| Search characteristics | ||
|---|---|---|
| Network | TN-C | |
| General specifications | ||
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 3 | |
| Suitable components | protection module M-LB-1.275.M | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC / 400 V AC | |
| Maximum continuous operating voltage | max. 275 V AC | |
| Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 20 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
| Reaction time | max. 25 ns | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 360 g | |
| Dimensions | 54 x 90 x 73 mm (2.1 x 3.6 x 2.9 inch) (3 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Search characteristics | ||
|---|---|---|
| Network | TN-S | |
| General specifications | ||
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 4 | |
| Suitable components | protection module M-LB-1.150.M | |
| Electrical specifications | ||
| Nominal voltage | 120 V AC / 240 V AC | |
| Maximum continuous operating voltage | max. 150 V AC | |
| Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 15 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
| Reaction time | max. 25 ns | |
| Short-circuit-proof | 50 kA eff | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 480 g | |
| Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Search characteristics | ||
|---|---|---|
| Network | TN-S | |
| General specifications | ||
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 4 | |
| Suitable components | protection module M-LB-1.275.M | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC / 400 V AC | |
| Maximum continuous operating voltage | max. 275 V AC | |
| Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
| Nominal discharge current (8/20 µs) | 20 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
| Reaction time | max. 25 ns | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 480 g | |
| Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Search characteristics | ||
|---|---|---|
| Network | TT | |
| General specifications | ||
| Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
| Number of protected supply lines | 4 | |
| Suitable components | protection module M-LB-1.275.M protection module M-LB-1.NPE.M | |
| Electrical specifications | ||
| Nominal voltage | 230 V AC / 400 V AC | |
| Maximum continuous operating voltage | max. 275 V AC (L-N) max. 255 V AC (N-PE) | |
| Temporary over-voltage | 335 V/5 s (TOV withstand) (L-N) 1200 V/200 ms (TOV withstand) (N-PE) | |
| Nominal discharge current (8/20 µs) | 20 kA | |
| Max. surge current (8/20 µs) | 40 kA | |
| Total discharge current (8/20 µs) | 12 kA (N-PE) | |
| Voltage protection level | max. 1.25 kV (L-N) max. 1 kV at 5 kA (L-N) &le 1.5 kV (N-PE) | |
| Reaction time | max. 25 ns (L-N) max. 100 ns (N-PE) | |
| Follow current extinguishing capability | 100 A eff (N-PE) | |
| Short-circuit-proof | 50 kA eff | |
| Overcurrent protection | max. 125 A gG , mains-side | |
| Fault indication output | ||
| Connection | terminals 11, 12, 14 | |
| Output | volt-free change-over contact | |
| Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
| Indicators/settings | ||
| Display elements | status display operating state (green) fault indication (red) | |
| Directive conformity | ||
| Low voltage | ||
| Directive 2014/35/EU | EN 61643-11:2012 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
| Mechanical specifications | ||
| Degree of protection | IP20 | |
| Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
| Material | ||
| Housing | thermoplastic, color grey , UL 94 V-0 | |
| Mass | approx. 480 g | |
| Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) | |
| Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
| Описание оборудования | ||
|---|---|---|
| &lambda/4 surge protection, N socket to N socket | ||
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC SELV/PELV | |
| Power consumption | < 5 W | |
| External bus | ||
| Connection | screw terminals for - 0.2 ... 4 mm2 (rigid wire) - 0.2 ... 2.5 mm2 (flexible wire) | |
| Interface 1 | Ethernet 10 BASE-T/100 BASE-TX , full galvanic isolation | |
| Protocol | HART UDP, MODBUS TCP | |
| Interface 2 | RS-485 | |
| Protocol | HART, MODBUS RTU | |
| Transfer rate | max. 115 kBit/s | |
| Galvanic isolation | ||
| Interface/interface | basic insulation according to IEC 61140, rated insulation voltage 50 Veff | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
| Directive 2014/53/EU | EN 300328: V2.1.1 EN 301489-17: V1.3.2 | |
| FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
| Mechanical specifications | ||
| Degree of protection | IP66/IP67 | |
| Mass | approx. 1 kg | |
| Dimensions | 258 mm x 114 mm x 84 mm without antenna and cable glands | |
| Mounting | panel mounting | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | FM 12 ATEX 0061 | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | Coc3042646 | |
| Approved for | NI Class I, Div. 2, GPS A-D NI Class II, Class III, Div. 2, GPS E-G | |
| IECEx approval | IECEx FMG 12.0002 | |
| Approved for | Ex nA IIC T4 Gc , Ex nAc T4 | |
| Supply | ||
|---|---|---|
| Rated voltage | 20 ... 30 V DC SELV/PELV | |
| Power consumption | < 5 W | |
| External bus | ||
| Connection | screw terminals for - 0.2 ... 4 mm2 (rigid wire) - 0.2 ... 2.5 mm2 (flexible wire) | |
| Interface 1 | Ethernet 10 BASE-T/100 BASE-TX , full galvanic isolation | |
| Protocol | HART UDP, EtherNet/IP | |
| Interface 2 | RS-485 | |
| Protocol | HART | |
| Transfer rate | max. 115 kBit/s | |
| Galvanic isolation | ||
| Interface/interface | basic insulation according to IEC 61140, rated insulation voltage 50 Veff | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2013 | |
| Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
| Directive 2014/53/EU | EN 300328: V2.1.1 EN 301489-17: V1.3.2 | |
| FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
| Conformity | ||
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
| Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
| Mechanical specifications | ||
| Degree of protection | IP66/IP67 | |
| Mass | approx. 1 kg | |
| Dimensions | 258 mm x 114 mm x 84 mm without antenna and cable glands | |
| Mounting | panel mounting | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | FM 12 ATEX 0061 , for additional certificates see www.pepperl-fuchs.com | |
| Marking | II 3 G Ex nA nC IIC T4 Gc | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
| International approvals | ||
| FM approval | Coc3042646 | |
| Approved for | NI Class I, Div. 2, GPS A-D NI Class II, Class III, Div. 2, GPS E-G | |
| IECEx approval | IECEx FMG 12.0002 | |
| Approved for | Ex nA nC IIC T4 Gc Ex nAc nCc T4 | |
Товаров: 0