Товаров: 0
На сумму: 0
| General specifications | ||
|---|---|---|
| Signal type | Analog output | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 11+, 12- | |
| Rated voltage | 20 ... 35 V DC | |
| Ripple | within the supply tolerance | |
| Power dissipation | 1.1 W at 20 mA into 10 V (equivalent to 500 &Omega) load | |
| Power consumption | 1.3 W | |
| Input | ||
| Connection side | control side | |
| Connection | terminals 7-, 8+ | |
| Voltage drop | approx. 4 V or internal resistance 200 &Omega at 20 mA | |
| Input resistance | > 100 k&Omega, when wiring resistance in the field < 50 &Omega or > 800 &Omega at 20 mA | |
| Current | 4 ... 20 mA limited to approx. 25 mA | |
| Output | ||
| Connection side | field side | |
| Connection | terminals 1+, 2- | |
| Current | 4 ... 20 mA | |
| Load | 100 ... 700 &Omega | |
| Voltage | &ge 14 V at 20 mA | |
| Transfer characteristics | ||
| Accuracy | 0.1 % | |
| Rise time | < 100 µs at bounce from 10 ... 90 % | |
| Indicators/settings | ||
| Display elements | LEDs | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Insulation coordination | EN 50178:1997 | |
| Galvanic isolation | EN 50178:1997 | |
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | screw terminals | |
| Mass | approx. 100 g | |
| Dimensions | 20 x 115 x 115 mm (0.8 x 4.5 x 4.5 inch) , housing type B1 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BAS 00 ATEX 7215 | |
| Marking |  II (1)G [Ex ia Ga] IIC ,  II (1)D [Ex ia Da] IIIC ,  I (M1) [Ex ia Ma] I | |
| Certificate | TÜV 99 ATEX 1499 X | |
| Marking |  II 3G Ex nA II T4 [device in zone 2] | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | ||
| Control drawing | 116-0129 | |
| UL approval | ||
| Control drawing | 116-0173 (cULus) | |
| IECEx approval | IECEx BAS 16.0045 | |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I | |
| Производитель | Pepperl+Fuchs | 
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках Компонент аналогового выхода SMART Current Driver KFD2-SCD-Ex1.LK Pepperl+Fuchs.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цена Компонент аналогового выхода SMART Current Driver KFD2-SCD-Ex1.LK Pepperl+Fuchs на сайте имеет информационный характер и может отличаться от цены в коммерческом предложении.