General specifications | ||
---|---|---|
Switching function | complementary | |
Output type | NPN | |
Slot width | 30 mm | |
Depth of immersion (lateral) | 27 ... 31 mm | |
Installation | ||
Output polarity | DC | |
Nominal ratings | ||
Operating voltage | 10 ... 65 V DC | |
Switching frequency | 0 ... 150 Hz | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | &le 3 V | |
Operating current | 0 ... 200 mA | |
No-load supply current | &le 20 mA | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | Connector M12 x 1 , 4-pin | |
Housing material | ABS | |
Degree of protection | IP67 |
General specifications | ||
---|---|---|
Switching function | complementary | |
Output type | PNP | |
Slot width | 30 mm | |
Depth of immersion (lateral) | 27 ... 31 mm | |
Output polarity | DC | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V DC | |
Switching frequency | 0 ... 150 Hz | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | &le 3 V | |
Operating current | 0 ... 200 mA | |
No-load supply current | &le 20 mA | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 2 m | |
Core cross-section | 0.75 mm2 | |
Housing material | ABS | |
Degree of protection | IP67 |
General specifications | ||
---|---|---|
Switching function | complementary | |
Output type | PNP | |
Slot width | 30 mm | |
Depth of immersion (lateral) | 27 ... 31 typ. | |
Installation | ||
Output polarity | DC | |
Nominal ratings | ||
Operating voltage | 10 ... 30 V | |
Switching frequency | 0 ... 150 Hz | |
Reverse polarity protection | reverse polarity protected | |
Short-circuit protection | pulsing | |
Voltage drop | &le 3 V | |
Operating current | 0 ... 200 mA | |
No-load supply current | &le 20 mA | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | Connector M12 x 1 , 4-pin | |
Housing material | ABS | |
Degree of protection | IP67 |
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Slot width | 30 mm | |
Depth of immersion (lateral) | 27 ... 30 mm | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) | |
Operating voltage | 5 ... 25 V | |
Switching frequency | 0 ... 150 Hz | |
Hysteresis | 0.1 ... 0.3 mm | |
Current consumption | ||
Measuring plate not detected | &ge 3 mA | |
Measuring plate detected | &le 1 mA | |
Functional safety related parameters | ||
MTTFd | 11060 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Approvals and certificates | ||
FM approval | ||
Control drawing | 116-0165 | |
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 2 m | |
Core cross-section | 0.75 mm2 | |
Housing material | ABS | |
Degree of protection | IP67 | |
Cable | ||
Bending radius | > 10 x cable diameter | |
Mass | 450 g | |
Equipment protection level Da | ||
Highest permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EU-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G 2G 1D |
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Slot width | 5 mm | |
Depth of immersion (lateral) | 5 ... 7 mm , typ. 6 mm | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) | |
Operating voltage | 5 ... 25 V | |
Switching frequency | 0 ... 2000 Hz | |
Hysteresis | 0.05 ... 0.65 mm | |
Current consumption | ||
Measuring plate not detected | &ge 3 mA | |
Measuring plate detected | &le 1 mA | |
Functional safety related parameters | ||
MTTFd | 9060 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
Mechanical specifications | ||
Connection type | flexible leads LiY , 500 mm | |
Core cross-section | 0.14 mm2 | |
Housing material | PBT | |
Degree of protection | IP67 | |
Equipment protection level Da | ||
Highest permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EU-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G 2G 1D |
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Slot width | 5 mm | |
Depth of immersion (lateral) | 8 ... 10 mm , typ. 9 mm | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) | |
Operating voltage | 5 ... 25 V | |
Switching frequency | 0 ... 2000 Hz | |
Hysteresis | 0.05 ... 0.3 mm | |
Current consumption | ||
Measuring plate not detected | &ge 3 mA | |
Measuring plate detected | &le 1 mA | |
Functional safety related parameters | ||
MTTFd | 4560 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Approvals and certificates | ||
FM approval | ||
Control drawing | 116-0165 | |
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 2 m | |
Core cross-section | 0.75 mm2 | |
Housing material | PBT | |
Degree of protection | IP67 | |
Cable | ||
Bending radius | > 10 x cable diameter | |
Equipment protection level Da | ||
Highest permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EU-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G 2G 1D |
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Slot width | 5 mm | |
Depth of immersion (lateral) | 8 ... 10 typ. 9 mm | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) | |
Switching frequency | 0 ... 2000 Hz | |
Current consumption | ||
Measuring plate not detected | min. 3 mA | |
Measuring plate detected | &le 1 mA | |
Functional safety related parameters | ||
MTTFd | 4560 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
Mechanical specifications | ||
Connection type | cable PVC , 6 m | |
Core cross-section | 0.75 mm2 | |
Housing material | PBT | |
Degree of protection | IP67 | |
Cable | ||
Bending radius | > 10 x cable diameter | |
Equipment protection level Da | ||
Highest permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EU-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G 2G 1D |
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Slot width | 5 mm | |
Depth of immersion (lateral) | 5 ... 7 mm , typ. 6 mm | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) | |
Operating voltage | 5 ... 25 V | |
Switching frequency | 0 ... 2000 Hz | |
Hysteresis | 0.05 ... 0.65 mm | |
Current consumption | ||
Measuring plate not detected | &ge 3 mA | |
Measuring plate detected | &le 1 mA | |
Functional safety related parameters | ||
MTTFd | 9060 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Approvals and certificates | ||
FM approval | ||
Control drawing | 116-0165 | |
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
Mechanical specifications | ||
Connection type | flexible leads LiY , 500 mm | |
Core cross-section | 0.14 mm2 | |
Housing material | PBT | |
Degree of protection | IP67 | |
Equipment protection level Da | ||
Highest permissible ambient temperature | Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EU-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained. | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G 2G 1D |
General specifications | ||
---|---|---|
Slot width | 5 mm | |
Depth of immersion (lateral) | 5 ... 7 mm , typ. 6 mm | |
Output polarity | NAMUR | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8.2 V (Ri approx. 1 k&Omega) | |
Operating voltage | 5 ... 25 V | |
Switching frequency | 0 ... 2000 Hz | |
Hysteresis | 0.05 ... 0.65 mm | |
Current consumption | ||
Measuring plate not detected | &ge 3 mA | |
Measuring plate detected | &le 1 mA | |
Functional safety related parameters | ||
MTTFd | 9060 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Approvals and certificates | ||
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -25 ... 100 °C (-13 ... 212 °F) | |
Mechanical specifications | ||
Connection type | flexible leads PTFE , 500 mm | |
Core cross-section | 0.14 mm2 | |
Housing material | PBT | |
Degree of protection | IP67 | |
Data for application in connection with hazardous areas | ||
Equipment protection level | Ga , Gb , Da , Mb | |
General information | ||
Use in the hazardous area | see instruction manuals |