General specifications | ||
---|---|---|
Measuring method | The device is a measuring system that functions according to the time-of-flight method. The distance from the reference point (process connection of the measuring device) to the product surface is measured. | |
Construction type | device with rod probe device with rope probe | |
Supply | ||
Rated voltage | 11.5 ... 35 V DC, 2-wire 10.4 ... 48 V DC, 4-wire 90 ... 253 V AC, 50/60 Hz | |
Input | ||
Measured variable | distance between reference point and product surface | |
Measurement range | rod probe: 4 m (13 ft) rope probe: 12 m (39 ft) | |
Output | ||
Output signal | 4 ... 20 mA 2 x 4 ... 20 mA | |
Communication | 4 ... 20 mA HART (standard) PROFIBUS PA (option) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Measurement accuracy | ||
Accuracy | digital: ±2 mm (0.08 inch) analog: 0.02 % sum of non-linearity, non-repeatability and hysteresis included in the maximum measured error | |
Operating conditions | ||
Process conditions | ||
Process temperature | -20 ... 80 °C (-4 ... 176 °F) | |
Process pressure (static pressure) | -1 ... 6 bar (-14.5 ... 87 psi) | |
Dielectric constant | rod probe: DC &ge 1.6 rope probe: DC &ge 1.6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP68, NEMA 6P (24 hours in water 1.83 m (6 ft) deep) IP66, NEMA 4X | |
Connection | gland M20 thread M20, G1/2, NPT1/2 device plug M12, 7/8 in | |
Material | materials in contact with process : rod probe: 1.4404/316L rope probe: 1.4401/316 process connections: 1.4404/316L, PPS-GF40 process membran, seal: Viton | |
Process connection | threads: G3/4, MNPT3/4 flanges: universal flange | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | see instruction manuals (SI) | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-1:2007 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 60079-31:2009 | |
International approvals | ||
IECEx approval | see instruction manuals (SI) | |
Certificates and approvals | ||
Overspill protection | see approval (ZE) | |
Telecommunications | radio license FCC | |
Accessories | ||
Designation | see technical information (TI) |
General specifications | ||
---|---|---|
Measuring method | The device is a measuring system that functions according to the time-of-flight method. The distance from the reference point (process connection of the measuring device) to the product surface is measured. | |
Construction type | device with rod probe device with coax probe device with rope probe | |
Supply | ||
Rated voltage | 11.5 ... 35 V DC, 2-wire 10.4 ... 48 V DC, 4-wire 90 ... 253 V AC, 50/60 Hz | |
Input | ||
Measured variable | distance between reference point and product surface | |
Measurement range | rod probe: 4 m/10 m (13 ft/33 ft) (for divisible/indivisible rod probes) coax probe: 6 m (20 ft) rope probe: 45 m (148 ft) | |
Output | ||
Output signal | 4 ... 20 mA 2 x 4 ... 20 mA | |
Communication | 4 ... 20 mA HART (standard) PROFIBUS PA (option) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Measurement accuracy | ||
Accuracy | digital: - measuring range up to 15 m (49 feet): ±2 mm (0.08 inch) - measuring range > 15 m (49 feet): ±10 mm (0.39 inch) analog: 0.02 % sum of non-linearity, non-repeatability and hysteresis included in the maximum measured error | |
Operating conditions | ||
Process conditions | ||
Process temperature | -40 ... 200 °C (-40 ... 392 °F) | |
Process pressure (static pressure) | -1 ... 40 bar (-14.5 ... 580.2 psi) | |
Dielectric constant | rod probe: DC &ge 1.6 coax probe: DC &ge 1.4 rope probe: DC &ge 1.6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP68, NEMA 6P (24 hours in water 1.83 m (6 ft) deep) IP66, NEMA 4X | |
Connection | gland M20 thread M20, G1/2, NPT1/2 device plug M12, 7/8 in | |
Material | materials in contact with process : rod probe, coax probe: 1.4404/316L rope probe: 1.4401/316 process connections: 1.4404/316L, 2.4602/Alloy C22 process membran, seal: Viton, EPDM, Kalrez, gas-tight feed through as option | |
Process connection | threads: from 3/4 in flanges: DIN EN from DN40, ANSI from 1-1/2 in, JIS from DN40 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | see instruction manuals (SI) | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-1:2007 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 60079-31:2009 | |
International approvals | ||
IECEx approval | see instruction manuals (SI) | |
Certificates and approvals | ||
Overspill protection | see approval (ZE) | |
Telecommunications | radio license FCC | |
Accessories | ||
Designation | see technical information (TI) |
General specifications | ||
---|---|---|
Measuring method | The device is a measuring system that functions according to the time-of-flight method. The distance from the reference point (process connection of the measuring device) to the product surface is measured. | |
Construction type | device with rod probe device with rope probe | |
Supply | ||
Rated voltage | 11.5 ... 35 V DC, 2-wire 10.4 ... 48 V DC, 4-wire 90 ... 253 V AC, 50/60 Hz | |
Input | ||
Measured variable | distance between reference point and product surface | |
Measurement range | rod probe: 4 m (13 ft) rope probe: 45 m (148 ft) | |
Output | ||
Output signal | 4 ... 20 mA 2 x 4 ... 20 mA | |
Communication | 4 ... 20 mA HART (standard) PROFIBUS PA (option) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Measurement accuracy | ||
Accuracy | digital: - measuring range up to 15 m (49 feet): ±2 mm (0.08 inch) - measuring range > 15 m (49 feet): ±10 mm (0.39 inch) analog: 0.02 % sum of non-linearity, non-repeatability and hysteresis included in the maximum measured error | |
Operating conditions | ||
Process conditions | ||
Process temperature | -30 ... 150 °C (-22 ... 302 °F) | |
Process pressure (static pressure) | -1 ... 16 bar (-14.5 ... 232.1 psi) | |
Dielectric constant | rod probe: DC &ge 1.6 rope probe: DC &ge 1.6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP68, NEMA 6P (24 hours in water 1.83 m (6 ft) deep) IP66, NEMA 4X | |
Connection | gland M20 thread M20, G1/2, NPT1/2 device plug M12, 7/8 in | |
Material | materials in contact with process : rod probe: 1.4404/316L rope probe: 1.4401/316 (optional PA coated) process connections: 1.4301/304, 1.4401/316, 1.4404/316L process membran, seal: Viton, EPDM | |
Process connection | threads: G1-1/2, NPT1-1/2 flanges: DIN EN from DN40, ANSI from 1-1/2", JIS from DN40 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | see instruction manuals (SI) | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-1:2007 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 60079-31:2009 | |
International approvals | ||
IECEx approval | see instruction manuals (SI) | |
Certificates and approvals | ||
Overspill protection | see approval (ZE) | |
Telecommunications | radio license FCC | |
Accessories | ||
Designation | see technical information (TI) |