Товаров: 0
На сумму: 0
Supply | ||
---|---|---|
Rated voltage | 7 ... 32 V DC | |
Rated current | < 1 mA , max. 25 mA | |
Electrical specifications | ||
Output rated operating current | 3.2 ... 25 mA | |
Supply | loop power for field devices voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V | |
Input | ||
Connection | - 5 wires, 600 mm long, exiting from male thread NPT1/2 - 1 external grounding point | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | up to 8 HART field devices (depending on installation) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013+A11:2013 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300 328 V1.8.1:2012 EN 301 489-1 V1.9.2:2011 EN 301 489-17 V2.2.1:2012-09 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Material | Aluminum alloy with polyurethane enamel paint | |
Mass | 460 g | |
Dimensions | 60.8 x 60.8 x 100 mm (l x w x h) | |
Data for application in connection with hazardous areas | ||
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
Производитель | Pepperl+Fuchs |
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
Запасные части и комплектующие подбираются самостоятельно покупателем строго по каталожным номерам из официальных деталировок производителей. В случае, если номенклатура товара совпадает с фактически поставленной, но не подходит на оборудование - в ее замене или возврате может быть отказано.
Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Основная валюта на сайте указана в долларах. Счета выставляются в рублях по курсу ЦБ РФ +3% на дату выставления счета.
Минимальный счет на запчасти (без учета доставки):
Наличие и срок поставки запчастей уточняйте у Вашего менеджера. Если Ваш заказ получается меньше суммы минимального счета, то цена на запчасти может быть увеличена. Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Условия платежа - 100% предоплата, если иное не оговорено в договоре.
Оплата по счету
Мы выставляем счёт на вашу организацию и отправляем его по электронной почте. Если вы в первый раз покупаете через нашу компанию, то присылайте реквизиты на почту info@zipstore.ru. Как только мы увидим деньги на нашем расчетном счете и подготовим груз к отправке - мы с Вами свяжемся по электронной почте, на которую выставлен счет.
Перед получением товара, убедитесь в его готовности к отгрузке у Вашего менеджера.
1) Самовывоз из Москвы
Необходимо заранее согласовать время получение товара с менеджером и иметь при себе доверенность от организации установленного образца или круглую печать.
Склад находится по адресу: 127282, г. Москва, ул. Полярная, д. 33, стр. 3, 2-ой этаж, помещение 3
Чтобы не заблудиться, можете распечатать схему проезда.
2) Доставка транспортной компанией
Товары отгружаются покупателю в течение недели после поступления денежных средств на расчетный счет Продавца, если иное не оговорено в счете. Мы бесплатно доставляем Ваш заказ до транспортной компании "Деловые Линии" в г. Москве при заказе от 50 000 рублей за запчасти. Услуги межтерминальной перевозки Вы оплачиваете самостоятельно при получении груза. Найти ближайший к Вам терминал "Деловых линий" для выдачи посылок можно здесь.
3) Самовывоз из 118 пунктов выдачи в других городах России
Оплата за доставку при получении. Найдите ближайший терминал выдачи посылок на карте.
4) Доставка по Москве
Минимальная стоимость доставки курьером по г. Москве составляет 600 рублей.
В нашей компании Вы можете выбрать удобный для Вас способ доставки груза:
1) Организация доставки силами Zipstore.ru
Мы самостоятельно вызываем для Вас ТК "Деловые Линии". Груз передается водителю или курьеру ТК, при наличии у него транспортной накладной на товар. Для заказа транспортной компании нашими силами, Вам необходимо написать письмо на электронную почту Вашего менеджера, в котором указать:
2) Организация доставки Вашими силами
Через любую Транспортную компанию (далее ТК), которую Вы вызываете к нам своими силами. Груз передается водителю или курьеру ТК, при наличии у него транспортной накладной на товар.
3) Отправка через ЕМS почту силами Zipstore.ru
Если Вы выбрали этот вариант, то стоимость услуги за перевозку включается в счет за товар, так как оплата курьеру ЕМS почты осуществляется наличными и только при отправке груза. Таким образом, в дальнейшем Вам не придется оплачивать отдельные счета ТК.
Для заказа EMS нашими силами, Вам необходимо написать письмо на электронную почту Вашего менеджера, в котором указать:
1. Качество Оборудования должно соответствовать техническим характеристикам, изложенным в инструкции по эксплуатации Оборудования.
2. Продавец гарантирует отсутствие производственных дефектов в поставленном Оборудовании в течение гарантийного периода.
3. Гарантийный период на Оборудование составляет 12 месяцев, на оригинальные запасные части 3 месяца, на аналоги 1 месяц, если иное не предусмотрено Спецификацией.
4. Претензии к внешнему виду товара принимаются в течение 2-х недель, с момента отгрузки товара.
5. Гарантия не распространяется на запчасти для технологического и ресторанного оборудования, интерфейсы (последовательного и Ethernet), материнские платы Godex, расходные материалы.
6. Если в течение гарантийного периода (п.3) Оборудование или его часть, указанные в Счете, окажутся дефектными, Продавец обязуется произвести ремонт или замену Оборудования или его части без оплаты Покупателем при соблюдении следующих условий:
6.1. Диагностика неисправности была проведена авторизованными специалистами производителя оборудования.
6.2. Покупатель письменно извещает Продавца об обнаруженных дефектах с их подробным описанием. Рекламация подписывается авторизованным специалистом.
6.3. Если дефекты не вызваны существенными нарушениями технических требований, оговоренных в инструкции по эксплуатации (в том числе нестабильностью параметров питающей электрической сети и отсутствием или ненадлежащим выполнением заземления Оборудования).
6.4. Если дефекты не вызваны вскрытием, ремонтом, модификацией или неправильным запуском Оборудования.
6.5. Если дефекты не вызваны повреждением вследствие действия на нее других неисправных частей.
6.6. Если отсутствуют видимые механические повреждения, в т.ч. сколы и царапины на нагревательной поверхности печатающих термоголовок (см. документ "Гарантийные обязательства на печатающие термоголовки").
6.7. Если дефекты не вызваны пожаром или затоплением помещения и не являются следствием неправильной эксплуатации Оборудования.
6.8. Если Специалистами Покупателя регулярно проводилось обслуживание Оборудования согласно инструкции по эксплуатации.
6.9. Если регулировка и настройка Оборудования проводилась Покупателем согласно инструкции по эксплуатации.
6.10. Если дефект не является следствием нормального износа быстроизнашивающихся деталей.
6.11. Если применялись расходные материалы, одобренные производителем.
6.12. Если оплата за товар произведена полностью.
7. При несоблюдении Покупателем условий, указанных в пп. 6.1.-6.12. , гарантия истекает немедленно.
8. Доставка гарантийного Оборудования производится силами и за счет Покупателя.
9. При невозможности замены бракованных Запчастей, неисправного Оборудования или неисправных частей Оборудования, возврат денежных средств производится в течении 14 рабочих дней, с момента заключения специалистами Продавца и оформления письма о возврате денежных средств Покупателем.
10. В случаях обнаружения брака (товара ненадлежащего качества) сразу необходимо упаковать товар, не пользоваться им, в течение ближайшего времени связаться с нами. Отправка товара ненадлежащего качества должна быть произведена в течении 5 дней с момента подтверждения брака Продавцом.
11. Возврат или обмен товара надлежащего качества остается на усмотрение Продавца, если иное не предусмотрено договором поставки (Закон о Защите Прав Потребителей не распространяется на взаимоотношения юридических лиц).
12. Должны быть сохранены упаковка товара (в чистом виде), товарный вид, потребительские свойства, пломбы, фабричные ярлыки, а также все полученные от продавца документы (чеки, бухгалтерские документы, инструкция по эксплуатации).
13. Денежные средства возвращаются тем же способом, которым был оплачен заказ.
14. Запчасти и расходные материалы для торгового, складского ресторанного и технологического оборудования не подлежат сертификации, по этой причине отказные письма не выдаются.
Все информационные материалы, представленные на сайте, носят справочный характер и не могут в полной мере передавать достоверную информацию о свойствах и характеристиках товара.
Фотография на сайте служит дополнительным источником для определения совместимости запчастей с Вашим оборудованием, и не может являться основным. Основной источник по совместимости запчастей - актуальная документация производителя оборудования, из которой значимой информацией для заказа являются: название запчасти и каталожный номер.
В случае возникновения вопросов, касающихся свойств и характеристик товара, перед оформлением счета обратитесь к нашим сотрудникам. Цены на сайте имеют информационный характер и могут отличаться от цен в коммерческом предложении.
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output rated operating current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Input | ||
Suitable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode | |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.3, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013, CLASS A | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300328 V2.1.1:2017 , EN 301489-17 V3.1.1:2017 , EN 301489-1 V2.1.1:2017 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
RoHs | ||
Directive 2011/65/EU (RoHS) | EN 50581:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | plastic | |
Mass | approx. 750 g | |
Dimensions | 92 x 89.5 x 92.8 mm (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-F8MK threads (NPT 1/2", NPT 3/4", G 1/2, M20) |
Supply | ||
---|---|---|
Rated voltage | 7 ... 30 V DC | |
Rated current | < 1 mA , max. 25 mA | |
Electrical specifications | ||
Output rated operating current | 3.2 ... 25 mA | |
Supply | loop power for field devices voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V | |
Input | ||
Connection | - 5 wires, 600 mm long, exiting from male thread NPT1/2 - 1 external grounding point | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | up to 8 HART field devices (depending on installation) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013+A11:2013 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300 328 V1.8.1:2012 EN 301 489-1 V1.9.2:2011 EN 301 489-17 V2.2.1:2012-09 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | temperature class T5: -40 ... 85 °C (-40 ... 185 °F) temperature class T6: -40 ... 75 °C (-40 ... 167 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Material | Aluminum alloy with polyurethane enamel paint | |
Mass | 460 g | |
Dimensions | 60.8 x 60.8 x 100 mm (l x w x h) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | FM 11 ATEX 0019 X | |
Marking | II 1 G Ex ia IIC T6/T5 Ga II 1 D Ex ia IIIC T95 °C Da | |
Certificate | FM 11 ATEX 0068 X | |
Marking | II 3 G Ex nA IIC T6/T5 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | CoC3040786(C) | |
Approved for | Class I, Zone 0, (A)Ex ia IIC T6/T5 Ga Class I, Zone 2, (A)Ex nA IIC T6/T5 Gc Class I, Zone 20, (A)Ex ia IIIC T95°C Da Class I, Division 1, Groups A - D Class II, Division 1, Groups E - G Class III Class I, Division 2, Groups A - D | |
IECEx approval | IECEx FMG 11.0010X | |
Approved for | Ex ia IIC T6/T5 Ga Ex nA IIC T6/T5 Gc Ex ia IIIC T95°C Da | |
Standards | IEC 60079-0:2011 , IEC 60079-11:2011 , IEC 60079-15:2010 |
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output rated operating current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Input | ||
Connectable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode | |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | plastic | |
Mass | approx. 750 g | |
Dimensions | 91 x 88.5 x 100.6 mm (3.6 x 3.5 x 4 inch) (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting versions see type code | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-MKF8 |
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output rated operating current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Input | ||
Connectable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode | |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | aluminum | |
Mass | approx. 1000 g | |
Dimensions | 91 x 88.5 x 100.6 mm (3.6 x 3.5 x 4 inch) (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting versions see type code | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | BVS 11 ATEX E 081 , for additional certificates see www.pepperl-fuchs.com | |
Group, category, type of protection, temperature class | II 2 G Ex ia IIC T4 Gb II 2 D Ex tb [ia] IIIC T70°C Db IP6x | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2009 , EN 60079-11:2007 , EN 60079-31:2009 | |
International approvals | ||
IECEx approval | BVS 11.0061 | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-MKF8 |
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output rated operating current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Input | ||
Suitable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode | |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.3, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013, CLASS A | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300328 V2.1.1:2017 , EN 301489-17 V3.1.1:2017 , EN 301489-1 V2.1.1:2017 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
RoHs | ||
Directive 2011/65/EU (RoHS) | EN 50581:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | Aluminum | |
Mass | approx. 1000 g | |
Dimensions | 92 x 89.5 x 92.8 mm (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 17 ATEX E 029 | |
Marking | II 2G Ex ia IIC T4/T3 Gb II 2D Ex tb [ia] IIIC T70°C Db | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0435 | |
IECEx approval | ||
IECEx certificate | IECEX BVS 17.0023 | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-F8MK threads (NPT 1/2", NPT 3/4", G 1/2, M20) |
Supply | ||
---|---|---|
Rated voltage | 7 ... 32 V DC | |
Rated current | < 1 mA , max. 25 mA | |
Electrical specifications | ||
Output rated operating current | 3.2 ... 25 mA | |
Supply | loop power for field devices voltage: 1 ... 2.5 V DC, adjustable in steps of 0.5 V | |
Input | ||
Connection | - 5 wires, 600 mm long, exiting from male thread NPT1/2 - 1 external grounding point | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | up to 8 HART field devices (depending on installation) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013+A11:2013 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300 328 V1.8.1:2012 EN 301 489-1 V1.9.2:2011 EN 301 489-17 V2.2.1:2012-09 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | temperature class T5: -40 ... 85 °C (-40 ... 185 °F) temperature class T6: -40 ... 75 °C (-40 ... 167 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP67 | |
Material | Aluminum alloy with polyurethane enamel paint | |
Mass | 460 g | |
Dimensions | 60.8 x 60.8 x 100 mm (l x w x h) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | FM 12 ATEX 0021 X | |
Marking | II 2 G Ex db IIC T6/T5 Gb II 2 D Ex tb IIIC T95°C Db | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | Coc3041762(C) | |
Approved for | Class I, Zone 1, (A)Ex db IIC T6/T5 Gb Class I, Zone 21, (A)Ex tb IIIC T95°C Db Class I, Division 1, Groups A - D Class II, Division 1, Groups E - G Class III | |
IECEx approval | IECEx FMG 12.0005X | |
Approved for | Ex db IIC T6/T5 Gb Ex tb IIIC T95°C Db | |
Standards | IEC 60079-0:2011 , IEC 60079-1:2014 , IEC 60079-31:2013 |
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output rated operating current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Input | ||
Suitable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode | |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.3, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013, CLASS A | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300328 V2.1.1:2017 , EN 301489-17 V3.1.1:2017 , EN 301489-1 V2.1.1:2017 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
RoHs | ||
Directive 2011/65/EU (RoHS) | EN 50581:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | plastic | |
Mass | approx. 750 g | |
Dimensions | 92 x 89.5 x 92.8 mm (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 17 ATEX E 029 | |
Marking | II 2G Ex ia IIC T4/T3 Gb | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | ||
IECEx certificate | IECEX BVS 17.0023 | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-F8MK threads (NPT 1/2", NPT 3/4", G 1/2, M20) |
Supply | ||
---|---|---|
Rated voltage | 7.2 V DC , battery operated | |
Electrical specifications | ||
Output rated operating current | 4 ... 20 mA | |
Supply | loop power for field devices voltage 8 ... 23 V DC, adjustable in steps of 0.1 V | |
Input | ||
Connectable field devices | usable for: - one point-to-point connection with a HART field device, or - one point-to-point connection with a 4 ... 20 mA field device, or - up to four externally powered HART field devices operating in multidrop mode | |
Connection | terminals 1, 2, 3, 4, 5, 6 multiple wirings available , depending on operating mode | |
Current | 4 ... 20 mA | |
HART communication | ||
Protocol | HART 7.1, backward compatible | |
Number of devices | - one passive 4 ... 20 mA/HART field device - up to 4 HART field devices in multidrop mode | |
Transfer rate | 1200 Bit/s | |
Parameters | primary/secondary master, preambles, retries and short address scan ranges | |
Output | ||
Output variables | PV: loop current SV, TV, QV:configurable according to user requirement - adapter: temperature, battery voltage, energy consumed and estimated battery life-time - 4 ... 20 mA device: scaled or linearized process value - HART device: up to four process variables | |
Transfer characteristics | ||
Accuracy | current input: 0.125 % of measuring range | |
Influence of ambient temperature | current input: 5 µA/K | |
Indicators/settings | ||
Parameter assignment | - wireless transmit power: configurable to 0 dBm or 10 dBm (EIRP) - device variables mapping - publishing of up to ten burst messages in a wireless network, period and trigger mode selectable - notification of up to five events from adapter and/or connected device(s) in a wireless network - scaling and linearization of 4 ... 20 mA signal of connected analog device - tuning of supply parameters for the connected device - locking/unlocking of device parameterization | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1:2006 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 99/5/EC | ETSI EN 300328: V1.7.1 (2006-10), ETSI EN 301489-17: V1.2.1 (2002-08), EN 60950:2001 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Vibration resistance | 20 ... 2000 Hz, 0,01 g2/Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Material | plastic | |
Mass | approx. 750 g | |
Dimensions | 91 x 88.5 x 100.6 mm (3.6 x 3.5 x 4 inch) (without cable glands and antenna) | |
Mounting | mounting on field device , panel or pole mounting versions see type code | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | BVS 11 ATEX E 081 , for additional certificates see www.pepperl-fuchs.com | |
Group, category, type of protection, temperature class | II 2 G Ex ia IIC T4 Gb | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0:2009 , EN 60079-11:2007 , EN 60079-31:2009 | |
International approvals | ||
IECEx approval | BVS 11.0061 | |
Accessories | ||
Designation | battery W-BAT-B2-Li mandatory for use in connection with hazardous areas (order separately) mounting set W-ACC-MKF8 |