менеджером и иметь при себе доверенность от организации установленного образца или круглую печать.
Склад находится по адресу: 127282, г. Москва, ул. Полярная, д. 33, стр. 3, 2-ой этаж, помещение 3
Чтобы не заблудиться, можете распечатать схему проезда.
2) Доставка транспортной компанией
Товары отгружаются покупателю в течение недели после поступления денежных средств на расчетный счет Продавца, если иное не оговорено в счете. Мы бесплатно доставляем Ваш заказ до транспортной компании "Деловые Линии" в г. Москве при заказе от 50 000 рублей за запчасти. Услуги межтерминальной перевозки Вы оплачиваете самостоятельно при получении груза. Найти ближайший к Вам терминал "Деловых линий" для выдачи посылок можно здесь.
3) Самовывоз из 118 пунктов выдачи в других городах России
Оплата за доставку при получении. Найдите ближайший терминал выдачи посылок на карте.
4) Доставка по Москве
Минимальная стоимость доставки курьером по г. Москве составляет 600 рублей.
В нашей компании Вы можете выбрать удобный для Вас способ доставки груза:
1) Организация доставки силами Zipstore.ru
Мы самостоятельно вызываем для Вас ТК "Деловые Линии". Груз передается водителю или курьеру ТК, при наличии у него транспортной накладной на товар. Для заказа транспортной компании нашими силами, Вам необходимо написать письмо на электронную почту Вашего менеджера, в котором указать:
2) Организация доставки Вашими силами
Через любую Транспортную компанию (далее ТК), которую Вы вызываете к нам своими силами. Груз передается водителю или курьеру ТК, при наличии у него транспортной накладной на товар.
3) Отправка через ЕМS почту силами Zipstore.ru
Если Вы выбрали этот вариант, то стоимость услуги за перевозку включается в счет за товар, так как оплата курьеру ЕМS почты осуществляется наличными и только при отправке груза. Таким образом, в дальнейшем Вам не придется оплачивать отдельные счета ТК.
Для заказа EMS нашими силами, Вам необходимо написать письмо на электронную почту Вашего менеджера, в котором указать:
1. Качество Оборудования должно соответствовать техническим характеристикам, изложенным в инструкции по эксплуатации Оборудования.
2. Продавец гарантирует отсутствие производственных дефектов в поставленном Оборудовании в течение гарантийного периода.
3. Гарантийный период на Оборудование составляет 12 месяцев, на оригинальные запасные части 3 месяца, на аналоги 1 месяц, если иное не предусмотрено Спецификацией.
4. Претензии к внешнему виду товара принимаются в течение 2-х недель, с момента отгрузки товара.
5. Гарантия не распространяется на запчасти для технологического и ресторанного оборудования, интерфейсы (последовательного и Ethernet), материнские платы Godex, расходные материалы.
6. Если в течение гарантийного периода (п.3) Оборудование или его часть, указанные в Счете, окажутся дефектными, Продавец обязуется произвести ремонт или замену Оборудования или его части без оплаты Покупателем при соблюдении следующих условий:
6.1. Диагностика неисправности была проведена авторизованными специалистами производителя оборудования.
6.2. Покупатель письменно извещает Продавца об обнаруженных дефектах с их подробным описанием. Рекламация подписывается авторизованным специалистом.
6.3. Если дефекты не вызваны существенными нарушениями технических требований, оговоренных в инструкции по эксплуатации (в том числе нестабильностью параметров питающей электрической сети и отсутствием или ненадлежащим выполнением заземления Оборудования).
6.4. Если дефекты не вызваны вскрытием, ремонтом, модификацией или неправильным запуском Оборудования.
6.5. Если дефекты не вызваны повреждением вследствие действия на нее других неисправных частей.
6.6. Если отсутствуют видимые механические повреждения, в т.ч. сколы и царапины на нагревательной поверхности печатающих термоголовок (см. документ "Гарантийные обязательства на печатающие термоголовки").
6.7. Если дефекты не вызваны пожаром или затоплением помещения и не являются следствием неправильной эксплуатации Оборудования.
6.8. Если Специалистами Покупателя регулярно проводилось обслуживание Оборудования согласно инструкции по эксплуатации.
6.9. Если регулировка и настройка Оборудования проводилась Покупателем согласно инструкции по эксплуатации.
6.10. Если дефект не является следствием нормального износа быстроизнашивающихся деталей.
6.11. Если применялись расходные материалы, одобренные производителем.
6.12. Если оплата за товар произведена полностью.
7. При несоблюдении Покупателем условий, указанных в пп. 6.1.-6.12. , гарантия истекает немедленно.
8. Доставка гарантийного Оборудования производится силами и за счет Покупателя.
9. При невозможности замены бракованных Запчастей, неисправного Оборудования или неисправных частей Оборудования, возврат денежных средств производится в течении 14 рабочих дней, с момента заключения специалистами Продавца и оформления письма о возврате денежных средств Покупателем.
10. В случаях обнаружения брака (товара ненадлежащего качества) сразу необходимо упаковать товар, не пользоваться им, в течение ближайшего времени связаться с нами. Отправка товара ненадлежащего качества должна быть произведена в течении 5 дней с момента подтверждения брака Продавцом.
11. Возврат или обмен товара надлежащего качества остается на усмотрение Продавца, если иное не предусмотрено договором поставки (Закон о Защите Прав Потребителей не распространяется на взаимоотношения юридических лиц).
12. Должны быть сохранены упаковка товара (в чистом виде), товарный вид, потребительские свойства, пломбы, фабричные ярлыки, а также все полученные от продавца документы (чеки, бухгалтерские документы, инструкция по эксплуатации).
13. Денежные средства возвращаются тем же способом, которым был оплачен заказ.
14. Запчасти и расходные материалы для торгового, складского ресторанного и технологического оборудования не подлежат сертификации, по этой причине отказные письма не выдаются.
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
В случае возникновения вопросов, касающихся свойств и характеристик товара, перед оформлением счета обратитесь к нашим сотрудникам. Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
General specifications | ||
---|---|---|
Switching function | complementary | |
Output type | PNP | |
Slot width | 3.5 mm | |
Depth of immersion (lateral) | 5 ... 7 mm | |
Output polarity | DC | |
Assured operating distance | ||
Output type | 3-wire | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V DC | |
Switching frequency | 0 ... 3000 Hz | |
Hysteresis | 0.1 ... 0.4 mm | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | &le 2 V | |
Operating current | 0 ... 100 mA | |
No-load supply current | &le 15 mA | |
Switching state indicator | LED | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Connection type | Cable connector M8 x 1 , 4-pin , cable: PVC , L = 500 mm ± 5 mm | |
Housing material | Crastin (PBTB) | |
Degree of protection | IP67 | |
General information | ||
Scope of delivery | screw M 1.7 x 10 , nut M1.7 |
General specifications | ||
---|---|---|
Switching function | Normally open (NO) | |
Output type | NPN | |
Rated operating distance | 1.5 mm | |
Installation | flush | |
Output polarity | DC | |
Assured operating distance | 0 ... 1.215 mm | |
Actuating element | Ferrous targets | |
Reduction factor rAl | 0 | |
Reduction factor rCu | 0 | |
Reduction factor r304 | 0.4 - 0.7 | |
Reduction factor rSt37 | 1 | |
Reduction factor rBrass | 0 | |
Output type | 3-wire | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V DC | |
Switching frequency | 80 Hz | |
Hysteresis | 5 ... 15 typ. 10 % | |
Reverse polarity protection | yes | |
Short-circuit protection | yes | |
Voltage drop | &le 2 V | |
Operating current | &le 100 mA | |
Current consumption | &le 10 mA | |
Off-state current | &le 10 µA | |
Indicators/operating means | ||
Operation indicator | LED red: output | |
Standard conformity | ||
Standards | EN 60947-5-2:2007 IEC 60947-5-2:2007 | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 75 °C (-13 ... 167 °F) | |
Mechanical specifications | ||
Connection type | Cable connector M12 x 1 , 3-pin with PUR cable 150 mm | |
Core cross-section | 0.14 mm2 | |
Housing material | Stainless steel 1.4305 / AISI 303 | |
Sensing face | Stainless steel 1.4305 / AISI 303 | |
Housing diameter | 8 mm | |
Degree of protection | IP67 |
General specifications | ||
---|---|---|
Switching function | Normally open (NO) | |
Output type | PNP | |
Rated operating distance | 6 mm | |
Installation | flush in mild steel | |
Output polarity | DC | |
Assured operating distance | 0 ... 4.86 mm | |
Reduction factor rAl | 1 | |
Reduction factor rCu | 0.85 | |
Reduction factor r304 | 0.5 (0.9 of material thickness 2 mm) | |
Reduction factor rSt37 | 1 | |
Output type | 3-wire | |
Nominal ratings | ||
Installation conditions | ||
A | 0 mm | |
B | 6 mm | |
C | 18 mm | |
F | 50 mm | |
Operating voltage | 10 ... 30 V | |
Switching frequency | 0 ... 600 Hz | |
Hysteresis | 3 ... 15 typ. 5 % | |
Reverse polarity protection | yes | |
Short-circuit protection | yes | |
Voltage drop | &le 2 V | |
Operating current | 0 ... 200 mA | |
Off-state current | &le 0.1 mA | |
No-load supply current | &le 10 mA | |
Switching state indicator | LED, yellow | |
Limit data | ||
Operating pressure statically | 80 bar (1160.3 psi) max. | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Mechanical specifications | ||
Connection type | cable TPE-S , 2 m | |
Housing material | Stainless steel 1.4435 / AISI 316L | |
Sensing face | Stainless steel 1.4435 / AISI 316L | |
Degree of protection | IP68 / IP69K | |
Mass | 112 g |
General specifications | ||
---|---|---|
Switching function | complementary | |
Output type | PNP | |
Slot width | 30 mm | |
Depth of immersion (lateral) | 27 ... 31 typ. | |
Installation | ||
Output polarity | DC | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V | |
Switching frequency | 0 ... 150 Hz | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | &le 3 V | |
Operating current | 0 ... 200 mA | |
No-load supply current | &le 20 mA | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | Connector M12 x 1 , 4-pin | |
Housing material | ABS | |
Degree of protection | IP67 |
General specifications | ||
---|---|---|
Rated operating distance | 8 mm | |
Installation | flush | |
Output polarity | switched high | |
Assured operating distance | 0 ... 6.48 mm | |
Reduction factor rAl | 1 | |
Reduction factor rCu | 1 | |
Reduction factor r304 | 1 | |
Reduction factor rSt37 | 1 | |
Output type | 4-wire | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V DC | |
Switching frequency | 0 ... 600 Hz | |
Hysteresis | typ. 5 % | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | &le 2 V | |
Rated insulation voltage | 60 V | |
Operating current | 0 ... 200 mA | |
Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
No-load supply current | &le 12 mA | |
Constant magnetic field | 200 mT | |
Alternating magnetic field | 200 mT | |
Switching state indicator | all direction LED, yellow | |
Functional safety related parameters | ||
MTTFd | 1393 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Approvals and certificates | ||
Protection class | II | |
Rated insulation voltage | 60 V | |
Rated impulse withstand voltage | 800 V | |
UL approval | cULus Listed, General Purpose Class 2 power source | |
CSA approval | cCSAus Listed, General Purpose Class 2 power source | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Connection type | cable PUR , 2 m | |
Core cross-section | 0.34 mm2 | |
Housing material | Brass, PTFE coated | |
Sensing face | PPS | |
Housing diameter | 18 mm | |
Degree of protection | IP68 / IP69K | |
Mass | 80 g | |
General information | ||
Scope of delivery | 2 self locking nuts in scope of delivery |
General specifications | ||
---|---|---|
Switching function | Normally open (NO) | |
Output type | PNP | |
Rated operating distance | 3 mm | |
Installation | non-flush | |
Output polarity | DC | |
Assured operating distance | 0 ... 2.43 mm | |
Reduction factor rAl | 0.5 | |
Reduction factor rCu | 0.5 | |
Reduction factor r304 | 0.75 | |
Output type | 3-wire | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V | |
Switching frequency | 0 ... 1000 Hz | |
Hysteresis | typ. 5% | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | &le 3 V | |
Operating current | 0 ... 100 mA | |
Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
No-load supply current | &le 15 mA | |
Switching state indicator | Multihole-LED, yellow | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | Connector M8 x 1 , 3-pin | |
Housing material | brass, nickel-plated | |
Sensing face | PBT | |
Housing diameter | 8 mm | |
Degree of protection | IP67 | |
General information | ||
Scope of delivery | 2 hex nuts included |
General specifications | ||
---|---|---|
Switching function | Normally open (NO) | |
Output type | PNP | |
Rated operating distance | 10 mm | |
Installation | non-flush | |
Output polarity | DC | |
Assured operating distance | 0 ... 8.1 mm | |
Reduction factor rAl | 1 | |
Reduction factor rCu | 1 | |
Reduction factor r304 | 1 | |
Reduction factor rSt37 | 1 | |
Output type | 3-wire | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V DC | |
Switching frequency | 0 ... 1000 Hz | |
Hysteresis | typ. 5 % | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | &le 2 V | |
Rated insulation voltage | 60 V | |
Operating current | 0 ... 200 mA | |
Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
No-load supply current | &le 12 mA | |
Constant magnetic field | 200 mT | |
Alternating magnetic field | 200 mT | |
Switching state indicator | Multihole-LED, yellow | |
Functional safety related parameters | ||
MTTFd | 1393 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Approvals and certificates | ||
Protection class | II | |
Rated insulation voltage | 60 V | |
Rated impulse withstand voltage | 800 V | |
UL approval | cULus Listed, General Purpose Class 2 power source | |
CSA approval | cCSAus Listed, General Purpose Class 2 power source | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Connection type | Connector M12 x 1 , 4-pin | |
Housing material | Brass, PTFE coated | |
Sensing face | PPS | |
Housing diameter | 12 mm | |
Degree of protection | IP67 | |
Mass | 15 g | |
General information | ||
Scope of delivery | 2 self locking nuts in scope of delivery |
General specifications | ||
---|---|---|
Switching function | Normally open (NO) | |
Output type | PNP | |
Rated operating distance | 8 mm | |
Installation | flush | |
Output polarity | DC | |
Assured operating distance | 0 ... 6.48 mm | |
Actuating element | Ferrous targets | |
Reduction factor rAl | 0 | |
Reduction factor rCu | 0 | |
Reduction factor r304 | 0.6 - 0.8 | |
Reduction factor rSt37 | 1 | |
Reduction factor rBrass | 0 | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V DC | |
Switching frequency | 0 ... 2 Hz | |
Hysteresis | 3 ... 15 typ. 5 % | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | &le 2 V | |
Operating current | &le 200 mA | |
Current consumption | < 14 mA | |
Off-state current | &le 10 µA | |
Operating voltage indicator | LED, green | |
Switching state indicator | LED, yellow | |
Mag. Field strength, AC fields | 250 mT | |
Mag. Field strength, DC fields | 250 mT | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | V1 connector (M12 x 1), 4-pin | |
Housing material | Xylan coated - Stainless steel 1.4305 / AISI 303 | |
Sensing face | Xylan coated - Stainless steel 1.4305 / AISI 303 | |
Housing diameter | 30 mm | |
Degree of protection | IP67 / IP68 / IP69K - cordset dependent according to cable specification |
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Slot width | 3.5 mm | |
Depth of immersion (lateral) | 5 ... 7 mm , typ. 6 mm | |
Installation | ||
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) | |
Operating voltage | 5 ... 25 V | |
Switching frequency | 0 ... 3000 Hz | |
Hysteresis | 0.8 ... 1.1 mm | |
Current consumption | ||
Measuring plate not detected | &ge 3 mA | |
Measuring plate detected | &le 1 mA | |
Functional safety related parameters | ||
MTTFd | 8760 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 | |
Approvals and certificates | ||
FM approval | ||
Control drawing | 116-0165 | |
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | flexible leads PVC , 500 mm | |
Core cross-section | 0.14 mm2 | |
Housing material | PBT | |
Degree of protection | IP67 | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 2G |
General specifications | ||
---|---|---|
Switching function | complementary | |
Output type | PNP | |
Slot width | 15 mm | |
Depth of immersion (lateral) | 17 ... 20 mm | |
Installation | ||
Output polarity | DC | |
Nominal ratings | ||
Nominal voltage | 8 V | |
Operating voltage | 10 ... 30 V DC | |
Switching frequency | 0 ... 500 Hz | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | &le 3 V | |
Operating current | 0 ... 200 mA | |
No-load supply current | &le 20 mA | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | Connector M12 x 1 , 4-pin | |
Housing material | PBT | |
Degree of protection | IP67 |
General specifications | ||
---|---|---|
Switching function | 2 x normally open (NO) | |
Output type | PNP | |
Rated operating distance | 3 mm | |
Installation | flush mountable | |
Output polarity | DC | |
Assured operating distance | 0 ... 2.43 mm | |
Actual operating distance | 2.6 ... 2.6 mm typ. | |
Reduction factor rAl | 0.5 | |
Reduction factor r304 | 1 | |
Reduction factor rSt37 | 1.1 | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V DC | |
Switching frequency | 0 ... 100 Hz | |
Hysteresis | typ. 5 % | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | &le 3 V | |
Operating current | 0 ... 200 mA | |
Off-state current | 0 ... 0.5 mA typ. 0.1 µA at 25 °C | |
No-load supply current | &le 25 mA | |
Operating voltage indicator | LED, green | |
Switching state indicator | LED, yellow | |
Valve status indicator | LED, yellow | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Connection (system side) | Cage tension spring terminals | |
Core cross-section (system side) | up to 2.5 mm2 | |
Connection (valve side) | Cage tension spring terminals | |
Core cross-section (valve side) | up to 2.5 mm2 | |
Housing material | PBT | |
Sensing face | PBT | |
Degree of protection | IP20 |
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR with safety function | |
Rated operating distance | 8 mm | |
Installation | non-flush | |
Assured operating distance | 0 ... 6.48 mm | |
Reduction factor rAl | 0.4 | |
Reduction factor rCu | 0.3 | |
Reduction factor r304 | 0.85 | |
Safety Integrity Level (SIL) | up to SIL3 acc. to IEC 61508 Danger! In safety-related applications the sensor must be operated with a qualified fail safe interface from Pepperl+Fuchs, such as KFD2-SH-EX1. Consider the "exida Functional Safety Assessment" document which is available on www.pepperl-fuchs.com as an integral part of this product's documentation. | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8.2 V | |
Switching frequency | 0 ... 200 Hz | |
Current consumption | ||
Measuring plate not detected | &ge 3 mA | |
Measuring plate detected | &le 1 mA | |
Functional safety related parameters | ||
MTTFd | 11850 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Approvals and certificates | ||
FM approval | ||
Control drawing | 116-0165 | |
UL approval | cULus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -40 ... 100 °C (-40 ... 212 °F) | |
Mechanical specifications | ||
Connection type | cable silicone , 10 m | |
Core cross-section | 0.75 mm2 | |
Housing material | Crastin (PBTB), black | |
Sensing face | Crastin (PBTB), black | |
Degree of protection | IP68 | |
Cable | ||
Bending radius | > 10 x cable diameter | |
Equipment protection level Gc (nA) | ||
Certificate | PF 15CERT3754 X | |
Special conditions | ||
Protection against transients | Ensure transient protection is provided and that the maximum value of the transient protection (140% of 85 V) is not exceeded. | |
Equipment protection level Dc (tc) | ||
Instruction | Manual electrical apparatus for hazardous areas | |
Device category 3D | for use in hazardous areas with combustible dust | |
Certificate | PF 15CERT3774 X | |
CE marking | [*PD-Z02586A*] | |
ATEX marking | II 3D Ex tc IIIC T80°C Dc The Ex-related marking can also be printed on the enclosed label. | |
Standards | EN 60079-0:2012+A11:2013, EN 60079-31:2014 Protection by enclosure "tc" Some of the information in this instruction manual is more specific than the information provided in the datasheet. | |
General | The corresponding datasheets, declarations of conformity, EC-type examination certificates, certifications, and control drawings, where applicable (see datasheets), form an integral part of this document. These documents can be found at www.pepperl-fuchs.com. The maximum surface temperature of the device was determined without a layer of dust on the apparatus. Some of the information in this instruction manual is more specific than the information provided in the datasheet. | |
Installation, commissioning | Laws and/or regulations and standards governing the use or intended usage goal must be observed. If the Ex-related marking is printed only on the supplied label, then this must be attached in the immediate vicinity of the sensor. The sticking surface for the label must be clean and free from grease. The attached label must be legible and indelible, including in the event of possible chemical corrosion. | |
Maintenance | No changes can be made to apparatus, which are operated in hazardous areas. Repairs to these apparatus are not possible. | |
Special conditions | ||
Minimum series resistance RV | A minimum series resistance RV is to be provided between the power supply voltage and the proximity switch in accordance with the following list. This can also be assured by using a switch amplifier. | |
Maximum operating voltage UBmax | The maximum permissible operating voltage UBmax must be restricted to the values given in the following list. Tolerances are not permitted. | |
Maximum permissible ambient temperature TUmax | Values can be obtained from the following list, depending on the max. operating voltage Ub max and the minimum series resistance Rv. | |
at UBmax=9 V, RV=562 &Omega | 58 °C (136.4 °F) | |
using an amplifier in accordance with EN 60947-5-6 | 58 °C (136.4 °F) | |
Protection from mechanical danger | The sensor must not be exposed to ANY FORM of mechanical danger. | |
Protection from UV light | The sensor and the connection cable must be protected from damaging UV-radiation. This can be achieved when the sensor is used in internal areas. | |
Protection of the connection cable | The connection cable must be prevented from being subjected to tension and torsional loading. | |
Electrostatic charge | Do not attach the nameplate provided in areas where electrostatic charge can build up. | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G 2G 3G 1D 3D |