General specifications | ||
---|---|---|
Signal type | Analog input/analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Rated voltage | loop powered | |
Power dissipation | 0.2 W | |
Control circuit | ||
Connection | terminals 8-, 9+ | |
Voltage | max. 30 V DC | |
Current | 4 ... 20 mA (quiescent current < 0.5 mA) | |
Power dissipation | 150 mW at 20 mA and Uin < 24 V | |
Field circuit | ||
Connection | terminals 1+, 2 / 3- | |
Voltage | &ge 16 V for supply voltage > 21 V | |
Current | 4 ... 20 mA (linear transmission 1 ... 22 mA) | |
Load | &le 800 &Omega (at 20 mA) | |
Transfer characteristics | ||
Voltage drop | see note | |
Influence of ambient temperature | < 0.5 µA/K | |
Damping | approx. 3 dB | |
Rise time | &le 20 µs at 0 &Omega, &le 600 µs with 800 &Omega load | |
Indicators/settings | ||
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 120 g | |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 02 ATEX 2064 | |
Marking | ![]() | |
Certificate | PF 11 CERT 0902 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | device with FM approval on request |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | within the supply tolerance | |
Rated current | < 20 mA | |
Power consumption | 0.35 W (24 V and 1 mA sense current) | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4 | |
Line fault detection | yes , at Pt100 | |
Lead resistance | &le 10 % of resistance value | |
Transmission range | 0 ... 10 mA | |
Available voltage | 9 V | |
Line fault detection | 8 nA | |
Output | ||
Connection side | control side | |
Connection | terminals 5-, 7-, 6+, 8+ | |
Current | 0 ... 10 mA | |
Available voltage | 0 ... 4.2 V | |
Fault signal | < 10 &Omega or > 400 &Omega, depending on lead disconnected (measuring current &le 1 mA) > 400 &Omega, terminal 3 lead disconnected in 2-/4-wire (measuring current &le 0.3 mA) | |
Transfer characteristics | ||
Accuracy | 0.1 % | |
Deviation | 4-wire Im &ge 1 mA: ±0.1 % of Rm or ± 0.1 &Omega (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: ± 1 % of Rm or 1 &Omega (the larger value is applicable). 3-wire Im &ge 1 mA: (±0.1 % - 0.1 &Omega Offset) or ± 0.2 &Omega (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: (±1 % - 0.1 &Omega Offset) or ± 1.1 &Omega (the larger value is applicable) | |
Rise time | signal response time &le 2 ms (10 ... 90 %) response to application of Im: Rm > 50 &Omega and Im < 5mA: < 5ms response to application of Im: Rm > 30 &Omega and Im < 5mA: < 10ms response to application of Im: Rm > 18 &Omega and Im < 5mA: < 20ms | |
Indicators/settings | ||
Display elements | LED | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BASEEFA 10 ATEX 0061 | |
Marking | ![]() ![]() ![]() | |
Certificate | BASEEFA 10 ATEX 0062X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 (cFMus) | |
UL approval | ||
Control drawing | 116-0332 (cULus) | |
IECEx approval | IECEx BAS 10.0024 IECEx BAS 10.0025X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
Accessories | ||
Designation | optional accessories: insertion bridge EBP 2- 5 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | within the supply tolerance | |
Rated current | < 20 mA | |
Power consumption | 0.35 W (24 V and 1 mA sense current) | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4 | |
Lead resistance | &le 10 % of resistance value | |
Transmission range | 0 ... 10 mA | |
Available voltage | 9 V | |
Output | ||
Connection side | control side | |
Connection | terminals 5-, 7-, 6+, 8+ | |
Current | 0 ... 10 mA | |
Available voltage | 0 ... 7 V | |
Transfer characteristics | ||
Accuracy | 0.1 % | |
Deviation | Im &ge 1 mA: ±0.1 % of Rm or ± 0.1 &Omega (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: ± 1 % of Rm or 1 &Omega (the larger value is applicable). | |
Rise time | signal response time &le 2 ms (10 ... 90 %) response to application of Im: Rm > 50 &Omega and Im < 5mA: < 5ms response to application of Im: Rm > 30 &Omega and Im < 5mA: < 10ms response to application of Im: Rm > 18 &Omega and Im < 5mA: < 20ms | |
Indicators/settings | ||
Display elements | LED | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BASEEFA 10 ATEX 0061 | |
Marking | ![]() ![]() ![]() | |
Certificate | BASEEFA 10 ATEX 0062X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 (cFMus) | |
UL approval | ||
Control drawing | 116-0332 (cULus) | |
IECEx approval | IECEx BAS 10.0024 IECEx BAS 10.0025X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
Accessories | ||
Designation | optional accessories: insertion bridge EBP 2- 5 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | within the supply tolerance | |
Rated current | < 20 mA | |
Power consumption | 0.35 W (24 V and 1 mA sense current) | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4 | |
Line fault detection | yes , at Pt100 | |
Lead resistance | &le 10 % of resistance value | |
Transmission range | 0 ... 10 mA | |
Available voltage | 9 V | |
Line fault detection | 8 nA | |
Output | ||
Connection side | control side | |
Connection | terminals 5-, 7-, 6+, 8+ | |
Current | 0 ... 10 mA | |
Available voltage | 0 ... 4.2 V | |
Fault signal | < 10 &Omega or > 400 &Omega, depending on lead disconnected (measuring current &le 1 mA) > 400 &Omega, terminal 3 lead disconnected in 2-/4-wire (measuring current &le 0.3 mA) | |
Transfer characteristics | ||
Accuracy | 0.1 % | |
Deviation | Im &ge 1 mA: ±0.1 % of Rm or ± 0.1 &Omega (the larger value is applicable) Im < 1 mA: accuracy reduces in proportion to Im. e. g. Im = 0.1 mA: ± 1 % of Rm or 1 &Omega (the larger value is applicable). | |
Rise time | signal response time &le 2 ms (10 ... 90 %) response to application of Im: Rm > 50 &Omega and Im < 5mA: < 5ms response to application of Im: Rm > 30 &Omega and Im < 5mA: < 10ms response to application of Im: Rm > 18 &Omega and Im < 5mA: < 20ms | |
Indicators/settings | ||
Display elements | LED | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | spring terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BASEEFA 10 ATEX 0061 | |
Marking | ![]() ![]() ![]() | |
Certificate | BASEEFA 10 ATEX 0062X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 (cFMus) | |
UL approval | ||
Control drawing | 116-0332 (cULus) | |
IECEx approval | IECEx BAS 10.0024 IECEx BAS 10.0025X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Описание оборудования | ||
---|---|---|
Transmission range 0 V ... 9 V |
Описание оборудования | ||
---|---|---|
Transmission range 0 V ... 12 V |
Описание оборудования | ||
---|---|---|
Transmission range 0 V ... ± 10 V |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Rated current | < 30 mA | |
Input | ||
Connection side | field side | |
Connection | terminals 4+, 5- | |
Input resistance | min. 10 M&Omega | |
Transmission range | -10 ... 10 V | |
Offset voltage/current | < 10 mV / < 1 µA | |
Output | ||
Connection side | control side | |
Connection | terminals 7-, 8+ | |
Voltage | -10 ... 10 V | |
Output resistance | max. 20 &Omega | |
Transfer characteristics | ||
Cut-off frequency | 50 kHz (-3 dB) | |
Rise time | &le 10 µs | |
Indicators/settings | ||
Display elements | LED | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 110 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7262 | |
Marking | ![]() | |
Certificate | BASEEFA 10 ATEX 0079X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
UL approval | ||
Control drawing | 116-0173 (cULus) | |
CSA approval | ||
Control drawing | 116-0132 | |
IECEx approval | IECEx BAS 10.0040X | |
Approved for | Ex nA IIC T4 Gc |
Описание оборудования | ||
---|---|---|
Transmission range 0 mV ... ± 500 mV |
Описание оборудования | ||
---|---|---|
Transmission range 0 mV ... ± 50 mV |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | &le 1.2 W | |
Power consumption | &le 1.6 W | |
Input | ||
Connection side | field side | |
Connection | terminals 4 (common), 1, 3 and 5 (supply -), 2 and 6 (signal -) | |
Input resistance | 10 k&Omega terminals 4 (common), 6-/2- | |
Output rated operating current | terminals 4 (common), 5-: > 10 mA at -21 V or > 20 mA at -18 V terminals 4 (common), 1-: 5.3 mA ±0.4 mA at -10 V terminals 4 (common), 3-: 3.6 mA ±0.7 mA at -10 V, 20 °C (68 °F) | |
Transmission range | -20 ... 0 V | |
Output | ||
Connection side | control side | |
Connection | terminals 7-, 8+ | |
Load | &ge 9 k&Omega (3-wire sensor), &ge 2 k&Omega (2-wire sensor) | |
Voltage | -20 ... 0 V | |
Output resistance | 24 &Omega typ., 27 &Omega maximum Since this is much less than the end-to-end resistance of a zener barrier, it may be necessary to specify a monitor intended for use without a barrier. Please follow the advice of the monitor manufacturer. | |
Transfer characteristics | ||
Cut-off frequency | 10 kHz (-0,1 dB) 20 kHz (-1 dB) | |
Deviation | DC transfer error (with 10 k&Omega load) < 10mV | |
Time delay relative to input | 7.1 ±0.3 µs | |
Ripple | in 200 kHz bandwidth < 20 mVrms in 20 kHz bandwidth < 3 mVrms | |
Indicators/settings | ||
Display elements | LED | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 125 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 02 ATEX 7206 | |
Marking | ![]() | |
EU-Type Examination Certificate | DMT 01 ATEX E 133 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1499 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 | |
International approvals | ||
UL approval | ||
Control drawing | 116-0316 (cULus) | |
IECEx approval | IECEx BAS 05.0078 IECEx BAS 10.0085X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Rated voltage | 12 ... 35 V DC loop powered | |
Power dissipation | 0.4 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Current range | 0 ... 20 mA , load &le 50 &Omega | |
Voltage range | 0 ... 10 V , load &ge 100 k&Omega | |
Output | ||
Connection side | control side | |
Connection | terminals 9+, 8- | |
Load | (U -12 V) / 0.02 A | |
Current output | 4 ... 20 mA , limited to &le 35 mA | |
Fault signal | downscaling &le 3 mA | |
Transfer characteristics | ||
Rise time | 250 ms | |
Indicators/settings | ||
Control elements | DIP-switch potentiometer | |
Configuration | via DIP switches via potentiometer | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Galvanic isolation | EN 50178:1997 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | ZELM 00 ATEX 0034 | |
Marking | ![]() | |
Certificate | TÜV 01 ATEX 1777 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0132 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 0.5 W | |
Power consumption | 0.6 W | |
Input | ||
Connection side | field side | |
Connection | terminals 4-, 5-, 3+, 2+, 1+ | |
Potentiometer | ||
Types of measuring | 3-, 4-, 5-wire technology | |
Lead resistance | 5 % of the potentiometer resistance (adjustable) | |
Output | ||
Connection side | control side | |
Connection | terminals 7-, 8+ | |
Voltage output | 0 ... 10 V | |
Output resistance | max. 30 &Omega | |
Transfer characteristics | ||
Accuracy | 0.05 % | |
Rise time | 10 to 90 % &le 8 ms 10 to 90 % within 1 % of span &le 25 ms | |
Indicators/settings | ||
Control elements | potentiometer | |
Configuration | via potentiometer | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 120 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7171 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1797 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
UL approval | ||
Control drawing | 116-0173 (cULus) | |
CSA approval | ||
Control drawing | 116-0132 | |
IECEx approval | IECEx BAS 10.0060 IECEx BAS 10.0061X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 0.5 W | |
Power consumption | 0.6 W | |
Input | ||
Connection side | field side | |
Connection | terminals 4-, 5-, 3+, 2+, 1+ | |
Potentiometer | ||
Types of measuring | 3-, 4-, 5-wire technology | |
Lead resistance | 5 % of the potentiometer resistance (adjustable) | |
Output | ||
Connection side | control side | |
Connection | terminals 7-, 8+ | |
Voltage output | 0 ... 5 V | |
Output resistance | max. 30 &Omega | |
Transfer characteristics | ||
Accuracy | 0.05 % | |
Rise time | 10 to 90 % &le 8 ms 10 to 90 % within 1 % of span &le 25 ms | |
Indicators/settings | ||
Control elements | potentiometer | |
Configuration | via potentiometer | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 120 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7171 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1797 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
UL approval | ||
Control drawing | 116-0173 (cULus) | |
CSA approval | ||
Control drawing | 116-0132 | |
IECEx approval | IECEx BAS 10.0060 IECEx BAS 10.0061X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 1 W | |
Power consumption | 1.3 W | |
Input | ||
Connection side | field side | |
Connection | terminals 4-, 5-, 3+, 2+, 1+ | |
Potentiometer | ||
Types of measuring | 3-, 4-, 5-wire technology | |
Lead resistance | 5 % of the potentiometer resistance (adjustable) | |
Output | ||
Connection side | control side | |
Connection | terminals 7-, 8+ | |
Current output | 0 ... 20 mA, load &le1 k&Omega | |
Transfer characteristics | ||
Accuracy | 0.05 % | |
Rise time | 10 to 90 % &le 8 ms 10 to 90 % within 1 % of span &le 25 ms | |
Indicators/settings | ||
Control elements | potentiometer | |
Configuration | via potentiometer | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 120 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7171 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1797 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
UL approval | ||
Control drawing | 116-0173 (cULus) | |
CSA approval | ||
Control drawing | 116-0132 | |
IECEx approval | IECEx BAS 10.0060 IECEx BAS 10.0061X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 1 W | |
Power consumption | 1.3 W | |
Input | ||
Connection side | field side | |
Connection | terminals 4-, 5-, 3+, 2+, 1+ | |
Potentiometer | ||
Types of measuring | 3-, 4-, 5-wire technology | |
Lead resistance | 5 % of the potentiometer resistance (adjustable) | |
Output | ||
Connection side | control side | |
Connection | terminals 7-, 8+ | |
Current output | 4 ... 20 mA, load &le1 k&Omega | |
Transfer characteristics | ||
Accuracy | 0.05 % | |
Rise time | 10 to 90 % &le 8 ms 10 to 90 % within 1 % of span &le 25 ms | |
Indicators/settings | ||
Control elements | potentiometer | |
Configuration | via potentiometer | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 120 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7171 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1797 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
UL approval | ||
Control drawing | 116-0173 (cULus) | |
CSA approval | ||
Control drawing | 116-0132 | |
IECEx approval | IECEx BAS 10.0060 IECEx BAS 10.0061X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 1 W | |
Power consumption | 1.3 W | |
Input | ||
Connection side | field side | |
Connection | terminals 4-, 5-, 3+, 2+, 1+ | |
Lead resistance | &le 5 % of the potentiometer resistance at &ge 500 &Omega (can be equalized by user) | |
Potentiometer resistance | &ge 500 &Omega | |
Potentiometer voltage | approx. 4.7 V | |
Output | ||
Connection side | control side | |
Connection | terminals 7-, 8+ | |
Current output | 0 ... 20 mA, load &le1 k&Omega | |
Transfer characteristics | ||
Accuracy | 0.05 % | |
Rise time | 10 to 90 % &le 8 ms 10 to 90 % within 1 % of span &le 25 ms | |
Indicators/settings | ||
Control elements | potentiometer | |
Configuration | via potentiometer | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 120 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7171 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1797 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
UL approval | ||
Control drawing | 116-0173 (cULus) | |
CSA approval | ||
Control drawing | 116-0132 | |
IECEx approval | IECEx BAS 10.0060 IECEx BAS 10.0061X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 0.6 W | |
Power consumption | 0.7 W | |
Input | ||
Connection side | field side | |
Connection | terminals 4-, 5-, 3+, 2+, 1+ | |
Lead resistance | 5 % of the potentiometer resistance at &ge 500 &Omega (can be equalized by user) | |
Potentiometer resistance | &ge 500 &Omega | |
Potentiometer voltage | approx. 4.7 V | |
Output | ||
Connection side | control side | |
Connection | terminals 7-, 8+ | |
Voltage output | 0 ... 10 V | |
Output resistance | max. 30 &Omega | |
Transfer characteristics | ||
Accuracy | 0.05 % | |
Rise time | 10 to 90 % &le 8 ms 10 to 90 % within 1 % of span &le 25 ms | |
Indicators/settings | ||
Control elements | potentiometer | |
Configuration | via potentiometer | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 120 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7171 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1797 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
UL approval | ||
Control drawing | 116-0173 (cULus) | |
CSA approval | ||
Control drawing | 116-0132 | |
IECEx approval | IECEx BAS 10.0060 IECEx BAS 10.0061X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Rated voltage | 12 ... 35 V DC loop powered | |
Power dissipation | 0.4 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2-, 3+ suitable for Pt100, 2- and 3-wire connection | |
Lead resistance | max. 100 &Omega per line | |
Measuring current | approx. 1 mA | |
Output | ||
Connection side | control side | |
Connection | terminals 9+, 8- | |
Load | (U -12 V) / 0.02 A | |
Current output | 4 ... 20 mA , limited to &le 35 mA | |
Fault signal | upscaling &ge 22 mA (limited to 35 mA) | |
Transfer characteristics | ||
Measurement range | span without linearization 25 ... 800 °C (77 ... 1472 °F)/with linearization 25 ... 375 °C (77 ... 707 °F), both adjustable zero point without linearization -200 ... 400 °C (-328 ... 752 °F)/with linearization -30 ... 375 °C (-22 ... 707 °F), both adjustable | |
Rise time | 250 ms | |
Indicators/settings | ||
Control elements | DIP-switch rotary switch | |
Configuration | via DIP switches via rotary switch | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Insulation coordination | EN 50178 | |
Galvanic isolation | EN 50178 | |
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | ZELM 00 ATEX 0036 | |
Marking | ![]() | |
Certificate | TÜV 01 ATEX 1777 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0132 |
Описание оборудования | ||
---|---|---|
24 V DC |
Описание оборудования | ||
---|---|---|
24 V DC |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 23+, 24- or power feed module/Power Rail | |
Rated voltage | 20 ... 30 V DC | |
Rated current | approx. 100 mA | |
Power dissipation/power consumption | &le 2 W / 2.2 W | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 6 | |
RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 | |
Types of measuring | 2-, 3-, 4-wire technology | |
Lead resistance | max. 50 &Omega | |
Measurement loop monitoring | sensor breakage, sensor short-circuit | |
Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) | |
Cold junction compensation | external and internal | |
Measurement loop monitoring | sensor breakage | |
Potentiometer | 0.8 ... 20 k&Omega | |
Types of measuring | 2-, 3-, 5-wire technology | |
Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV | |
Input resistance | &ge 250 k&Omega (0 ... 10 V) min. 1 M&Omega (0 ... 1 V, -100 ... 100 mV) | |
Measuring current | approx. 400 µA with resistance measuring sensor | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
Output I, II | relay | |
Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output III | Analog current output | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 &Omega | |
Fault signal | downscale I &le 3.6 mA, upscale I &ge 21 mA (acc. NAMUR NE43) | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Sampling rate | approx. 700 ms | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | TÜV 03 ATEX 2140 | |
Marking | ![]() ![]() | |
Certificate | PF 08 CERT 1213 X | |
Marking | ![]() | |
Output I, II | ||
Contact loading | 50 V AC/2 A/cos &phi > 0.7 40 V DC/1 A resistive load | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 23, 24 | |
Rated voltage | 20 ... 90 V DC / 48 ... 253 V AC | |
Power dissipation/power consumption | &le 2 W 2.5 VA / 2.2 W 3 VA | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 6 | |
RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 | |
Types of measuring | 2-, 3-, 4-wire technology | |
Lead resistance | max. 50 &Omega | |
Measurement loop monitoring | sensor breakage, sensor short-circuit | |
Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) | |
Cold junction compensation | external and internal | |
Measurement loop monitoring | sensor breakage | |
Potentiometer | 0.8 ... 20 k&Omega | |
Types of measuring | 2-, 3-, 5-wire technology | |
Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV | |
Input resistance | &ge 250 k&Omega (0 ... 10 V) min. 1 M&Omega (0 ... 1 V, -100 ... 100 mV) | |
Measuring current | approx. 400 µA with resistance measuring sensor | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
Output I, II | relay | |
Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output III | Analog current output | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 &Omega | |
Fault signal | downscale I &le 3.6 mA, upscale I &ge 21 mA (acc. NAMUR NE43) | |
Transfer characteristics | ||
Sampling rate | approx. 700 ms | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | TÜV 03 ATEX 2140 | |
Marking | ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Rated voltage | 12 ... 35 V DC loop powered | |
Power dissipation | 0.4 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2-, 3- thermocouple E, J, K, N, R, S or T, cold junction referenced to 0 °C (32 °F) | |
Lead resistance | max. 100 &Omega per line | |
Current | lead monitoring ON: &le 15 nA OFF: &le 1 nA | |
Output | ||
Connection side | control side | |
Connection | terminals 9+, 8- | |
Load | (U -12 V) / 0.02 A | |
Current output | 4 ... 20 mA , limited to &le 35 mA | |
Fault signal | downscaling &le 3 mA , upscaling &ge 22 mA | |
Transfer characteristics | ||
Measurement range | span 4 ... 100 mV, zero point -12 ... 60 mV , both adjustable | |
Characteristic curve | the output voltage is linearly proportionate to the input voltage (not to temperature) | |
Rise time | 250 ms | |
Indicators/settings | ||
Control elements | DIP-switch rotary switch | |
Configuration | via DIP switches via rotary switch | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Insulation coordination | EN 50178 | |
Galvanic isolation | EN 50178 | |
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | ZELM 00 ATEX 0035 | |
Marking | ![]() | |
Certificate | TÜV 01 ATEX 1777 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0132 |
Описание оборудования | ||
---|---|---|
Current output 0/4 mA ... 20 mA |
Описание оборудования | ||
---|---|---|
Current output 0/4 mA ... 20 mA |
Описание оборудования | ||
---|---|---|
Voltage output 0/1 V ... 5 V |
Описание оборудования | ||
---|---|---|
Current output 0/4 mA ... 20 mA |
Описание оборудования | ||
---|---|---|
Voltage output 0/1 V ... 5 V |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Rated voltage | loop powered | |
Power dissipation | 0.8 W | |
Input | ||
Connection side | control side | |
Connection | terminals 7, 8, 9 | |
Input current | &le 21 mA per channel | |
Output | ||
Safety note | Attention! Combination of output Ex i with output not Ex i is not permitted. If load voltage > 50 V, de-energize before removing the terminals. | |
Connection side | field side | |
Connection | terminals 1, 2, 3 4, 5, 6 | |
Contact loading | 230 V AC/2 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Energized/De-energized delay | approx. 10 ms / approx. 5 ms | |
Mechanical life | 5 x 106 switching cycles | |
Transfer characteristics | ||
Switching frequency | < 10 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | DMT 00 ATEX E 016 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 00 ATEX 1621 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0261 | |
CSA approval | ||
Control drawing | 116-0156 | |
IECEx approval | IECEx BVS 10.0025 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |