General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 50 mA | |
Power dissipation | 1 W | |
Power consumption | < 1.3 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Output I, II | signal, relay | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Transfer characteristics | ||
Switching frequency | &le 10 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2080 | |
Marking | ![]() ![]() ![]() | |
Fault indication output | ||
Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) | |
Certificate | PF 08 CERT 0803 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1493 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 11.0034 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Производитель | Pepperl+Fuchs |
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках Дискретный вход Switch Amplifier KFD2-SR2-Ex2.W Pepperl+Fuchs.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цена Дискретный вход Switch Amplifier KFD2-SR2-Ex2.W Pepperl+Fuchs на сайте имеет информационный характер и может отличаться от цены в коммерческом предложении.
Основная валюта на сайте указана в долларах. Счета выставляются в рублях по курсу ЦБ РФ +3% на дату выставления счета.
Минимальный счет на запчасти (без учета доставки):
Наличие и срок поставки запчастей уточняйте у Вашего менеджера. Если Ваш заказ получается меньше суммы минимального счета, то цена на запчасти может быть увеличена. Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Условия платежа - 100% предоплата, если иное не оговорено в договоре.
Как купить Дискретный вход Switch Amplifier KFD2-SR2-Ex2.W Pepperl+Fuchs?
Мы выставляем счёт на вашу организацию и отправляем его по электронной почте. Если вы в первый раз покупаете через нашу компанию, то присылайте реквизиты на почту info@zipstore.ru. Как только мы увидим деньги на нашем расчетном счете и подготовим груз к отправке - мы с Вами свяжемся по электронной почте, на которую выставлен счет.
Перед получением товара, убедитесь в его готовности к отгрузке у Вашего менеджера.
1) Самовывоз из Москвы
Необходимо заранее согласовать время получение товара с менеджером и иметь при себе доверенность от организации установленного образца или круглую печать.
Склад находится по адресу: 127282, г. Москва, ул. Полярная, д. 33, стр. 3, 2-ой этаж, помещение 3
Чтобы не заблудиться, можете распечатать схему проезда.
2) Доставка транспортной компанией
Товары отгружаются покупателю в течение недели после поступления денежных средств на расчетный счет Продавца, если иное не оговорено в счете. Мы бесплатно доставляем Ваш заказ до транспортной компании "Деловые Линии" в г. Москве при заказе от 50 000 рублей за запчасти. Услуги межтерминальной перевозки Вы оплачиваете самостоятельно при получении груза. Найти ближайший к Вам терминал "Деловых линий" для выдачи посылок можно здесь.
3) Самовывоз из 118 пунктов выдачи в других городах России
Оплата за доставку при получении. Найдите ближайший терминал выдачи посылок на карте.
4) Доставка по Москве
Минимальная стоимость доставки курьером по г. Москве составляет 600 рублей.
В нашей компании Вы можете выбрать удобный для Вас способ доставки Дискретный вход Switch Amplifier KFD2-SR2-Ex2.W Pepperl+Fuchs:
1) Организация доставки силами Zipstore.ru
Мы самостоятельно вызываем для Вас ТК "Деловые Линии". Груз передается водителю или курьеру ТК, при наличии у него транспортной накладной на товар. Для заказа транспортной компании нашими силами, Вам необходимо написать письмо на электронную почту Вашего менеджера, в котором указать:
2) Организация доставки Вашими силами
Через любую Транспортную компанию (далее ТК), которую Вы вызываете к нам своими силами. Груз передается водителю или курьеру ТК, при наличии у него транспортной накладной на товар.
3) Отправка через ЕМS почту силами Zipstore.ru
Если Вы выбрали этот вариант, то стоимость услуги за перевозку включается в счет за товар, так как оплата курьеру ЕМS почты осуществляется наличными и только при отправке груза. Таким образом, в дальнейшем Вам не придется оплачивать отдельные счета ТК.
Для заказа EMS нашими силами, Вам необходимо написать письмо на электронную почту Вашего менеджера, в котором указать:
1. Качество Оборудования должно соответствовать техническим характеристикам, изложенным в инструкции по эксплуатации Оборудования.
2. Продавец гарантирует отсутствие производственных дефектов в поставленном Оборудовании в течение гарантийного периода.
3. Гарантийный период на Оборудование составляет 12 месяцев, на оригинальные запасные части 3 месяца, на аналоги 1 месяц, если иное не предусмотрено Спецификацией.
4. Претензии к внешнему виду товара принимаются в течение 2-х недель, с момента отгрузки товара.
5. Гарантия не распространяется на запчасти для технологического и ресторанного оборудования, интерфейсы (последовательного и Ethernet), материнские платы Godex, расходные материалы.
6. Если в течение гарантийного периода (п.3) Оборудование или его часть, указанные в Счете, окажутся дефектными, Продавец обязуется произвести ремонт или замену Оборудования или его части без оплаты Покупателем при соблюдении следующих условий:
6.1. Диагностика неисправности была проведена авторизованными специалистами производителя оборудования.
6.2. Покупатель письменно извещает Продавца об обнаруженных дефектах с их подробным описанием. Рекламация подписывается авторизованным специалистом.
6.3. Если дефекты не вызваны существенными нарушениями технических требований, оговоренных в инструкции по эксплуатации (в том числе нестабильностью параметров питающей электрической сети и отсутствием или ненадлежащим выполнением заземления Оборудования).
6.4. Если дефекты не вызваны вскрытием, ремонтом, модификацией или неправильным запуском Оборудования.
6.5. Если дефекты не вызваны повреждением вследствие действия на нее других неисправных частей.
6.6. Если отсутствуют видимые механические повреждения, в т.ч. сколы и царапины на нагревательной поверхности печатающих термоголовок (см. документ "Гарантийные обязательства на печатающие термоголовки").
6.7. Если дефекты не вызваны пожаром или затоплением помещения и не являются следствием неправильной эксплуатации Оборудования.
6.8. Если Специалистами Покупателя регулярно проводилось обслуживание Оборудования согласно инструкции по эксплуатации.
6.9. Если регулировка и настройка Оборудования проводилась Покупателем согласно инструкции по эксплуатации.
6.10. Если дефект не является следствием нормального износа быстроизнашивающихся деталей.
6.11. Если применялись расходные материалы, одобренные производителем.
6.12. Если оплата за товар произведена полностью.
7. При несоблюдении Покупателем условий, указанных в пп. 6.1.-6.12. , гарантия истекает немедленно.
8. Доставка гарантийного Оборудования производится силами и за счет Покупателя.
9. При невозможности замены бракованных Запчастей, неисправного Оборудования или неисправных частей Оборудования, возврат денежных средств производится в течении 14 рабочих дней, с момента заключения специалистами Продавца и оформления письма о возврате денежных средств Покупателем.
10. В случаях обнаружения брака (товара ненадлежащего качества) сразу необходимо упаковать товар, не пользоваться им, в течение ближайшего времени связаться с нами. Отправка товара ненадлежащего качества должна быть произведена в течении 5 дней с момента подтверждения брака Продавцом.
11. Возврат или обмен товара надлежащего качества остается на усмотрение Продавца, если иное не предусмотрено договором поставки (Закон о Защите Прав Потребителей не распространяется на взаимоотношения юридических лиц).
12. Должны быть сохранены упаковка товара (в чистом виде), товарный вид, потребительские свойства, пломбы, фабричные ярлыки, а также все полученные от продавца документы (чеки, бухгалтерские документы, инструкция по эксплуатации).
13. Денежные средства возвращаются тем же способом, которым был оплачен заказ.
14. Запчасти и расходные материалы для торгового, складского ресторанного и технологического оборудования не подлежат сертификации, по этой причине отказные письма не выдаются.
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
В случае возникновения вопросов, касающихся свойств и характеристик товара, перед оформлением счета обратитесь к нашим сотрудникам. Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | 20 ... 15 mA | |
Power dissipation | &le 1 W including maximum power dissipation in the output | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I &ge 6.5 mA | |
Pulse/Pause ratio | min. 100 µs / min. 100 µs | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 8, 9 | |
Rated voltage | 30 V DC | |
Rated current | 100 mA , short-circuit protected | |
Response time | &le 200 µs | |
Signal level | 1-signal: (external voltage) - 3 V max. for 100 mA 0-signal: blocked output (off-state current &le 10 µA) | |
Output I | signal Transistor | |
Output II | signal or error message Transistor | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 16 ATEX 0016 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 16.0009X | |
Approved for | Ex nA [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I | |
Accessories | ||
Optional accessories | power feed module KFD2-EB2 Universal Power Rail UPR-03 Universal Power Rail UPR-03-S profile rail K-DUCT-BU profile rail K-DUCT-UPR-03 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 50 mA | |
Power dissipation | 1 W | |
Power consumption | < 1.3 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 8, 9 output III: terminals 10, 11 output IV: terminals 11, 12 | |
Output I, II, III, IV | channel 1, 2 relay | |
Contact loading | 50 V AC/1 A/cos &phi > 0.7 40 V DC/1 A resistive load | |
Minimum switch current | 1 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 108 switching cycles | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 10 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2004 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2083 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1493 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
CSA approval | ||
Control drawing | 116-0047 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | 30 ... 20 mA | |
Power dissipation | &le 1.1 W including maximum power dissipation in the output | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I &ge 6.5 mA | |
Pulse/Pause ratio | min. 100 µs / min. 100 µs | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 8, 9 | |
Rated voltage | 30 V DC | |
Rated current | 100 mA , short-circuit protected | |
Response time | &le 200 µs | |
Signal level | 1-signal: (external voltage) - 3 V max. for 100 mA 0-signal: blocked output (off-state current &le 10 µA) | |
Output I | signal Transistor | |
Output II | signal Transistor | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 16 ATEX 0016 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 16.0009X | |
Approved for | Ex nA [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I | |
Accessories | ||
Optional accessories | power feed module KFD2-EB2 Universal Power Rail UPR-03 Universal Power Rail UPR-03-S profile rail K-DUCT-BU profile rail K-DUCT-UPR-03 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 14, 15 | |
Rated voltage | 207 ... 253 V AC, 45 ... 65 Hz | |
Power dissipation | 1 W | |
Power consumption | max. 1.5 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 8, 9 | |
Signal level | 1-signal: switching voltage - 2.5 V max. at 10 mA switching current or 3 V max. at 100 mA switching current 0-signal: switched off (off-state current &le 10 µA) | |
Output I, II | signal electronic output, passive | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 98 ATEX 2164 | |
Marking | ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
International approvals | ||
UL approval | ||
Control drawing | 116-0145 | |
CSA approval | ||
Control drawing | 116-0047 |
Описание оборудования | ||
---|---|---|
100 V AC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | 35 ... 25 mA | |
Power dissipation | &le 750 mW | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2- 3+, 4- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I &ge 6.5 mA | |
Pulse/Pause ratio | min. 100 µs / min. 100 µs | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 5, 6 output II: terminals 7, 8 | |
Rated voltage | typ. 8 V max. 20 V DC | |
Response time | &le 200 µs | |
Output I, II | signal or error message, passive transistor output (resistive) 0-signal: 14 k&Omega ± 10 % 1-signal: 1.8 k&Omega ± 10 % fault: > 100 k&Omega | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BASEEFA 13 ATEX 0080 | |
Marking | ![]() ![]() ![]() | |
Certificate | PF 13 CERT 2760 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
UL approval | ||
Control drawing | 116-0374 (cULus) | |
IECEx approval | IECEx BAS 13.0046 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Описание оборудования | ||
---|---|---|
230 V AC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 14, 15 | |
Rated voltage | 103.5 ... 126.5 V AC , 45 ... 65 Hz | |
Power dissipation | 1 W | |
Power consumption | max. 1.5 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 8, 9 | |
Signal level | 1-signal: switching voltage - 2.5 V max. at 10 mA switching current or 3 V max. at 100 mA switching current 0-signal: switched off (off-state current &le 10 µA) | |
Output I, II | signal electronic output, passive | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 98 ATEX 2164 | |
Marking | ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
International approvals | ||
UL approval | ||
Control drawing | 116-0145 | |
CSA approval | ||
Control drawing | 116-0047 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 14, 15 | |
Rated voltage | 207 ... 253 V AC, 45 ... 65 Hz | |
Power dissipation | 1.2 W | |
Power consumption | max. 1.3 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Output I | signal relay | |
Output II | signal or error message relay | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Transfer characteristics | ||
Switching frequency | &le 10 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2081 | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
UL approval | ||
Control drawing | 116-0145 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 11.0031 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Описание оборудования | ||
---|---|---|
24 V DC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 14, 15 | |
Rated voltage | 103.5 ... 126 V AC , 45 ... 65 Hz | |
Power dissipation | 1.2 W | |
Power consumption | max. 1.3 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Output I, II | signal relay | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Transfer characteristics | ||
Switching frequency | &le 10 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2081 | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
UL approval | ||
Control drawing | 116-0145 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 11.0031 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | 30 ... 20 mA | |
Power dissipation | &le 800 mW including maximum power dissipation in the output | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2- 3+, 4- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I &ge 6.5 mA | |
Pulse/Pause ratio | min. 100 µs / min. 100 µs | |
Output | ||
Connection side | control side | |
Connection | terminals 5, 6 7, 8 | |
Rated voltage | 30 V DC | |
Rated current | 50 mA | |
Response time | &le 200 µs | |
Signal level | 1-signal: (external voltage) - 3 V max. for 50 mA 0-signal: blocked output (off-state current &le 10 µA) | |
Output I | signal Transistor | |
Output II | signal Transistor | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | spring terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BASEEFA 13 ATEX 0080 | |
Marking | ![]() ![]() ![]() | |
Certificate | PF 13 CERT 2760 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
UL approval | ||
Control drawing | 116-0374 (cULus) | |
IECEx approval | IECEx BAS 13.0046 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Switching function | Normally closed (NC) | |
Output type | NAMUR | |
Rated operating distance | 5 mm | |
Installation | flush | |
Assured operating distance | 0 ... 4.05 mm | |
Reduction factor rAl | 0.4 | |
Reduction factor rCu | 0.3 | |
Reduction factor r304 | 0.85 | |
Output type | 2-wire | |
Nominal ratings | ||
Nominal voltage | 8 V | |
Switching frequency | 0 ... 500 Hz | |
Current consumption | ||
Measuring plate not detected | min. 3 mA | |
Measuring plate detected | &le 1 mA | |
Functional safety related parameters | ||
MTTFd | 4542 a | |
Mission Time (TM) | 20 a | |
Diagnostic Coverage (DC) | 0 % | |
Compliance with standards and directives | ||
Standard conformity | ||
NAMUR | EN 60947-5-6:2000 IEC 60947-5-6:1999 | |
Approvals and certificates | ||
UL approval | cULus Listed, General Purpose | |
CSA approval | cCSAus Listed, General Purpose | |
CCC approval | CCC approval / marking not required for products rated &le36 V | |
Ambient conditions | ||
Ambient temperature | -40 ... 150 °C (-40 ... 302 °F) | |
Mechanical specifications | ||
Connection type | cable SIHF , 15 m | |
Core cross-section | 0.34 mm2 | |
Housing material | PPS | |
Sensing face | PPS | |
Degree of protection | IP65 | |
Cable | ||
Bending radius | > 10 x cable diameter | |
General information | ||
Use in the hazardous area | see instruction manuals | |
Category | 1G 2G |
Описание оборудования | ||
---|---|---|
Input 0/4 mA ... 20 mA Output 0/4 mA ... 20 mA |
Описание оборудования | ||
---|---|---|
Input 0/4 mA ... 20 mA Output 0/4 mA ... 20 mA (current sink) |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 0.5 W | |
Power consumption | 0.6 W | |
Input | ||
Connection side | field side | |
Connection | terminals 4-, 5-, 3+, 2+, 1+ | |
Potentiometer | ||
Types of measuring | 3-, 4-, 5-wire technology | |
Lead resistance | 5 % of the potentiometer resistance (adjustable) | |
Output | ||
Connection side | control side | |
Connection | terminals 7-, 8+ | |
Voltage output | 0 ... 10 V | |
Output resistance | max. 30 &Omega | |
Transfer characteristics | ||
Accuracy | 0.05 % | |
Rise time | 10 to 90 % &le 8 ms 10 to 90 % within 1 % of span &le 25 ms | |
Indicators/settings | ||
Control elements | potentiometer | |
Configuration | via potentiometer | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 120 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7171 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1797 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
UL approval | ||
Control drawing | 116-0173 (cULus) | |
CSA approval | ||
Control drawing | 116-0132 | |
IECEx approval | IECEx BAS 10.0060 IECEx BAS 10.0061X | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I Ex nA II T4 Gc |