Functional safety related parameters | ||
---|---|---|
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | terminals 17+, 18- | |
Rated voltage | 20 ... 32 V DC typical at 100 mA | |
Power consumption | max. 3 W | |
HART signal channels (non-intrinsically safe) | ||
Conformity | HART field device input (revision 5 to 7) | |
Connection | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 | |
Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
Terminating resistor | external 230 ... 500 &Omega standard (up to 1000 &Omega possible) | |
Output voltage | &ge 400 mV ss (with the terminator resistance specified above) | |
Output resistance | 100 &Omega or smaller, capacitive coupling | |
Input impedance | according to HART specification | |
Input voltage range | 0.08 ... 4 V ss typ. ± 5.2 V as local reference | |
Interface | ||
Transfer rate | 9600, 19200, or 38400 Bit/s (selectable with DIL switch (2 and 3) by the user) | |
Type | RS-485 , 2-wire multidrop | |
Address selection | One of 31 possible addresses selectable per DIL switch (4 ... 8) | |
Indicators/settings | ||
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | approx. 250 g | |
Dimensions | 40 x 107 x 115 mm (1.6 x 4.2 x 4.5 inch) , housing type C1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 07 CERT 1143 X | |
Marking | II 3G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
Functional safety related parameters | ||
---|---|---|
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | via 14-channel flat cable form master KFD2-HMM-16 | |
HART signal channels (non-intrinsically safe) | ||
Conformity | HART field device input (revision 5 to 7) | |
Connection | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 | |
Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
Terminating resistor | external 230 ... 500 &Omega standard (up to 1000 &Omega possible) | |
Output voltage | &ge 400 mV ss (with the terminator resistance specified above) | |
Output resistance | 100 &Omega or smaller, capacitive coupling | |
Input impedance | according to HART specification | |
Input voltage range | 0.08 ... 4 V ss typ. ± 5.2 V as local reference | |
Indicators/settings | ||
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | approx. 100 g | |
Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 07 CERT 1143 X | |
Marking | II 3G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |