General specifications | ||
---|---|---|
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 1 | |
Electrical specifications | ||
Nominal voltage | 120 V AC | |
Maximum continuous operating voltage | max. 150 V AC max. 200 V DC | |
Nominal discharge current (8/20 µs) | 15 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 50 g | |
Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
Mounting | in the surge protection barrier M-LB-*.****.* |
General specifications | ||
---|---|---|
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 1 | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 275 V AC max. 350 V DC | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 50 g | |
Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
Mounting | in the surge protection barrier M-LB-*.****.* |
General specifications | ||
---|---|---|
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 1 | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 255 V AC | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 50 g | |
Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
Mounting | in the surge protection barrier M-LB-*.****.* |
General specifications | ||
---|---|---|
Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
Number of protected supply lines | 1 | |
Electrical specifications | ||
Nominal voltage | 120 V AC | |
Maximum continuous operating voltage | max. 150 V AC/DC | |
Nominal discharge current (8/20 µs) | 2 kA | |
Max. surge current (8/20 µs) | 4 kA | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 50 g | |
Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
Mounting | in the surge protection barrier M-LB-*.****.* |
General specifications | ||
---|---|---|
Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
Number of protected supply lines | 1 | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 255 V AC/DC | |
Nominal discharge current (8/20 µs) | 3 kA | |
Max. surge current (8/20 µs) | 5 kA | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 50 g | |
Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
Mounting | in the surge protection barrier M-LB-*.****.* |
General specifications | ||
---|---|---|
Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
Number of protected supply lines | 1 | |
Electrical specifications | ||
Nominal voltage | 24 V AC | |
Maximum continuous operating voltage | max. 30 V AC/DC | |
Nominal discharge current (8/20 µs) | 1 kA | |
Max. surge current (8/20 µs) | 2 kA | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 50 g | |
Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
Mounting | in the surge protection barrier M-LB-*.****.* |
General specifications | ||
---|---|---|
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 1 | |
Suitable components | protection module M-LB-1.150.M | |
Electrical specifications | ||
Nominal voltage | 120 V AC | |
Maximum continuous operating voltage | max. 150 V AC max. 200 V DC | |
Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 15 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 240 g | |
Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 1 | |
Suitable components | protection module M-LB-1.275.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 275 V AC max. 350 V DC | |
Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 240 g | |
Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
Number of protected supply lines | 2 | |
Suitable components | protection module M-LB-2.150.T3.M | |
Electrical specifications | ||
Nominal voltage | 120 V AC | |
Maximum continuous operating voltage | max. 150 V AC/DC | |
Nominal discharge current (8/20 µs) | 2 kA | |
Max. surge current (8/20 µs) | 4 kA | |
Voltage protection level | max. 640 V (L-N) max. 800 V (L/N-PE) | |
Reaction time | max. 25 ns (L-N) max. 100 ns (L/N-PE) | |
Short-circuit-proof | 6 kA eff at max. mains-side overcurrent protection | |
Overcurrent protection | max. 25 A gL/gG (B 25 A) , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Operating conditions | ||
Installation conditions | ||
Mounting location | indoor | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 120 g | |
Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TN | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 2 | |
Suitable components | protection module M-LB-1.150.M | |
Electrical specifications | ||
Nominal voltage | 120 V AC | |
Maximum continuous operating voltage | max. 150 V AC | |
Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 15 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 240 g | |
Dimensions | 36 x 90 x 73 mm (1.4 x 3.6 x 2.9 inch) (2 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
Number of protected supply lines | 2 | |
Suitable components | protection module M-LB-2.255.T3.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 255 V AC | |
Temporary over-voltage | 335 V 335 V/5 s (TOV withstand) (L-N) 400 V/5 s (TOV withstand) (L/N-PE) 1200 V+Ucs/200 ms (TOV safe failure) (L+N-PE) 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 3 kA | |
Max. surge current (8/20 µs) | 5 kA | |
Voltage protection level | max. 1.25 kV (L-N) max. 1.5 kV (L/N-PE) | |
Reaction time | max. 25 ns (L-N) max. 100 ns (L/N-PE) | |
Short-circuit-proof | 6 kA eff at max. mains-side overcurrent protection | |
Overcurrent protection | max. 25 A gL/gG (B 25 A) , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Operating conditions | ||
Installation conditions | ||
Mounting location | indoor | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 120 g | |
Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TN | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 2 | |
Suitable components | protection module M-LB-1.275.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 275 V AC | |
Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 240 g | |
Dimensions | 36 x 90 x 73 mm (1.4 x 3.6 x 2.9 inch) (2 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TT | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 2 | |
Suitable components | protection module M-LB-1.275.M protection module M-LB-1.NPE.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 275 V AC (L-N) max. 255 V AC (N-PE) | |
Temporary over-voltage | 335 V/5 s (TOV withstand) (L-N) 1200 V/200 ms (TOV withstand) (N-PE) | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Total discharge current (8/20 µs) | 12 kA (N-PE) | |
Voltage protection level | max. 1.25 kV (L-N) max. 1 kV at 5 kA (L-N) &le 1.5 kV (N-PE) | |
Reaction time | max. 25 ns (L-N) max. 100 ns (N-PE) | |
Follow current extinguishing capability | 100 A eff (N-PE) | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 240 g | |
Dimensions | 36 x 90 x 73 mm (1.4 x 3.6 x 2.9 inch) (2 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
Number of protected supply lines | 2 | |
Suitable components | protection module M-LB-2.30.T3.M | |
Electrical specifications | ||
Nominal voltage | 24 V AC | |
Maximum continuous operating voltage | max. 30 V AC/DC | |
Nominal discharge current (8/20 µs) | 1 kA | |
Max. surge current (8/20 µs) | 2 kA | |
Voltage protection level | max. 180 V (L-N) max. 630 V (L/N-PE) | |
Reaction time | max. 25 ns (L-N) max. 100 ns (L/N-PE) | |
Short-circuit-proof | 6 kA eff at max. mains-side overcurrent protection | |
Overcurrent protection | max. 25 A gL/gG (B 25 A) , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Operating conditions | ||
Installation conditions | ||
Mounting location | indoor | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 120 g | |
Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TN-C | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 3 | |
Suitable components | protection module M-LB-1.150.M | |
Electrical specifications | ||
Nominal voltage | 120 V AC / 240 V AC | |
Maximum continuous operating voltage | max. 150 V AC | |
Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 15 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 360 g | |
Dimensions | 54 x 90 x 73 mm (2.1 x 3.6 x 2.9 inch) (3 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TN-C | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 3 | |
Suitable components | protection module M-LB-1.275.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC / 400 V AC | |
Maximum continuous operating voltage | max. 275 V AC | |
Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 360 g | |
Dimensions | 54 x 90 x 73 mm (2.1 x 3.6 x 2.9 inch) (3 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TN-S | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 4 | |
Suitable components | protection module M-LB-1.150.M | |
Electrical specifications | ||
Nominal voltage | 120 V AC / 240 V AC | |
Maximum continuous operating voltage | max. 150 V AC | |
Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 15 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 480 g | |
Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TN-S | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 4 | |
Suitable components | protection module M-LB-1.275.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC / 400 V AC | |
Maximum continuous operating voltage | max. 275 V AC | |
Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 480 g | |
Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TT | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 4 | |
Suitable components | protection module M-LB-1.275.M protection module M-LB-1.NPE.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC / 400 V AC | |
Maximum continuous operating voltage | max. 275 V AC (L-N) max. 255 V AC (N-PE) | |
Temporary over-voltage | 335 V/5 s (TOV withstand) (L-N) 1200 V/200 ms (TOV withstand) (N-PE) | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Total discharge current (8/20 µs) | 12 kA (N-PE) | |
Voltage protection level | max. 1.25 kV (L-N) max. 1 kV at 5 kA (L-N) &le 1.5 kV (N-PE) | |
Reaction time | max. 25 ns (L-N) max. 100 ns (N-PE) | |
Follow current extinguishing capability | 100 A eff (N-PE) | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 480 g | |
Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Товаров: 0
На сумму: 0