Атол 30Ф не включается (заводской брак)
Валерий
14 января 2022
Supply | ||
---|---|---|
Rated voltage | 20 ... 30 V DC | |
Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
Power dissipation | 0.7 W , with Multiplexer | |
Reverse polarity protection | yes | |
HART signal channels (intrinsically safe) | ||
HART signal channels | ||
Number of channels | 32 unbalanced signal loops | |
Redundancy | ||
Supply | yes | |
Galvanic isolation | ||
HART signal channels | 30 V DC | |
Ambient conditions | ||
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
Relative humidity | 5 ... 90 %, non-condensing | |
Mechanical specifications | ||
Core cross-section | 2.5 mm2 (16 AWG) | |
Connection | field side: screw terminals control side: 56-pin Elco connector RS 485 interface: removable screw terminals power: removable screw terminals | |
Mass | approx. 500 g | |
Dimensions | without HiDMux2700: 254 x 107 x 79 mm (10 x 4.2 x 3.1 inch) with HiDMux2700: 254 x 107 x 208 mm (10 x 4.2 x 8.2 inch) | |
Mounting | DIN rail mounting |
Supply | ||
---|---|---|
Rated voltage | 20 ... 30 V DC | |
Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
Power dissipation | 0.7 W , with Multiplexer | |
Reverse polarity protection | yes | |
HART signal channels (intrinsically safe) | ||
HART signal channels | ||
Number of channels | 32 unbalanced signal loops | |
Redundancy | ||
Supply | yes | |
Galvanic isolation | ||
HART signal channels | 30 V DC | |
Ambient conditions | ||
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
Relative humidity | 5 ... 90 %, non-condensing | |
Mechanical specifications | ||
Core cross-section | 2.5 mm2 (16 AWG) | |
Connection | field side: screw terminals control side: 56-pin Elco connector RS 485 interface: removable screw terminals power: removable screw terminals | |
Mass | approx. 500 g | |
Dimensions | without HiDMux2700: 333 x 125 x 79 mm (13.1 x 4.9 x 3.1 inch) with Mux2700: 333 x 125 x 208 mm (13.1 x 4.9 x 8.2 inch) | |
Mounting | DIN rail mounting |
Supply | ||
---|---|---|
Rated voltage | 20 ... 30 V DC | |
Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
Power dissipation | 0.7 W , with Multiplexer | |
Reverse polarity protection | yes | |
HART signal channels (intrinsically safe) | ||
HART signal channels | ||
Number of channels | 32 unbalanced signal loops | |
Redundancy | ||
Supply | yes | |
Galvanic isolation | ||
HART signal channels | 30 V DC | |
Ambient conditions | ||
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
Relative humidity | 5 ... 90 %, non-condensing | |
Mechanical specifications | ||
Core cross-section | 2.5 mm2 (16 AWG) | |
Connection | field side: screw terminals control side: 56-pin Elco connector RS 485 interface: removable screw terminals power: removable screw terminals | |
Mass | approx. 500 g | |
Dimensions | without HiDMux2700: 333 x 125 x 79 mm (13.1 x 4.9 x 3.1 inch) with Mux2700: 333 x 125 x 208 mm (13.1 x 4.9 x 8.2 inch) | |
Mounting | DIN rail mounting |
Supply | ||
---|---|---|
Rated voltage | 20 ... 30 V DC | |
Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
Power dissipation | 0.7 W , with Multiplexer | |
Reverse polarity protection | no | |
HART signal channels (intrinsically safe) | ||
HART signal channels | ||
Number of channels | 32 unbalanced signal loops | |
Redundancy | ||
Supply | no | |
Galvanic isolation | ||
HART signal channels | 30 V DC | |
Ambient conditions | ||
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
Relative humidity | 5 ... 90 %, non-condensing | |
Mechanical specifications | ||
Core cross-section | 2.5 mm2 (16 AWG) | |
Connection | field side: screw terminals control side: KS connector (proprietary) RS 485 interface: removable screw terminals power: removable screw terminals | |
Mass | approx. 500 g | |
Dimensions | without HiDMux2700: 330 x 107 x 79 mm (12.9 x 4.2 x 3.1 inch) with HiDMux2700: 330 x 107 x 208 mm (12.9 x 4.2 x 8.2 inch) | |
Mounting | DIN rail mounting |
Supply | ||
---|---|---|
Rated voltage | 20 ... 30 V DC | |
Fusing | 3.15 A , 5 x 20 mm (0.2 x 0.8 inch) | |
Power dissipation | 0.7 W , with Multiplexer | |
Reverse polarity protection | no | |
HART signal channels (intrinsically safe) | ||
HART signal channels | ||
Number of channels | 32 unbalanced signal loops | |
Redundancy | ||
Supply | no | |
Galvanic isolation | ||
HART signal channels | 30 V DC | |
Ambient conditions | ||
Ambient temperature | 0 ... 55 °C (32 ... 131 °F) | |
Relative humidity | 5 ... 90 %, non-condensing | |
Mechanical specifications | ||
Core cross-section | 2.5 mm2 (16 AWG) | |
Connection | field side: screw terminals control side: KS connector (proprietary) RS 485 interface: removable screw terminals power: removable screw terminals | |
Mass | approx. 500 g | |
Dimensions | without HiDMux2700: 330 x 107 x 79 mm (12.9 x 4.2 x 3.1 inch) with HiDMux2700: 330 x 107 x 208 mm (12.9 x 4.2 x 8.2 inch) | |
Mounting | DIN rail mounting |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 19 ... 30 V DC | |
Rated current | approx. 120 mA at 24 V DC | |
Power dissipation | 2.3 W | |
Power consumption | 2.9 W | |
HART signal channels (intrinsically safe) | ||
Conformity | HART field device input (revision 5 to 7) | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 5, 6 | |
Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
Input resistance | 250 &Omega , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
Available voltage | &ge 15.5 V at 20 mA, short-circuit protected | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 , output II: terminals 13, 14, 15 , output III: terminals 19, 20, 21 | |
Output signal | analog | |
Current range | 4 ... 20 mA , (source or sink mode) | |
Load | max. 650 &Omega , source mode | |
Voltage range | 5 ... 30 V , sink mode from external supply | |
Fault signal | downscale I &le 2 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
Other outputs | HART communicator on terminals 22, 24 | |
Collective error message | Power Rail and LED red | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 | |
Marking | ![]() | |
Certificate | PF 07 CERT 1142 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
IECEx approval | ||
IECEx certificate | IECEx BAS 07.0047 | |
IECEx marking | [Ex ia] IIC , [Ex iaD] |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 19 ... 30 V DC | |
Rated current | approx. 130 mA at 24 V DC | |
Power dissipation | 2.5 W | |
Power consumption | 3.1 W | |
HART signal channels (intrinsically safe) | ||
Conformity | HART field device input (revision 5 to 7) | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 5, 6 | |
Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
Input resistance | 250 &Omega , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
Available voltage | &ge 15.5 V at 20 mA, short-circuit protected | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12, output II: terminals 16, 17, 18 output III: terminals 7, 8, 9, output IV: terminals 13, 14, 15, output V: terminals 19, 20, 21 | |
Output I, II | ||
Output signal | relay and LED yellow | |
Mechanical life | 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output III, IV, V | ||
Output signal | analog | |
Current range | 4 ... 20 mA , (source or sink mode) | |
Load | max. 650 &Omega , source mode | |
Voltage range | 5 ... 30 V , sink mode from external supply | |
Fault signal | downscale I &le 2 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
Other outputs | HART communicator on terminals 22, 24 | |
Collective error message | Power Rail and LED red | |
Transfer characteristics | ||
Relay | programmable either for fault or trip value (with direction, hysteresis and delay) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 | |
Marking | ![]() | |
Certificate | PF 07 CERT 1141 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
IECEx approval | ||
IECEx certificate | IECEx BAS 07.0047 | |
IECEx marking | [Ex ia] IIC , [Ex iaD] |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 19 ... 30 V | |
Rated current | approx. 140 mA at 24 V DC | |
Power dissipation | 2.7 W | |
Power consumption | 3.3 W | |
HART signal channels (intrinsically safe) | ||
Conformity | HART field device input (revision 5 to 7) | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 5, 6 | |
Open circuit voltage/short-circuit current | typ. 24 V / 28 mA | |
Input resistance | 250 &Omega , 5 % (terminals 2, 3 and with jumper on 5, 6) | |
Available voltage | &ge 15.5 V at 20 mA, short-circuit protected | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, output II: terminals 11, 12, output III: terminals 16, 17, output IV: terminals 17, 18 output V: terminals 7, 8, 9, output VI: terminals 13, 14, 15, output VII: terminals 19, 20, 21 | |
Output I, II, III, IV | ||
Output signal | relay and LED yellow | |
Mechanical life | 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output V, VI, VII | ||
Output signal | analog | |
Current range | 4 ... 20 mA , (source or sink mode) | |
Load | max. 650 &Omega , source mode | |
Voltage range | 5 ... 30 V , sink mode from external supply | |
Fault signal | downscale I &le 2 mA, upscale I &ge 21.5 mA (acc. NAMUR NE43) or hold measurement value | |
Other outputs | HART communicator on terminals 22, 24 | |
Collective error message | Power Rail and LED red | |
Transfer characteristics | ||
Relay | programmable either for fault or trip value (with direction, hysteresis and delay) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BASEEFA 07 ATEX 0174 | |
Marking | ![]() | |
Certificate | PF 07 CERT 1141 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0129 | |
IECEx approval | ||
IECEx certificate | IECEx BAS 07.0047 | |
IECEx marking | [Ex ia] IIC , [Ex iaD] |
Товаров: 0
На сумму: 0