Атол 30Ф не включается (заводской брак)
Валерий
14 января 2022
Supply | ||
---|---|---|
Rated voltage | 7 ... 32 V DC | |
Rated current | < 1 mA , max. 25 mA | |
Electrical specifications | ||
Output rated operating current | 3.2 ... 25 mA | |
Supply | loop power for field devices voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V | |
Input | ||
Connection | - 5 wires, 600 mm long, exiting from male thread NPT1/2 - 1 external grounding point | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | up to 8 HART field devices (depending on installation) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013+A11:2013 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300 328 V1.8.1:2012 EN 301 489-1 V1.9.2:2011 EN 301 489-17 V2.2.1:2012-09 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Material | Aluminum alloy with polyurethane enamel paint | |
Mass | 460 g | |
Dimensions | 60.8 x 60.8 x 100 mm (l x w x h) | |
Data for application in connection with hazardous areas | ||
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
Supply | ||
---|---|---|
Rated voltage | 7 ... 30 V DC | |
Rated current | < 1 mA , max. 25 mA | |
Electrical specifications | ||
Output rated operating current | 3.2 ... 25 mA | |
Supply | loop power for field devices voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V | |
Input | ||
Connection | - 5 wires, 600 mm long, exiting from male thread NPT1/2 - 1 external grounding point | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | up to 8 HART field devices (depending on installation) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013+A11:2013 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300 328 V1.8.1:2012 EN 301 489-1 V1.9.2:2011 EN 301 489-17 V2.2.1:2012-09 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | temperature class T5: -40 ... 85 °C (-40 ... 185 °F) temperature class T6: -40 ... 75 °C (-40 ... 167 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Material | Aluminum alloy with polyurethane enamel paint | |
Mass | 460 g | |
Dimensions | 60.8 x 60.8 x 100 mm (l x w x h) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | FM 11 ATEX 0019 X | |
Marking | II 1 G Ex ia IIC T6/T5 Ga II 1 D Ex ia IIIC T95 °C Da | |
Certificate | FM 11 ATEX 0068 X | |
Marking | II 3 G Ex nA IIC T6/T5 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | CoC3040786(C) | |
Approved for | Class I, Zone 0, (A)Ex ia IIC T6/T5 Ga Class I, Zone 2, (A)Ex nA IIC T6/T5 Gc Class I, Zone 20, (A)Ex ia IIIC T95°C Da Class I, Division 1, Groups A - D Class II, Division 1, Groups E - G Class III Class I, Division 2, Groups A - D | |
IECEx approval | IECEx FMG 11.0010X | |
Approved for | Ex ia IIC T6/T5 Ga Ex nA IIC T6/T5 Gc Ex ia IIIC T95°C Da | |
Standards | IEC 60079-0:2011 , IEC 60079-11:2011 , IEC 60079-15:2010 |
Supply | ||
---|---|---|
Rated voltage | 7 ... 32 V DC | |
Rated current | < 1 mA , max. 25 mA | |
Electrical specifications | ||
Output rated operating current | 3.2 ... 25 mA | |
Supply | loop power for field devices voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V | |
Input | ||
Connection | - 5 wires, 600 mm long, exiting from male thread NPT1/2 - 1 external grounding point | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | up to 8 HART field devices (depending on installation) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013+A11:2013 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300 328 V1.8.1:2012 EN 301 489-1 V1.9.2:2011 EN 301 489-17 V2.2.1:2012-09 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | temperature class T5: -40 ... 85 °C (-40 ... 185 °F) temperature class T6: -40 ... 75 °C (-40 ... 167 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Material | Aluminum alloy with polyurethane enamel paint | |
Mass | 460 g | |
Dimensions | 60.8 x 60.8 x 100 mm (l x w x h) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | FM 12 ATEX 0021 X | |
Marking | II 2 G Ex db IIC T6/T5 Gb II 2 D Ex tb IIIC T95°C Db | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | Coc3041762(C) | |
Approved for | Class I, Zone 1, (A)Ex db IIC T6/T5 Gb Class I, Zone 21, (A)Ex tb IIIC T95°C Db Class I, Division 1, Groups A - D Class II, Division 1, Groups E - G Class III | |
IECEx approval | IECEx FMG 12.0005X | |
Approved for | Ex db IIC T6/T5 Gb Ex tb IIIC T95°C Db | |
Standards | IEC 60079-0:2011 , IEC 60079-1:2014 , IEC 60079-31:2013 |
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output rated operating current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Input | ||
Connectable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode | |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | aluminum | |
Mass | approx. 1000 g | |
Dimensions | 91 x 88.5 x 100.6 mm (3.6 x 3.5 x 4 inch) (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting versions see type code | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | BVS 11 ATEX E 081 , for additional certificates see www.pepperl-fuchs.com | |
Group, category, type of protection, temperature class | II 2 G Ex ia IIC T4 Gb II 2 D Ex tb [ia] IIIC T70°C Db IP6x | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2009 , EN 60079-11:2007 , EN 60079-31:2009 | |
International approvals | ||
IECEx approval | BVS 11.0061 | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-MKF8 |
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output rated operating current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Input | ||
Connectable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode | |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | plastic | |
Mass | approx. 750 g | |
Dimensions | 91 x 88.5 x 100.6 mm (3.6 x 3.5 x 4 inch) (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting versions see type code | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-MKF8 |
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output rated operating current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Input | ||
Connectable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode | |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | plastic | |
Mass | approx. 750 g | |
Dimensions | 91 x 88.5 x 100.6 mm (3.6 x 3.5 x 4 inch) (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting versions see type code | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | BVS 11 ATEX E 081 , for additional certificates see www.pepperl-fuchs.com | |
Group, category, type of protection, temperature class | II 2 G Ex ia IIC T4 Gb | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2009 , EN 60079-11:2007 , EN 60079-31:2009 | |
International approvals | ||
IECEx approval | BVS 11.0061 | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-MKF8 |
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output rated operating current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Input | ||
Suitable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode | |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.3, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013, CLASS A | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300328 V2.1.1:2017 , EN 301489-17 V3.1.1:2017 , EN 301489-1 V2.1.1:2017 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
RoHs | ||
Directive 2011/65/EU (RoHS) | EN 50581:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | Aluminum | |
Mass | approx. 1000 g | |
Dimensions | 92 x 89.5 x 92.8 mm (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 17 ATEX E 029 | |
Marking | II 2G Ex ia IIC T4/T3 Gb II 2D Ex tb [ia] IIIC T70°C Db | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0435 | |
IECEx approval | ||
IECEx certificate | IECEX BVS 17.0023 | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-F8MK threads (NPT 1/2", NPT 3/4", G 1/2, M20) |
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output rated operating current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Input | ||
Suitable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode | |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.3, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013, CLASS A | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300328 V2.1.1:2017 , EN 301489-17 V3.1.1:2017 , EN 301489-1 V2.1.1:2017 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
RoHs | ||
Directive 2011/65/EU (RoHS) | EN 50581:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | plastic | |
Mass | approx. 750 g | |
Dimensions | 92 x 89.5 x 92.8 mm (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-F8MK threads (NPT 1/2", NPT 3/4", G 1/2, M20) |
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output rated operating current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Input | ||
Suitable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode | |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.3, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013, CLASS A | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300328 V2.1.1:2017 , EN 301489-17 V3.1.1:2017 , EN 301489-1 V2.1.1:2017 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
RoHs | ||
Directive 2011/65/EU (RoHS) | EN 50581:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | plastic | |
Mass | approx. 750 g | |
Dimensions | 92 x 89.5 x 92.8 mm (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 17 ATEX E 029 | |
Marking | II 2G Ex ia IIC T4/T3 Gb | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | ||
IECEx certificate | IECEX BVS 17.0023 | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-F8MK threads (NPT 1/2", NPT 3/4", G 1/2, M20) |
Описание оборудования | ||
---|---|---|
Adapter N socket to N socket |
Описание оборудования | ||
---|---|---|
Adapter N socket to TNC socket |
Описание оборудования | ||
---|---|---|
Adapter N plug to TNC plug |
Описание оборудования | ||
---|---|---|
Adapter TNC plug to N socket |
Описание оборудования | ||
---|---|---|
Panel antenna for 2.4 GHz band |
Описание оборудования | ||
---|---|---|
Rod antenna for 2.4 GHz band |
Описание оборудования | ||
---|---|---|
Rod antenna for 2.4 GHz band |
Описание оборудования | ||
---|---|---|
Panel antenna for 2.4 GHz band |
Electrical specifications | ||
---|---|---|
Nominal voltage | 3.6 V | |
Nominal current | 5 mA | |
Nominal capacity | 19 Ah , capacity can varies with usage conditions | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | 15 ... 30 °C (59 ... 86 °F) recommended -40 ... 80 °C (-40 ... 176 °F) at accelerated derating | |
Mechanical specifications | ||
Mass | approx. 90 g | |
Dimensions | Ø33 x 61,5 mm (1.3 x 2.4 inch) |
Electrical specifications | ||
---|---|---|
Nominal voltage | 7.2 V | |
Nominal current | 250 mA | |
Nominal capacity | 19 Ah , capacity can varies with usage conditions | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Storage temperature | 15 ... 30 °C (59 ... 86 °F) recommended -40 ... 80 °C (-40 ... 176 °F) at accelerated derating | |
Mechanical specifications | ||
Mass | approx. 285 g | |
Dimensions | 75 x 71 x 39 mm (2.95 x 2.8 x 1.5 inch) |
Описание оборудования | ||
---|---|---|
Coaxial cable, N plug to N plug |
Mechanical specifications | ||
---|---|---|
Mass | approx. 5 g | |
Dimensions | 13 x 17 x 7 mm (0.53 x 0.66 x 0.27 inch) |
Mechanical specifications | ||
---|---|---|
Material | metal | |
Mass | approx. 175 g | |
Dimensions | 95 x 38 x 40 mm (3.7 x 1.5 x 1.6 inch) | |
Mounting | pole mounting |
Mechanical specifications | ||
---|---|---|
Material | metal | |
Mass | approx. 200 g | |
Dimensions | 81 x 214 x 50 mm (3.2 x 8.4 x 1.97 inch) | |
Mounting | panel or pole mounting |
Описание оборудования | ||
---|---|---|
&lambda/4 surge protection, N socket to N socket |
Mechanical specifications | ||
---|---|---|
Material | metal | |
Mass | approx. 43 g | |
Dimensions | 34 x 26.5 mm |
Mechanical specifications | ||
---|---|---|
Material | metal | |
Mass | 29 g | |
Dimensions | 24 x 26.5 mm |
Mechanical specifications | ||
---|---|---|
Material | metal | |
Mass | approx. 27 g | |
Dimensions | 23 x 26.5 mm |
Mechanical specifications | ||
---|---|---|
Material | metal | |
Mass | approx. 84 g | |
Dimensions | 34 x 33.5 mm |
Supply | ||
---|---|---|
Rated voltage | 3.6 V DC , battery operated | |
Power dissipation/power consumption | < 0.09 W | |
Input | ||
Connection | terminals 1, 2, 3, 4 | |
RTD | type Pt100, Pt1000 (IEC 751: 1995 GOST: alpha = 0.391) | |
Connection | 2-wire: 2 sensors, 3- or 4-wire: 1 sensor | |
Lead resistance | max. 10 &Omega | |
Measuring circuit monitoring | sensor breakage | |
Thermocouples | type E, J, K, T (IEC 584-1) | |
Cold junction compensation | internal , external | |
Measuring circuit monitoring | sensor breakage | |
Measurement range | type K: -270 ... 1370 °C type T: -270 ... 400 °C type E: -270 ... 1000 °C type J: -210 ... 1200 °C | |
Resistor | ||
Measurement range | 0 ... 500 &Omega , 0 ... 4000 &Omega | |
Voltage | mV Input | |
Measurement range | -100 ... 100 mV , 0 ... 300 mV | |
Input resistance | &ge 1 M&Omega | |
Output | ||
Output variables | PV: input 1 (°C, &Omega, mV) SV: input 2 (°C, &Omega, mV) TV: CJC temperature (°C) estimated battery life (days) battery voltage (volts) residual battery capacity (%) | |
Transfer characteristics | ||
Accuracy | - internal cold junction compensation error ± 1,5 °C (typ. acc. to IEC 61298-3) - external cold junction compensation error ± 1 °C (typ.) - resolution error < 0.1 °C - accuracy TC ± 20 µV - accuracy RTD: ± 100 m&Omega | |
Indicators/settings | ||
Parameter assignment | - sampling period: 1, 2, 5, 10, 30 seconds or 1, 2, 5, 10, 30, 60 minutes - transmit power: configurable 0 dBm or 10 dBm (EIRP) - sensor type - mapping of input measuring values 1 and 2 into primary variable (PV) and secondary variable (SV) - publishing of up to three messages from the device, transmission rate selectable from 4 seconds to 60 minutes | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Accuracy | IEC 61298-3 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP65 | |
Mass | approx. 1000 g | |
Dimensions | 77 x 129 x 177 mm (3 x 5.08 x 6.97 inch) | |
Mounting | panel or pole mounting | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | IMQ 09 ATEX 008X | |
Group, category, type of protection | II 2(1)G Ex ia [ia] IIC T4 | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2006, EN 60079-11:2007, EN 60079-26:2007 | |
International approvals | ||
FM approval | CoC 3042534 | |
IECEx approval | IECEx INE 09.0025X | |
Approved for | Ex ia IIC T4 | |
Accessories | ||
Designation | battery W-BAT-B1-Li mandatory for use in connection with hazardous areas (order separately) Mounting set W-ACC-F7MK External cold junction compensation W-ACC-CJC |
Supply | ||
---|---|---|
Rated voltage | 20 ... 30 V DC SELV/PELV | |
Power consumption | < 5 W | |
External bus | ||
Connection | screw terminals for - 0.2 ... 4 mm2 (rigid wire) - 0.2 ... 2.5 mm2 (flexible wire) | |
Interface 1 | Ethernet 10 BASE-T/100 BASE-TX , full galvanic isolation | |
Protocol | HART UDP, MODBUS TCP | |
Interface 2 | RS-485 | |
Protocol | HART, MODBUS RTU | |
Transfer rate | max. 115 kBit/s | |
Galvanic isolation | ||
Interface/interface | basic insulation according to IEC 61140, rated insulation voltage 50 Veff | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300328: V2.1.1 EN 301489-17: V1.3.2 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66/IP67 | |
Mass | approx. 1 kg | |
Dimensions | 258 mm x 114 mm x 84 mm without antenna and cable glands | |
Mounting | panel mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | FM 12 ATEX 0061 | |
Marking | II 3 G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
International approvals | ||
FM approval | Coc3042646 | |
Approved for | NI Class I, Div. 2, GPS A-D NI Class II, Class III, Div. 2, GPS E-G | |
IECEx approval | IECEx FMG 12.0002 | |
Approved for | Ex nA IIC T4 Gc , Ex nAc T4 |
Товаров: 0
На сумму: 0