| General specifications | ||
|---|---|---|
| Signal type | Analog output | |
| Functional safety related parameters | ||
| Safety Integrity Level (SIL) | SIL 2 | |
| Supply | ||
| Connection | Power Rail or terminals 9+, 10- | |
| Rated voltage | 19 ... 30 V DC | |
| Ripple | &le 10 % | |
| Rated current | &le 35 mA | |
| Power dissipation | &le 600 mW | |
| Power consumption | &le 700 mW | |
| Input | ||
| Connection side | control side | |
| Connection | terminals 5-, 6+ | |
| Input signal | 4 ... 20 mA , limited to approx. 27 mA | |
| Voltage drop | depending on switch configuration open loop voltage of the control system < 19 V: approx. 5 V at 20 mA open loop voltage of the control system < 26 V: approx. 12 V at 20 mA | |
| Input resistance | > 100 k&Omega, with field wiring open | |
| Output | ||
| Connection side | field side | |
| Connection | terminals 1+, 2- | |
| Current | 4 ... 20 mA | |
| Load | 0 ... 625 &Omega | |
| Voltage | &ge 12.5 V at 20 mA | |
| Ripple | 20 mV rms | |
| Transfer characteristics | ||
| Deviation | at 20 °C (68 °F), 0/4 ... 20 mA &le ± 0.1 % incl. non-linearity and hysteresis | |
| Frequency range | field side into the control side: bandwidth with 0.5 Vpp signal 0 ... 3 kHz (-3 dB) control side into the field side: bandwidth with 1 mApp signal 0 ... 3 kHz (-3 dB) | |
| Rise time | 10 to 90 % &le 100 ms | |
| Indicators/settings | ||
| Display elements | LED | |
| Control elements | DIP-switch | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2006 | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | spring terminals | |
| Mass | approx. 100 g | |
| Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | CESI 11 ATEX 094 | |
| Marking |  II (1)G [Ex ia Ga] IIC ,  II (1) D [Ex ia Da] IIIC ,  I (M1) [Ex ia Ma] I | |
| Certificate | PF 11 CERT 1968X | |
| Marking |  II 3G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
| International approvals | ||
| UL approval | ||
| Control drawing | 116-0395 (cULus) | |
| IECEx approval | IECEx CES 12.0004 | |
| Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I | |
| Производитель | Pepperl+Fuchs | 
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках Компонент аналогового выхода SMART Current Driver KCD2-SCD-Ex1.HC.SP Pepperl+Fuchs.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цена Компонент аналогового выхода SMART Current Driver KCD2-SCD-Ex1.HC.SP Pepperl+Fuchs на сайте имеет информационный характер и может отличаться от цены в коммерческом предложении.