General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Rated voltage | 12 ... 35 V DC loop powered | |
Power dissipation | 0.4 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Current range | 0 ... 20 mA , load &le 50 &Omega | |
Voltage range | 0 ... 10 V , load &ge 100 k&Omega | |
Output | ||
Connection side | control side | |
Connection | terminals 9+, 8- | |
Load | (U -12 V) / 0.02 A | |
Current output | 4 ... 20 mA , limited to &le 35 mA | |
Fault signal | downscaling &le 3 mA | |
Transfer characteristics | ||
Rise time | 250 ms | |
Indicators/settings | ||
Control elements | DIP-switch potentiometer | |
Configuration | via DIP switches via potentiometer | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Insulation coordination | EN 50178 | |
Galvanic isolation | EN 50178 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | 30 ... 20 mA | |
Power dissipation | &le 800 mW including maximum power dissipation in the output | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2- 3+, 4- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I &ge 6.5 mA | |
Pulse/Pause ratio | min. 100 µs / min. 100 µs | |
Output | ||
Connection side | control side | |
Connection | terminals 5, 6 7, 8 | |
Rated voltage | 30 V DC | |
Rated current | 50 mA | |
Response time | &le 200 µs | |
Signal level | 1-signal: (external voltage) - 3 V max. for 50 mA 0-signal: blocked output (off-state current &le 10 µA) | |
Output I | signal Transistor | |
Output II | signal Transistor | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Rated voltage | 12 ... 35 V DC loop powered | |
Power dissipation | 0.4 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2-, 3+ suitable for Pt100, 2- and 3-wire connection | |
Lead resistance | max. 100 &Omega per line | |
Measuring current | approx. 1 mA | |
Output | ||
Connection side | control side | |
Connection | terminals 9+, 8- | |
Load | (U -12 V) / 0.02 A | |
Current output | 4 ... 20 mA , limited to &le 35 mA | |
Fault signal | sensor burnout: upscaling &ge 22 mA , limited to &le 35 mA | |
Transfer characteristics | ||
Measurement range | span without linearization 25 ... 800 °C (77 ... 1472 °F)/ with linearisation 25 ... 375 °C (77 ... 707 °F) zero point without linearization -200 ... 400 °C (-328 ... 752 °F)/ with linearisation -30 ... 375 °C (-22 ... 707 °F) span and zero point adjustable | |
Rise time | 250 ms | |
Indicators/settings | ||
Control elements | DIP-switch rotary switch | |
Configuration | via DIP switches via rotary switch | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Conformity | ||
Insulation coordination | EN 50178 | |
Galvanic isolation | EN 50178 | |
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Rated voltage | 12 ... 35 V DC loop powered | |
Power dissipation | 0.4 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2-, 3- thermocouples type E, J, K, N, R, S or T cold junction referenced to 0 °C (32 °F) | |
Lead resistance | max. 100 &Omega per line | |
Current | lead monitoring ON: &le 15 nA OFF: &le 1 nA | |
Output | ||
Connection side | control side | |
Connection | terminals 9+, 8- | |
Load | (U -12 V) / 0.02 A | |
Current output | 4 ... 20 mA , limited to &le 35 mA | |
Fault signal | downscaling &le 3 mA , upscaling &ge 22 mA | |
Transfer characteristics | ||
Measurement range | span 4 ... 100 mV, zero point -12 ... 60 mV , both adjustable | |
Characteristic curve | the output voltage is linearly proportionate to the input voltage (not to temperature) | |
Rise time | 250 ms | |
Indicators/settings | ||
Control elements | DIP-switch rotary switch | |
Configuration | via DIP switches via rotary switch | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Conformity | ||
Insulation coordination | EN 50178 | |
Galvanic isolation | EN 50178 | |
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Power consumption | max. 1.5 W | |
Input | ||
Connection side | field side | |
Connection | Input I: terminals 1+, 2+, 3- Input II: terminals 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | not available | |
Control input | sensor power supply approx. 8.2 V, impedance 1.2 k&Omega | |
Pulse duration | > 200 µs for standstill monitoring, > 250 µs for rotation direction detecion | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Trip value | for standstill monitoring: 0.1 Hz 0.5 Hz 2 Hz 10 Hz adjustable via DIP switch (S1 and S2) | |
Transfer characteristics | ||
Accuracy | 5 % (S3 = I), 30 % (S3 = II) | |
Start-up override | 5 seconds or 20 seconds, programmable | |
Frequency range | &le 2 kHz | |
Rotation direction detection | 90° phase difference between pulse input signal 1 and 2, overlapping &ge 125 µs | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Rated voltage | loop powered | |
Power dissipation | < 1.5 W | |
Power consumption | < 1.5 W | |
Input | ||
Connection side | control side | |
Connection | Input terminals 7, 8 test input terminals 10, 11, 12 | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Signal level | 0-signal: -3 ... 3 V DC 1-signal: 20 ... 26.5 V | |
Rated current | 45 ... 50 mA | |
Output | ||
Connection side | field side | |
Connection | output I (ETS): terminals 2, 3 output II (DTS): terminals 4, 5, 6 output I and II (DPS): terminals 2, 3, 4, 5, 6 | |
Contact loading | 253 V AC/5 A/cos &phi 0.7 30 V DC/5 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 10 ms / approx. 5 ms | |
Mechanical life | 5 x 106 switching cycles | |
Transfer characteristics | ||
Switching frequency | < 10 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 15 CERT 3844 X | |
Marking | II 3G Ex nA nC IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013, EN 60079-15:2010 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | terminals 14, 15 | |
Rated voltage | 20 ... 48 V DC or 90 ... 253 V AC , 45 ... 65 Hz | |
Rated current | &le 230 mA | |
Power dissipation | 2.3 W | |
Power consumption | max. 4.5 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2, 3- | |
Rated values | 22 ... 24 V DC / 100 mA , see additional information | |
Short-circuit current | max. 125 mA | |
Switching point | PNP: 0-signal: < 12.5 V 1-signal: > 13.5 V NPN and push-pull output: 0-signal: < 4.5 V 1-signal: > 5.5 V | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Output I, II | signal, relay | |
Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 125 V AC/4 A/ cos &phi > 0.7 40 V DC / 2 A | |
Mechanical life | 20 x 106 switching cycles | |
Electrical life | 0.2 x 106 switching cycles (40 V DC, 2 A, ohmic) 0.4 x 106 switching cycles (253 V AC, 2 A, cos &phi = 1) 0.25 x 106 switching cycles (253 V AC, 2 A, cos &phi = 0.7) | |
Minimum load | 50 mW, 5 V DC | |
Energized/De-energized delay | &le 90 ms / &le 90 ms | |
Transfer characteristics | ||
Switching frequency | &le 5 Hz for delay 0 s adjustable energized/de-energized delay: 0 ... 79 s | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 166 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 10 CERT 1417 X | |
Marking | II 3G Ex nA nC IIC T4 Gc | |
Output I, II | ||
Contact loading | 50 V AC/2 A/cos &phi > 0.7 40 V DC/1 A resistive load | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Rated voltage | loop powered | |
Power dissipation | < 1.5 W | |
Power consumption | < 1.5 W | |
Input | ||
Connection side | control side | |
Connection | terminals 7, 8 | |
Pulse/Pause ratio | min. 35 ms / min. 35 ms | |
Signal level | 0-signal: 0 ... 5 V DC 1-signal: 20 ... 30 V | |
Rated current | approx. 58 mA | |
Output | ||
Connection side | field side | |
Connection | terminals 2, 3 | |
Contact loading | 230 V AC/2 A/cos &phi 0.7 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | 5 ... 15 ms / 5 ... 10 ms | |
Mechanical life | 5 x 106 switching cycles | |
Electrical life | 2 x 105 switching cycles , at maximium load | |
Transfer characteristics | ||
Switching frequency | < 10 Hz | |
Indicators/settings | ||
Display elements | LED | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | terminals 14, 15 | |
Rated voltage | 19 ... 90 V DC / 48 ... 253 V AC | |
Rated current | &le 110 mA DC / &le 75 mA AC | |
Power dissipation | 1.3 W | |
Power consumption | 2.1 W | |
Input | ||
Connection side | field side | |
Input I | ||
Input signal | 0/4 ... 20 mA | |
Rated current | 22 mA | |
Available voltage | > 15 V at 20 mA , terminals 1+, 3- | |
Open circuit voltage/short-circuit current | 21 V / 26 mA , terminals 1+, 3- terminals 1+, 2- not short-circuit protected | |
Input resistance | < 55 &Omega , terminals 2-, 3+ | |
Input II | ||
Input signal | 0/2 ... 10 V | |
Input resistance | > 1 M&Omega | |
Output | ||
Connection side | control side | |
Output I | current output | |
Connection | source: terminals 7(-), 8(+) sink: terminals 7(+), 9(-) | |
Output signal | 0/4 ... 20 mA | |
Source | load 0 ... 750 &Omega open circuit voltage < 21 V | |
Sink | voltage across terminals 5 ... 30 V | |
Output II | voltage output | |
Connection | terminals 10-, 11+ | |
Output signal | 0/2 ... 10 V | |
Load | min. 10 k&Omega | |
Transfer characteristics | ||
Reaction time | 150 ms | |
Indicators/settings | ||
Display elements | LED | |
Control elements | DIP-switch rotary switch | |
Configuration | via DIP switches via rotary switch | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Low voltage | ||
Directive 2006/95/EC | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Описание оборудования | ||
---|---|---|
2-channel |
General specifications | ||
---|---|---|
Signal type | Analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 30 mA | |
Power dissipation | &le 600 mW | |
Power consumption | &le 700 mW | |
Input | ||
Connection side | control side | |
Connection | terminals 5-, 6+ | |
Input signal | 4 ... 20 mA limited to approx. 30 mA | |
Voltage drop | depending on switch configuration open loop voltage of the control system < 23 V: approx. 6 V at 20 mA open loop voltage of the control system < 27 V: approx. 10 V at 20 mA | |
Input resistance | > 100 k&Omega, with field wiring open | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Current | 4 ... 20 mA | |
Load | 0 ... 650 &Omega | |
Voltage | &ge 13 V at 20 mA | |
Ripple | 20 mV rms | |
Transfer characteristics | ||
Accuracy | 0.1 % | |
Deviation | at 20 °C (68 °F), 0/4 ... 20 mA &le ± 0.1 % incl. non-linearity and hysteresis | |
Frequency range | bandwidth at 0.5 Vss signal 0 ... 3 kHz (-3 dB) | |
Rise time | 10 to 90 % &le 100 ms | |
Indicators/settings | ||
Display elements | LED | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Описание оборудования | ||
---|---|---|
24 V DC |
General specifications | ||
---|---|---|
Signal type | Analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 0.8 W at 20 mA into 10 V (equivalent to 500 &Omega) load | |
Power consumption | 1 W at 20 mA | |
Input | ||
Connection side | control side | |
Connection | terminals 7-, 8+, (9+) | |
Voltage drop | approx. 4 V or internal resistance 200 &Omega at 20 mA | |
Input resistance | > 100 k&Omega, when wiring resistance in the field > 16 V (equivalent to 800 &Omega at 20 mA) | |
Current | 4 ... 20 mA limited to approx. 25 mA | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Current | 4 ... 20 mA | |
Load | 100 ... 700 &Omega | |
Voltage | &ge 14 V at 20 mA | |
Transfer characteristics | ||
Accuracy | 0.05 % | |
Rise time | < 100 µs , 10 ... 90 % step change | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Описание оборудования | ||
---|---|---|
Current output 0/4 mA ... 20 mA |
Описание оборудования | ||
---|---|---|
Current output 0/4 mA ... 20 mA |
Описание оборудования | ||
---|---|---|
Input 0/4 mA ... 20 mA Output 0/4 mA ... 20 mA |
Описание оборудования | ||
---|---|---|
Input 4 mA ... 20 mA Output 4 mA ... 20 mA |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | terminals 14+, 15- or Power Rail | |
Rated voltage | 20 ... 30 V DC | |
Rated current | &le 80 mA DC | |
Power consumption | &le 1.6 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 3- : mV, V terminals 2+, 3- : mA | |
Input resistance | voltage: 1 M&Omega , current: max. 100 &Omega | |
Limit | 30 V | |
Current | 0 ... 20 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 7-, 8+, 9- | |
Output I | signal, relay | |
Contact loading | 250 V AC/2 A/cos &phi 0.7 40 V DC/2 A | |
Mechanical life | 2 x 107 switching cycles | |
Energized/De-energized delay | approx. 10 ms / approx. 10 ms | |
Output II | analog | |
Load | current: max. 550 &Omega , voltage: min. 1 k&Omega | |
Transfer characteristics | ||
Deviation | 0.1 % of full-scale value | |
Reaction time | &ge 150 ms/&le 300 ms | |
Indicators/settings | ||
Display elements | display | |
Control elements | Control panel | |
Configuration | via operating buttons | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Low voltage | ||
Directive 2006/95/EC | EN 50178:1997 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Описание оборудования | ||
---|---|---|
Input 0/4 mA ... 20 mA Output 0/4 mA ... 20 mA |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | terminals 14, 15 | |
Rated voltage | 20 ... 90 V DC / 48 ... 253 V AC | |
Rated current | &le 80 mA DC / &le 45 mA AC | |
Power consumption | &le 1.6 W / &le 2.6 VA | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 3- : mV, V terminals 2+, 3- : mA | |
Input resistance | voltage: 1 M&Omega , current: max. 100 &Omega | |
Limit | 30 V | |
Current | 0 ... 20 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 7-, 8+, 9- | |
Output I | signal, relay | |
Contact loading | 250 V AC/2 A/cos &phi 0.7 40 V DC/2 A | |
Mechanical life | 2 x 107 switching cycles | |
Energized/De-energized delay | approx. 10 ms / approx. 10 ms | |
Output II | analog | |
Load | current: max. 550 &Omega , voltage: min. 1 k&Omega | |
Transfer characteristics | ||
Deviation | 0.1 % of full-scale value | |
Reaction time | &ge 150 ms/&le 300 ms | |
Indicators/settings | ||
Display elements | display | |
Control elements | Control panel | |
Configuration | via operating buttons | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Low voltage | ||
Directive 2006/95/EC | EN 50178:1997 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Описание оборудования | ||
---|---|---|
48 V AC ... 253 V AC/20 V DC ... 90 V DC |
Описание оборудования | ||
---|---|---|
Input 0/4 mA ... 20 mA Output 0/4 mA ... 20 mA |
Описание оборудования | ||
---|---|---|
Input 0/4 mA ... 20 mA 2 x Output 0/4 mA ... 20 mA (current sink) |
Описание оборудования | ||
---|---|---|
Input 0/4 mA ... 20 mA 2 x Output 0/4 mA ... 20 mA |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 0.8 W | |
Power consumption | 0.8 W | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 5, 6 | |
Thermocouples | type B, E, J, K, N, R, S, T (IEC 584-1: 1995) type L (DIN 43710: 1985) | |
Voltage | 0 ... 10 V , 2 ... 10 V | |
Current | 0 ... 20 mA , 4 ... 20 mA | |
Load | 20 &Omega for 20 mA 200 k&Omega for 10 V | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Output I, II | relay | |
Contact loading | 253 V AC/2 A/500 VA/cos &phi min. 0.7 40 V DC/2 A resistive load | |
Mechanical life | 2 x 107 switching cycles | |
Transfer characteristics | ||
Resolution | temperature: 0.0625 °C, resistance: 62.5 m&Omega, voltage: 62.5 µV, current: 625 nA | |
Influence of supply voltage | < 0.001 % of sensor input range | |
Input delay | &le 370 ms (rise time and energizing delay of relay) | |
Indicators/settings | ||
Display elements | LEDs | |
Configuration | via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 20 ... 30 V DC | |
Rated current | approx. 130 mA | |
Power dissipation | 2 W | |
Power consumption | 2.5 W | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3 | |
Input I | ||
Input signal | 0/4 ... 20 mA | |
Available voltage | &ge 15 V at 20 mA | |
Open circuit voltage/short-circuit current | 24 V / 33 mA | |
Input resistance | 45 &Omega (terminals 2, 3) | |
Line fault detection | breakage I < 0.2 mA short-circuit I > 22 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 Output: analog terminals 8+, 7- | |
Output signal | 0 ... 20 mA or 4 ... 20 mA | |
Output I, II | signal, relay | |
Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 V DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Output III | Signal, analog | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 &Omega | |
Fault signal | downscale I &le 3.6 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
International approvals | ||
UL approval | E223772 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 23, 24 | |
Rated voltage | 20 ... 90 V DC or 48 ... 253 V AC | |
Power dissipation | 2 W / 3 VA | |
Power consumption | 2.2 W / 4 VA | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3 | |
Input I | ||
Input signal | 0/4 ... 20 mA | |
Available voltage | > 15 V at 20 mA | |
Open circuit voltage/short-circuit current | 24 V / 33 mA | |
Input resistance | 45 &Omega (terminals 2, 3) | |
Line fault detection | breakage I < 0.2 mA short-circuit I > 22 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 Output: analog terminals 8+, 7- | |
Output signal | 0 ... 20 mA or 4 ... 20 mA | |
Output I, II | signal, relay | |
Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 V DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Output III | Signal, analog | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 &Omega | |
Fault signal | downscale I &le 3.6 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 1.4 W at 20 mA into 10 V (equivalent to 500 &Omega) load | |
Power consumption | 1.8 W at 20 mA | |
Input | ||
Connection side | control side | |
Connection | terminals 7-, 8+, (9+) 10-, 11+, (12+) | |
Voltage drop | approx. 4 V or internal resistance 200 &Omega at 20 mA | |
Input resistance | > 100 k&Omega, when wiring resistance in the field > 16 V (equivalent to 800 &Omega at 20 mA) | |
Current | 4 ... 20 mA limited to approx. 25 mA | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- 4+, 5- | |
Current | 4 ... 20 mA | |
Load | 100 ... 700 &Omega | |
Voltage | &ge 14 V at 20 mA | |
Transfer characteristics | ||
Accuracy | 0.05 % | |
Rise time | < 100 µs , 10 ... 90 % step change | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |