Functional safety related parameters | ||
---|---|---|
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | terminals 17+, 18- | |
Rated voltage | 20 ... 32 V DC typical at 100 mA | |
Power consumption | max. 3 W | |
HART signal channels (non-intrinsically safe) | ||
Conformity | HART field device input (revision 5 to 7) | |
Connection | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 | |
Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
Terminating resistor | external 230 ... 500 &Omega standard (up to 1000 &Omega possible) | |
Output voltage | &ge 400 mV ss (with the terminator resistance specified above) | |
Output resistance | 100 &Omega or smaller, capacitive coupling | |
Input impedance | according to HART specification | |
Input voltage range | 0.08 ... 4 V ss typ. ± 5.2 V as local reference | |
Interface | ||
Transfer rate | 9600, 19200, or 38400 Bit/s (selectable with DIL switch (2 and 3) by the user) | |
Type | RS-485 , 2-wire multidrop | |
Address selection | One of 31 possible addresses selectable per DIL switch (4 ... 8) | |
Indicators/settings | ||
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | approx. 250 g | |
Dimensions | 40 x 107 x 115 mm (1.6 x 4.2 x 4.5 inch) , housing type C1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 07 CERT 1143 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
Functional safety related parameters | ||
---|---|---|
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | via 14-channel flat cable form master KFD2-HMM-16 | |
HART signal channels (non-intrinsically safe) | ||
Conformity | HART field device input (revision 5 to 7) | |
Connection | 26-pin flat cable for analog connections 14-pin flat cable for master-slave connection between KFD2-HMM-16 and KFD0-HMS-16 | |
Leakage current | < 3 µA at -20 ... 85 °C (-4 ... 185 °F) | |
Terminating resistor | external 230 ... 500 &Omega standard (up to 1000 &Omega possible) | |
Output voltage | &ge 400 mV ss (with the terminator resistance specified above) | |
Output resistance | 100 &Omega or smaller, capacitive coupling | |
Input impedance | according to HART specification | |
Input voltage range | 0.08 ... 4 V ss typ. ± 5.2 V as local reference | |
Indicators/settings | ||
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Mass | approx. 100 g | |
Dimensions | 20 x 93 x 115 mm (0.8 x 3.7 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | PF 07 CERT 1143 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
HART signal channels (non-intrinsically safe) | ||
---|---|---|
Load resistor | 250 &Omega | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | 0 ... 50 °C (32 ... 122 °F) | |
Storage temperature | -15 ... 50 °C (5 ... 122 °F) | |
Relative humidity | &le 93 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | field side connection: spring terminals control side connection: NFP-26A, 26-pin (Yamaichi) | |
Core cross-section | 0.25 ... 1.5 mm2 (24 ... 12 AWG) | |
Mass | approx. 150 g | |
Dimensions | 67 x 90 x 110 mm (2.6 x 3.5 x 4.3 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
HART signal channels (non-intrinsically safe) | ||
---|---|---|
Load resistor | 220 &Omega , switchable on | |
Interface | ||
Type | multiplexer connection : 26-pin NFP-26A (Yamaichi) | |
Signal lines | ||
Rated current | max. 30 mA per channel | |
Indicators/settings | ||
DIP switch | selection of operating mode: - ON: without load resistor - OFF: with load resistor | |
Factory setting | DIP switches S1 and S2: ON | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | 0 ... 50 °C (32 ... 122 °F) | |
Storage temperature | -15 ... 50 °C (5 ... 122 °F) | |
Relative humidity | &le 93 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | ||
Field side | screw terminals , green | |
Control side | screw terminals , green HART : 1 x IDC plug, 26-pin | |
Core cross-section | screw terminals: 0.25 ... 1.5 mm2 (24 ... 16 AWG) | |
Mass | approx. 200 g | |
Dimensions | 110 x 125 x 67 mm (4.3 x 4.9 x 2.6 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
Supply | ||
---|---|---|
Rated voltage | 20.4 ... 27.6 V DC SELV/PELV | |
Voltage drop | 0.9 V , voltage drop across the series diode on the termination board must be considered | |
Fusing | 1 A | |
Redundancy | ||
Supply | yes | |
Signal lines | ||
Rated current | max. 30 mA per channel | |
Indicators/settings | ||
Display elements | - LED PS-A (Termination Board power supply), green LED - LED PS-B (Termination Board power supply), green LED | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | 0 ... 50 °C (32 ... 122 °F) | |
Storage temperature | -15 ... 50 °C (5 ... 122 °F) | |
Relative humidity | &le 93 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | field side connection: screw terminals, green control side connection: ELCO socket, 56-pin | |
Core cross-section | 0.5 ... 2.5 mm2 (20 ... 12 AWG) | |
Mass | approx. 400 g | |
Dimensions | 123 x 126 x 67 mm (4.9 x 5.0 x 2.6 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
Supply | ||
---|---|---|
Rated voltage | 25 ... 28 V DC SELV/PELV | |
Fusing | 1 A | |
Redundancy | ||
Supply | yes | |
Indicators/settings | ||
Display elements | - LED PS-A (Termination Board power supply), green LED - LED PS-B (Termination Board power supply), green LED | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 For further information see system description. | |
Degree of protection | IEC 60529:2001 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | 0 ... 50 °C (32 ... 122 °F) | |
Storage temperature | -15 ... 50 °C (5 ... 122 °F) | |
Relative humidity | &le 93 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | field side connection: screw terminals, green control side connection: ELCO socket, 56-pin | |
Core cross-section | 0.5 ... 2.5 mm2 (20 ... 12 AWG) | |
Mass | approx. 400 g | |
Dimensions | 123 x 126 x 67 mm (4.9 x 5.0 x 2.6 inch) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 19 ... 30 V DC | |
Rated current | approx. 120 mA at 24 V DC | |
Power dissipation | 2.3 W | |
Power consumption | 2.9 W | |
HART signal channels (intrinsically safe) | ||
Conformity | HART field device input (revision 5 to 7) | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 5, 6 | |
Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
Input resistance | 250 &Omega , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
Available voltage | &ge 15.5 V at 20 mA, short-circuit protected | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 , output II: terminals 13, 14, 15 , output III: terminals 19, 20, 21 | |
Output signal | analog | |
Current range | 4 ... 20 mA , (source or sink mode) | |
Load | max. 650 &Omega , source mode | |
Voltage range | 5 ... 30 V , sink mode from external supply | |
Fault signal | downscale I &le 2 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
Other outputs | HART communicator on terminals 22, 24 | |
Collective error message | Power Rail and LED red | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 | |
Marking | ![]() | |
Certificate | PF 07 CERT 1142 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
IECEx approval | ||
IECEx certificate | IECEx BAS 07.0047 | |
IECEx marking | [Ex ia] IIC , [Ex iaD] |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 19 ... 30 V DC | |
Rated current | approx. 130 mA at 24 V DC | |
Power dissipation | 2.5 W | |
Power consumption | 3.1 W | |
HART signal channels (intrinsically safe) | ||
Conformity | HART field device input (revision 5 to 7) | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 5, 6 | |
Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
Input resistance | 250 &Omega , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
Available voltage | &ge 15.5 V at 20 mA, short-circuit protected | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12, output II: terminals 16, 17, 18 output III: terminals 7, 8, 9, output IV: terminals 13, 14, 15, output V: terminals 19, 20, 21 | |
Output I, II | ||
Output signal | relay and LED yellow | |
Mechanical life | 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output III, IV, V | ||
Output signal | analog | |
Current range | 4 ... 20 mA , (source or sink mode) | |
Load | max. 650 &Omega , source mode | |
Voltage range | 5 ... 30 V , sink mode from external supply | |
Fault signal | downscale I &le 2 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
Other outputs | HART communicator on terminals 22, 24 | |
Collective error message | Power Rail and LED red | |
Transfer characteristics | ||
Relay | programmable either for fault or trip value (with direction, hysteresis and delay) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 | |
Marking | ![]() | |
Certificate | PF 07 CERT 1141 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
IECEx approval | ||
IECEx certificate | IECEx BAS 07.0047 | |
IECEx marking | [Ex ia] IIC , [Ex iaD] |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 19 ... 30 V | |
Rated current | approx. 140 mA at 24 V DC | |
Power dissipation | 2.7 W | |
Power consumption | 3.3 W | |
HART signal channels (intrinsically safe) | ||
Conformity | HART field device input (revision 5 to 7) | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 5, 6 | |
Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
Input resistance | 250 &Omega , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
Available voltage | &ge 15.5 V at 20 mA, short-circuit protected | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, output II: terminals 11, 12, output III: terminals 16, 17, output IV: terminals 17, 18 output V: terminals 7, 8, 9, output VI: terminals 13, 14, 15, output VII: terminals 19, 20, 21 | |
Output I, II, III, IV | ||
Output signal | relay and LED yellow | |
Mechanical life | 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output V, VI, VII | ||
Output signal | analog | |
Current range | 4 ... 20 mA , (source or sink mode) | |
Load | max. 650 &Omega , source mode | |
Voltage range | 5 ... 30 V , sink mode from external supply | |
Fault signal | downscale I &le 2 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
Other outputs | HART communicator on terminals 22, 24 | |
Collective error message | Power Rail and LED red | |
Transfer characteristics | ||
Relay | programmable either for fault or trip value (with direction, hysteresis and delay) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 | |
Marking | ![]() | |
Certificate | PF 07 CERT 1141 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
IECEx approval | ||
IECEx certificate | IECEx BAS 07.0047 | |
IECEx marking | [Ex ia] IIC , [Ex iaD] |