Mechanical specifications | ||
---|---|---|
Material | copper Cu3/10 |
Mechanical specifications | ||
---|---|---|
Material | cardboard | |
Dimensions | 25 pieces, perforated, labeling field 29 x 8 mm (1.14 x 0.3 inch) |
Hazardous area connection | ||
---|---|---|
Connection | terminals 1, 2, 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6, 7, 8 | |
Indicators/settings | ||
Labeling | space for labeling at the front | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Mechanical specifications | ||
---|---|---|
Dimensions | 12.5 x 91.5 x 13 mm (0.49 x 3.6 x 0.51 inch) | |
Mounting | DIN rail mounting |
Mechanical specifications | ||
---|---|---|
Construction type | spacing 12.5 mm (0.49 inch) |
Mechanical specifications | ||
---|---|---|
Construction type | protective conductor terminal block 0.2 ... 4 mm2 |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 48.5 &Omega | |
Series resistance | max. 50 &Omega | |
Fuse rating | 100 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 5 V | |
Measurement loop | max. 3 V at 10 µA (1 V at 1 µA) | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 2009 &Omega | |
Series resistance | max. 2030.5 &Omega | |
Fuse rating | 80 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 7.5 V | |
Measurement loop | max. 7 V at 10 µA (6 V at 1 µA) | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 206.5 &Omega | |
Series resistance | max. 209.5 &Omega | |
Fuse rating | 100 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 5 V | |
Measurement loop | max. 3 V at 10 µA (1 V at 1 µA) | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)G [Ex ia Ga] IIC, II (1)D [Ex ia Da] IIIC, I (M1) [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 10 &Omega | |
Series resistance | max. 18.18 &Omega | |
Fuse rating | 250 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 4.3 V | |
Measurement loop | max. 0.9 V at 1 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 50 &Omega | |
Series resistance | max. 56 &Omega | |
Fuse rating | 100 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 8.5 V | |
Measurement loop | max. 6.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 22 &Omega | |
Series resistance | max. 29 &Omega | |
Fuse rating | 160 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 14.1 V | |
Measurement loop | max. 13.7 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 100 &Omega | |
Series resistance | max. 107 &Omega | |
Fuse rating | 100 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 13.3 V | |
Measurement loop | max. 13 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 1 k&Omega | |
Series resistance | max. 1025 &Omega | |
Fuse rating | 100 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 13.3 V | |
Measurement loop | max. 13 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 100 &Omega | |
Series resistance | max. 121 &Omega | |
Fuse rating | 63 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 13.3 V | |
Measurement loop | max. 13 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7096 | |
Marking | II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA II T4 [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0355 (cULus) | |
CSA approval | ||
Control drawing | 116-0119 |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 150 &Omega | |
Series resistance | max. 166 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 19.5 V | |
Measurement loop | max. 19 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 300 &Omega | |
Series resistance | max. 327 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 26.9 V | |
Measurement loop | max. 26.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 300 &Omega | |
Series resistance | max. 342 &Omega +2 V | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Current limit | 45 mA | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 26.9 V | |
Measurement loop | max. 26.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 300 &Omega | |
Series resistance | max. 341 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 26.9 V | |
Measurement loop | max. 26.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7096 | |
Marking | II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA II T4 [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0355 (cULus) | |
CSA approval | ||
Control drawing | 116-0119 |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 240 &Omega | |
Series resistance | max. 250 &Omega | |
Fuse rating | 80 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 26.9 V | |
Measurement loop | max. 26.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 240 &Omega | |
Series resistance | max. 273 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 26.9 V | |
Measurement loop | max. 26.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7096 | |
Marking | II (1)GD, I (M1) [Ex ia] IIC, [Ex iaD], [Ex ia] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA II T4 [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0355 (cULus) | |
CSA approval | ||
Control drawing | 116-0119 |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 10 &Omega | |
Series resistance | max. 18.18 &Omega | |
Fuse rating | 250 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 4.4 V | |
Measurement loop | max. 0.9 V at 1 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 10 &Omega | |
Series resistance | max. 15.5 &Omega | |
Fuse rating | 200 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 6.4 V | |
Measurement loop | max. 6 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 1000 &Omega | |
Series resistance | max. 1033 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 10.4 V | |
Measurement loop | max. 10 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | DC version, positive polarity | |
Electrical specifications | ||
Nominal resistance | 100 &Omega | |
Series resistance | max. 107 &Omega | |
Fuse rating | 100 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 13.3 V | |
Measurement loop | max. 13 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | II (1)GD, I (M1) [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I (-20 °C &le Tamb &le 60 °C) [circuit(s) in zone 0/1/2] | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | II 3G Ex nA IIC T4 Gc [device in zone 2] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |