| Functional safety related parameters | ||
|---|---|---|
| Safety Integrity Level (SIL) | SIL 3 | |
| Supply | ||
| Connection | SL1: 1a, 1b(-) 2a, 2b(+) | |
| Rated voltage | 20.4 ... 30 V DC via Termination Board | |
| Rated current | 28 mA at 24 V , RS-485, quiescent current | |
| Power dissipation | 0.7 W at 24 V | |
| HART signal channels (non-intrinsically safe) | ||
| Number of channels | 32 | |
| Conformity | HART field device input (revision 5 to 7) | |
| Signal range | 0.12 Vpp < signal < 1.5 Vpp | |
| Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
| Terminating resistor | external 230 ... 500 &Omega standard (up to 1000 &Omega possible) | |
| Output voltage | &ge 400 mV ss (with the terminator resistance specified above) | |
| Output resistance | 100 &Omega or smaller, capacitive coupling | |
| DC isolation | dual capacitor each channel | |
| Common mode voltage | up to 30 V | |
| Input impedance | > 5 k&Omega , according to HART specification | |
| Input voltage range | 0.12 ... 1.5 V ss | |
| Common mode voltage | max. 30 V | |
| Differential mode clamping | ± 5.2 V , for transient or AC signals | |
| Common mode clamping | ± 10 V , for transient or AC signals | |
| Carrier detect level | signal > 0.12 Vpp, carrier detection activated signal < 0.08 Vpp, carrier detection not activated | |
| Transmit amplitude | 200 &Omega load, 0.43 Vpp < signal < 0.49 Vpp 500 &Omega load, 1.1 Vpp < signal < 1.2 Vpp | |
| Device type | DC isolated bus device | |
| Impedance | high impedance | |
| Data link type | HART primary and secondary | |
| Field multi point support | option available upon request | |
| Interface | ||
| Transfer rate | 9600 MBit/s, 19200 MBit/s or 38400 MBit/s, selectable via switch | |
| Address | 1 ... 31 , adjustable via DIP switch | |
| Type | RS-485 , differential pair and grounding | |
| Topology | multi point, master/slave connection | |
| Indicators/settings | ||
| Display elements | LEDs LED PWR ON (power supply), one green LED LED HART TX (HART transmission), one yellow LED LED FAULT (lead fault), one red LED | |
| Control elements | DIP switches at the housing side for: - unit slave address - baud rate - test mode on/off | |
| Configuration | via DIP switches | |
| Labeling | space for labeling at the front | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Mass | approx. 140 g | |
| Dimensions | 18 x 106 x 128 mm (0.7 x 4.2 x 5 inch) | |
| Mounting | on Termination Board | |
| Data for application in connection with hazardous areas | ||
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| CSA approval | 1256050 | |
| Approved for | Class I, Division 2, Groups A, B, C, D Class I, Zone 2, IIC | |
| Supply | ||
|---|---|---|
| Connection | X20: terminals 1, 3 (+) 2, 4 (-) | |
| Nominal voltage | 24 V DC SELV/PELV | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 0.5 A | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Interface | ||
| Type/number | 2 x RS-485 | |
| Redundancy | ||
| Supply | Redundancy available. Each supply is decoupled. | |
| Indicators/settings | ||
| Display elements | LED PWR1 (Termination Board power supply), green LED LED PWR2 (Termination Board power supply), green LED | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | ||
| Control side | RS-485 : 1 x screw terminal , black HART : 2 x IDC plug, 34-pin | |
| Supply | pluggable screw terminals , black | |
| Core cross-section | screw terminals: 0.25 ... 1.5 mm2 (24 ... 12 AWG) | |
| Material | housing: polycarbonate, 10 % glass fiber reinforced | |
| Mass | approx. 190 g | |
| Dimensions | 50 x 200 x 163 mm (1.97 x 7.9 x 6.42 inch) , height including module assembly | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Supply | ||
|---|---|---|
| Connection | X20: terminals 1, 3 (+) 2, 4 (-) | |
| Nominal voltage | 24 V DC SELV/PELV | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 0.5 A | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Interface | ||
| Type/number | 2 x RS-485 | |
| Redundancy | ||
| Supply | Redundancy available. Each supply is decoupled. | |
| Indicators/settings | ||
| Display elements | LED PWR1 (Termination Board power supply), green LED LED PWR2 (Termination Board power supply), green LED | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | ||
| Control side | RS-485 : 1 x screw terminal , black HART : 4 x IDC plug, 34-pin | |
| Supply | pluggable screw terminals , black | |
| Core cross-section | screw terminals: 0.25 ... 1.5 mm2 (24 ... 12 AWG) | |
| Material | housing: polycarbonate, 10 % glass fiber reinforced | |
| Mass | approx. 210 g | |
| Dimensions | 50 x 200 x 163 mm (1.97 x 7.9 x 6.42 inch) , height including module assembly | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Supply | ||
|---|---|---|
| Connection | X20: terminals 1, 3 (+) 2, 4 (-) | |
| Nominal voltage | 24 V DC SELV/PELV | |
| Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
| Ripple | &le 10 % | |
| Fusing | 0.5 A | |
| Power dissipation | &le 500 mW , without modules | |
| Reverse polarity protection | yes | |
| Interface | ||
| Type/number | 2 x RS-485 | |
| Redundancy | ||
| Supply | Redundancy available. Each supply is decoupled. | |
| Indicators/settings | ||
| Display elements | LED PWR1 (Termination Board power supply), green LED LED PWR2 (Termination Board power supply), green LED | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
| Degree of protection | IEC 60529:2001 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Connection | ||
| Control side | RS-485 : 1 x screw terminal , black HART : 4 x IDC plug, 34-pin | |
| Supply | pluggable screw terminals , black | |
| Core cross-section | screw terminals: 0.25 ... 1.5 mm2 (24 ... 12 AWG) | |
| Material | housing: polycarbonate, 10 % glass fiber reinforced | |
| Mass | approx. 210 g | |
| Dimensions | 50 x 200 x 163 mm (1.97 x 7.9 x 6.42 inch) , height including module assembly | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: fixed screw terminals control side: PCS-specified connector RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 700 g | |
| Dimensions | without HiDMux2700: 333 x 125 x 79 mm (13.1 x 4.9 x 3.1 inch) with Mux2700: 333 x 125 x 208 mm (13.1 x 4.9 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC | |
| Fusing | 2 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 64 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | HART loop interface: connectors depending on version RS-485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 152 x 121 x 53 mm (6 x 4.75 x 2.1 inch) with HiDMux2700: 152 x 121 x 142 mm (6 x 4.75 x 5.6 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: fixed screw terminals control side: fixed screw terminals RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 222 x 122 x 79 mm (8.7 x 4.8 x 3.1 inch) with HiDMux2700: 222 x 122 x 208 mm (8.7 x 4.8 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 100 mA , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: screw terminals/Sub-D socket 2 x 37-pin RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 700 g | |
| Dimensions | without HiDMux2700: 300 x 127 x 72 mm (11.8 x 5 x 2.84 inch) with HiDMux2700: 300 x 127 x 186 mm (11.8 x 5 x 7.3 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 315 mA , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: 2 x 37-pin Sub-D socket control side: 4 x 26-pin connectors RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 260 x 120 x 57 mm (10.2 x 4.7 x 2.84 inch) with HiDMux2700: 260 x 120 x 190 mm (10.2 x 4.7 x 7.5 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 315 mA , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: 5.08 mm removable screw terminals control side: 50-pin Centronics plug RS-485 interface: 5.08 mm removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 333 x 127 x 57 mm (13.1 x 5 x 2.84 inch) with HiDMux2700: 333 x 127 x 190 mm (13.1 x 5 x 7.5 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 315 mA , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: 5.08 mm removable screw terminals control side: 50-pin Centronics plug RS-485 interface: 5.08 mm removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 307 x 120 x 57 mm (12.1 x 4.7 x 2.84 inch) with HiDMux2700: 307 x 120 x 190 mm (12.1 x 4.7 x 7.5 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 24 V DC | |
| Fusing | 315 mA , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: 5.08 mm removable screw terminals control side: 50-pin Centronics plug RS-485 interface: 5.08 mm removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 333 x 127 x 57 mm (13.1 x 5 x 2.84 inch) with HiDMux2700: 333 x 127 x 190 mm (13.1 x 5 x 7.5 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: 56-pin Elco connector RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 256 x 125 x 79 mm (10 x 4.9 x 3.1 inch) with HiDMux2700: 256 x 125 x 208 mm (10 x 4.9 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: 56-pin Elco connector RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 256 x 125 x 79 mm (10 x 4.9 x 3.1 inch) with HiDMux2700: 256 x 125 x 208 mm (10 x 4.9 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: 56-pin Elco connector RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 256 x 125 x 79 mm (10 x 4.9 x 3.1 inch) with HiDMux2700: 256 x 125 x 208 mm (10 x 4.9 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: 56-pin Elco connector RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 254 x 107 x 79 mm (10 x 4.2 x 3.1 inch) with HiDMux2700: 254 x 107 x 208 mm (10 x 4.2 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: 56-pin Elco connector RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 333 x 125 x 79 mm (13.1 x 4.9 x 3.1 inch) with Mux2700: 333 x 125 x 208 mm (13.1 x 4.9 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | yes | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | yes | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: 56-pin Elco connector RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 333 x 125 x 79 mm (13.1 x 4.9 x 3.1 inch) with Mux2700: 333 x 125 x 208 mm (13.1 x 4.9 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | no | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | no | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: KS connector (proprietary) RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 330 x 107 x 79 mm (12.9 x 4.2 x 3.1 inch) with HiDMux2700: 330 x 107 x 208 mm (12.9 x 4.2 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC | |
| Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
| Power dissipation | 0.7 W , with Multiplexer | |
| Reverse polarity protection | no | |
| HART signal channels (intrinsically safe) | ||
| HART signal channels | ||
| Number of channels | 32 unbalanced signal loops | |
| Redundancy | ||
| Supply | no | |
| Galvanic isolation | ||
| HART signal channels | 30 V DC | |
| Ambient conditions | ||
| Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
| Relative humidity | 5 ... 90 %, non-condensing | |
| Mechanical specifications | ||
| Core cross-section | 2.5 mm2 (16 AWG) | |
| Connection | field side: screw terminals control side: KS connector (proprietary) RS 485 interface: removable screw terminals power: removable screw terminals | |
| Mass | approx. 500 g | |
| Dimensions | without HiDMux2700: 330 x 107 x 79 mm (12.9 x 4.2 x 3.1 inch) with HiDMux2700: 330 x 107 x 208 mm (12.9 x 4.2 x 8.2 inch) | |
| Mounting | DIN rail mounting | |
Товаров: 0
На сумму: 0