General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 10 &Omega | |
Series resistance | max. 18.18 &Omega | |
Fuse rating | 250 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 4.3 V | |
Measurement loop | max. 0.9 V at 1 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 50 &Omega | |
Series resistance | max. 56 &Omega | |
Fuse rating | 100 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 8.8 V | |
Measurement loop | max. 6.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 100 &Omega | |
Series resistance | max. 107 &Omega | |
Fuse rating | 100 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 13.6 V | |
Measurement loop | max. 13 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 1 k&Omega | |
Series resistance | max. 1025 &Omega | |
Fuse rating | 100 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 13.6 V | |
Measurement loop | max. 13 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
Mechanical specifications | ||
---|---|---|
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 300 &Omega | |
Series resistance | max. 327 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 | |
Safe area connection | ||
Connection | terminals 7, 8 | |
Working voltage | ||
Supply loop | max. 26.3 V | |
Measurement loop | max. 26 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 12 &Omega | |
Series resistance | max. 27.27 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 2, 3 2, 4 | |
Safe area connection | ||
Connection | terminals 5, 7 6, 7 8, 7 | |
Working voltage | ||
Supply loop | max. 3.7 V | |
Measurement loop | max. 0.6 V at 1 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 10 &Omega | |
Series resistance | max. 18.18 &Omega | |
Fuse rating | 250 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 4.3 V | |
Measurement loop | max. 0.9 V at 1 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 50 &Omega | |
Series resistance | max. 64 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 8.8 V | |
Measurement loop | max. 6.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 10 &Omega | |
Series resistance | max. 79 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 8.8 V | |
Measurement loop | max. 6.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7096 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0355 (cULus) | |
CSA approval | ||
Control drawing | 116-0119 |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 100 &Omega | |
Series resistance | max. 106 &Omega | |
Fuse rating | 100 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 7.7 V | |
Measurement loop | max. 6.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 100 &Omega | |
Series resistance | max. 115 &Omega | |
Fuse rating | 100 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 7.7 V | |
Measurement loop | max. 6.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7096 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0355 (cULus) | |
CSA approval | ||
Control drawing | 116-0119 |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 360 &Omega | |
Series resistance | max. 380 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 7.7 V | |
Measurement loop | max. 6.5 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 1000 &Omega | |
Series resistance | max. 1033 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 11.1 V | |
Measurement loop | max. 10 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 100 &Omega | |
Series resistance | max. 115 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 13.6 V | |
Measurement loop | max. 13 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 ... mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 150 &Omega | |
Series resistance | max. 166 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 11.1 V | |
Measurement loop | max. 10 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 150 &Omega | |
Series resistance | max. 169 &Omega | |
Fuse rating | 63 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 11.1 V | |
Measurement loop | max. 10 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 00 ATEX 7096 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0355 (cULus) | |
CSA approval | ||
Control drawing | 116-0119 |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 75 &Omega | |
Series resistance | max. 82 &Omega | |
Fuse rating | 100 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 11.1 V | |
Measurement loop | max. 10 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 120 &Omega | |
Series resistance | max. 136 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 15.6 V | |
Measurement loop | max. 15 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 300 &Omega | |
Series resistance | max. 327 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 19.6 V | |
Measurement loop | max. 19 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
General specifications | ||
---|---|---|
Type | AC version | |
Electrical specifications | ||
Nominal resistance | 600 &Omega | |
Series resistance | max. 646 &Omega | |
Fuse rating | 50 mA | |
Hazardous area connection | ||
Connection | terminals 1, 2 3, 4 | |
Safe area connection | ||
Connection | terminals 5, 6 7, 8 | |
Working voltage | ||
Supply loop | max. 26.3 V | |
Measurement loop | max. 26 V at 10 µA | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Core cross-section | max. 2 x 2.5 mm2 | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 115 x 110 mm (0.5 x 4.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BAS 01 ATEX 7005 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1484 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0118 | |
UL approval | ||
Control drawing | 116-0139 | |
CSA approval | ||
Control drawing | 116-0119 | |
IECEx approval | IECEx BAS 09.0142 IECEx BAS 17.0091X | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I Ex ec IIC T4 Gc |
Описание оборудования | ||
---|---|---|
115 V AC |
Описание оборудования | ||
---|---|---|
230 V AC |
Описание оборудования | ||
---|---|---|
230 V AC |
Описание оборудования | ||
---|---|---|
230 V AC |
Описание оборудования | ||
---|---|---|
230 V AC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 20 ... 30 V DC | |
Input | ||
Connection side | field side | |
Connection | terminals 1 (mass), 2 (min), 3 (max) | |
Open circuit voltage/short-circuit current | approx. 10 V AC (approx. 1 Hz) / approx. 5 mA | |
Control input | min./max. control system: terminals 1, 2, 3 on/off control system: terminals 1, 3 | |
Response sensitivity | 1 ... 30 k&Omega , adjustable via potentiometer (20 turns) | |
Output | ||
Connection side | control side | |
Connection | terminals 7, 8, 9 | |
Output | 1 changeover contact | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Energized/De-energized delay | approx. 1 s / approx. 1 s | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch potentiometer | |
Configuration | via DIP switches via potentiometer | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals , max. 2.5 mm2 | |
Mass | approx. 110 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | Power Rail or terminals 11+, 12- | |
Rated voltage | 20 ... 30 V DC | |
Input | ||
Connection side | field side | |
Connection | terminals 1 (mass), 2 (min), 3 (max) | |
Open circuit voltage/short-circuit current | approx. 10 V AC (approx. 1 Hz) / approx. 5 mA | |
Control input | min./max. control system: terminals 1, 2, 3 on/off control system: terminals 1, 3 | |
Response sensitivity | 5 ... 150 k&Omega , adjustable via potentiometer (20 turns) | |
Output | ||
Connection side | control side | |
Connection | terminals 7, 8, 9 | |
Output | 1 changeover contact | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Energized/De-energized delay | approx. 1 s / approx. 1 s | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch potentiometer | |
Configuration | via DIP switches via potentiometer | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals , max. 2.5 mm2 | |
Mass | approx. 110 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Описание оборудования | ||
---|---|---|
24 V DC |
Описание оборудования | ||
---|---|---|
24 V DC |