| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 0.6 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Input | ||
| Input resistance | 500 k&Omega | |
| Digital input | ||
| Number of channels | 15 | |
| Connection | channel I: 1+, 16- channel II: 2+, 16- channel III: 3+, 16- channel IV: 4+, 16- channel V: 5+, 16- channel VI: 6+, 16- channel VII: 7+, 16- channel VIII: 8+, 16- channel IX: 9+, 16- channel X: 10+, 16- channel XI: 11+, 16- channel XII: 12+, 16- channel XIII: 13+, 16- channel XIV: 14+, 16- channel XV: 15+, 16- | |
| Digital signals (active) | AC 95 ... 230 V (250 V max.) in-phase | |
| Switching point: ON | 90 V | |
| Switching point: OFF | 55 V | |
| Minimum pulse duration | 2 periods | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: communication fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 130 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| International approvals | ||
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 0.6 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Input | ||
| Input resistance | 10 k&Omega | |
| Digital input | ||
| Number of channels | 15 | |
| Connection | channel I: 9+, 8- channel II: 10+, 8- channel III: 11+, 8- channel IV: 12+, 8- channel V: 13+, 8- channel VI: 14+, 8- channel VII: 15+, 8- channel VIII: 16+, 8- channel IX: 1+, 8- channel X: 2+, 8- channel XI: 3+, 8- channel XII: 4+, 8- channel XIII: 5+, 8- channel XIV: 6+, 8- channel XV: 7+, 8- | |
| Digital signals (active) | DC 24 V (30 V max.) | |
| Switching point: ON | < 12 V | |
| Switching point: OFF | > 2 V | |
| Minimum pulse duration | 40 ms | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Status LED (I) red: communication error | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 130 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ic] IIC T4 Gc | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 0.5 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 2 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 1+, 2/3- channel II: 4+, 5/6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 20 ms | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Status LED (1, 3) red: line fault (per channel) Status LED (2, 4) yellow: signal (per channel) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 110 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC | |
| Input | ||
| Voltage | 12.6 V | |
| Current | 12.8 mA | |
| Power | 40.1 mW (linear characteristic) | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PTB 03 ATEX 2042 | |
| UL approval | E106378 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 0.5 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 3 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 1+, 4- channel II: 2+, 5- channel III: 3+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 20 ms | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault, per channel LED yellow: signal (status), per channel | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC | |
| Input | ||
| Voltage | 10.5 V | |
| Current | 35 mA | |
| Power | 92 mW | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X PTB 03 ATEX 2042 | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 0.7 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 8 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection | channel I: 1+, 2- channel II: 3+, 4- channel III: 5+, 6- channel IV: 7+, 8- channel V: 9+, 10- channel VI: 11+, 12- channel VII: 13+, 14- channel VIII: 15+, 16- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Status LED (I) red: line fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 130 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC | |
| Input | ||
| Voltage | 14.9 V | |
| Current | 15.7 mA | |
| Power | 58.2 mW (linear characteristic) | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PTB 03 ATEX 2042 | |
| UL approval | E106378 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 1.2 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 8 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection | Terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8-, 9+, 10-, 11+, 12-, 13+,14-, 15+, 16- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 15 ms | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-8) red: line fault (lead breakage or short circuit) , yellow: signal (per channel) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with spring terminal (0.14 ... 0.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | EXA 13 ATEX 0036X | |
| Marking | II 3(1) G Ex nA [ia Ga] IIC T4 Gc I (M1) [Ex ia Ma] I II (1) D [Ex ia Da] IIIC | |
| Input | ||
| Voltage | 10 V | |
| Current | 12 mA | |
| Power | 30 mW (linear characteristic) | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2011 EN 60079-11:2011 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | EXA 13 ATEX 0036X | |
| UL approval | E106378 | |
| IECEx approval | EXA 13.0003X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 2 W | |
| Power consumption | 3 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Analog input | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | pressure converter | |
| Field device [2] | flow converter | |
| Field device [3] | level converter | |
| Field device [4] | Temperature Converter | |
| Field device interface | ||
| Connection | 2-wire transmitter | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
| Input resistance | 15 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: > 21 mA Can be parameterized in the range 0 ... 22 mA | |
| Open-circuit | factory setting: < 3.6 mA Can be parameterized in the range 0 ... 22 mA | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Analog output | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | Proportional Valve | |
| Field device [2] | I/P converters | |
| Field device [3] | on-site display | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: < 50 &Omega configurable between 0 ... 26 mA | |
| Open-circuit | deviation of preset output value > 0.5 mA | |
| Load | 750 &Omega max. | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Watchdog | output off 0.5 s after serious fault | |
| Digital input | ||
| Number of channels | 4 | |
| Sensor interface | ||
| Connection [2] | volt-free contact | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Digital signals (active) | ||
| Switching point: ON | > 2.1 mA | |
| Switching point: OFF | < 1.2 mA | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) | |
| Short-circuit | > 7 mA | |
| Open-circuit | < 0.1 mA | |
| Digital output | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8- | |
| Drive capability | 12 V / 22 mA | |
| Open loop voltage | min. 22.7 V | |
| Current limit | 22 mA | |
| Internal resistor | 385 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Test current | 0.4 mA | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | < 0.2 mA | |
| Transfer characteristics | ||
| Deviation | ||
| After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
| Refresh time | approx. 100 ms (4 channels) | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Configuration LED (AI, AO, DI, DO) white: selected channel mode | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2000 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 100 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | BVS 12 ATEX E 115 X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Galvanic isolation | ||
| Rated voltage | 250 V field circuits to control and supply circuits | |
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | BVS 12 ATEX E 115 X | |
| IECEx approval | BVS 11.0068X | |
| Approved for | Ex nAc [ic] IIC T4 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 2 W | |
| Power consumption | 3 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Analog input | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | pressure converter | |
| Field device [2] | flow converter | |
| Field device [3] | level converter | |
| Field device [4] | Temperature Converter | |
| Field device interface | ||
| Connection | 2-wire transmitter | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
| Input resistance | 15 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: > 21 mA Can be parameterized in the range 0 ... 22 mA | |
| Open-circuit | factory setting: < 3.6 mA Can be parameterized in the range 0 ... 22 mA | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Analog output | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | Proportional Valve | |
| Field device [2] | I/P converters | |
| Field device [3] | on-site display | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: < 50 &Omega configurable between 0 ... 26 mA | |
| Open-circuit | deviation of preset output value > 0.5 mA | |
| Load | 750 &Omega max. | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Watchdog | output off 0.5 s after serious fault | |
| Digital input | ||
| Number of channels | 4 | |
| Sensor interface | ||
| Connection [2] | volt-free contact | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Digital signals (active) | ||
| Switching point: ON | > 2.1 mA | |
| Switching point: OFF | < 1.2 mA | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) | |
| Short-circuit | > 7 mA | |
| Open-circuit | < 0.1 mA | |
| Digital output | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8- | |
| Drive capability | 12 V / 22 mA | |
| Open loop voltage | min. 22.7 V | |
| Current limit | 22 mA | |
| Internal resistor | 385 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Test current | 0.4 mA | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | < 0.2 mA | |
| Transfer characteristics | ||
| Deviation | ||
| After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
| Refresh time | approx. 100 ms (4 channels) | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Configuration LED (AI, AO, DI, DO) white: selected channel mode | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2000 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 100 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BVS 11 ATEX E 116 X | |
| Marking | II 3(1) G Ex nA [ia Ga] IIC T4 Gc I (M1) [Ex ia Ma] I II (1) D [Ex ia Da] IIIC | |
| Input | ||
| Voltage | 27 V | |
| Current | 87 mA | |
| Power | 575 mW (linear characteristic) | |
| Output | ||
| Voltage | 27 V | |
| Current | 87 mA | |
| Power | 575 mW (linear characteristic) | |
| Galvanic isolation | ||
| Rated voltage | 250 V field circuits to control and supply circuits | |
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 60079-26:2007 EN 61241-11:2006 EN 50303:2000 | |
| International approvals | ||
| ATEX approval | BVS 11 ATEX E 116X | |
| UL approval | E106378 | |
| IECEx approval | BVS 11.0068X | |
| Approved for | Ex nAc [ia] IIC T4 [Ex ia] IIIC [Ex ia] I | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 1.8 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 2 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 2+, 5- channel II: 3+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Digital output | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4- | |
| Open loop voltage | 24 V | |
| Current limit | 75 mA | |
| Internal resistor | 210 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 110 &Omega | |
| Open-circuit | > 1.2 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault, per channel LED yellow: signal (status), per channel | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 110 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Input | ||
| Voltage | 14 V | |
| Current | 16 mA | |
| Power | 55 mW (linear characteristic) | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Output | ||
| Voltage | 27.8 V | |
| Current | 183 mA | |
| Power | 1270 mW | |
| Internal capacitance | 3.3 µF | |
| Internal inductance | 0 mH | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA [ic] IIB T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ic] IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | Use only in connection with the power supplies LB9*** | |
| Power dissipation | 1.3 W | |
| Power consumption | 1.8 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 2 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 2+, 5- channel II: 3+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Digital output | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4- | |
| Open loop voltage | 23 V | |
| Current limit | 50 mA | |
| Internal resistor | 258 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | > 10 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (O: output, I1: input 1, I2: input 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 150 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | EXA 16 ATEX 0035X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Input | ||
| Voltage | 10 V | |
| Current | 13 mA | |
| Power | 33 mW (linear characteristic) | |
| Internal capacitance | 1.2 nF | |
| Internal inductance | 0 mH | |
| Output | ||
| Voltage | 24.2 V | |
| Current | 108 mA | |
| Power | 654 mW | |
| Internal capacitance | 12 nF | |
| Internal inductance | 0 mH | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | EXA 16 ATEX 0035X | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | Use only in connection with the power supplies LB9*** | |
| Power dissipation | 1.3 W | |
| Power consumption | 1.8 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 2 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 2+, 5- channel II: 3+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Digital output | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4- | |
| Open loop voltage | 16.5 V | |
| Current limit | 50 mA | |
| Internal resistor | 131 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | > 10 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (O: output, I1: input 1, I2: input 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 110 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | EXA 16 ATEX 0035X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Input | ||
| Voltage | 10 V | |
| Current | 13 mA | |
| Power | 33 mW (linear characteristic) | |
| Internal capacitance | 1.2 nF | |
| Internal inductance | 0 mH | |
| Output | ||
| Voltage | 17.8 V | |
| Current | 162 mA | |
| Power | 721 mW | |
| Internal capacitance | 12 nF | |
| Internal inductance | 0 mH | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | EXA 16 ATEX 0035X | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 1.3 W | |
| Power consumption | 1.6 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 2 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 2+, 5- channel II: 3+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Digital output | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4- | |
| Open loop voltage | 22 V | |
| Current limit | 50 mA | |
| Internal resistor | 315 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 20 &Omega | |
| Open-circuit | > 2 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault, per channel LED yellow: signal (status), per channel | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 110 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC | |
| Input | ||
| Voltage | 14 V | |
| Current | 16 mA | |
| Power | 55 mW (linear characteristic) | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Output | ||
| Voltage | 24.9 V | |
| Current | 91 mA | |
| Power | 558 mW | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X PTB 03 ATEX 2042 | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 1.8 W | |
| Power consumption | 2.4 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 2 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 2+, 5- channel II: 3+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Digital output | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4- | |
| Open loop voltage | 24 V | |
| Current limit | 75 mA | |
| Internal resistor | 210 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 110 &Omega | |
| Open-circuit | > 1.2 k&Omega | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault, per channel LED yellow: signal (status), per channel | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 110 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (1) G [Ex ia] IIB II (1) D [Ex ia] IIIC | |
| Input | ||
| Voltage | 14 V | |
| Current | 16 mA | |
| Power | 55 mW (linear characteristic) | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Output | ||
| Voltage | 27.8 V | |
| Current | 183 mA | |
| Power | 1270 mW | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIB T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X PTB 03 ATEX 2042 | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 1.4 W | |
| Power consumption | 1.7 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 2 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 2+, 5- channel II: 3+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Digital output | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4- | |
| Open loop voltage | 24 V | |
| Current limit | 50 mA | |
| Internal resistor | 360 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 70 &Omega | |
| Open-circuit | > 2 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault, per channel LED yellow: signal (status), per channel | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 110 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC | |
| Input | ||
| Voltage | 14 V | |
| Current | 16 mA | |
| Power | 55 mW (linear characteristic) | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Output | ||
| Voltage | 27.8 V | |
| Current | 91.5 mA | |
| Power | 636 mW | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X PTB 03 ATEX 2042 | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 1 W | |
| Power consumption | 1.6 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 2 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 2+, 5- channel II: 3+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Digital output | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4- | |
| Open loop voltage | 22 V | |
| Current limit | 50 mA | |
| Internal resistor | 220 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 220 &Omega | |
| Open-circuit | > 1.3 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault, per channel LED yellow: signal (status), per channel | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 110 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC | |
| Input | ||
| Voltage | 14 V | |
| Current | 16 mA | |
| Power | 55 mW (linear characteristic) | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Output | ||
| Voltage | 24.2 V | |
| Current | 145 mA | |
| Power | 872 mW | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X PTB 03 ATEX 2042 | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 1.3 W | |
| Power consumption | 1.8 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 2 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 2+, 5- channel II: 3+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Digital output | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4- | |
| Open loop voltage | 25.3 V | |
| Current limit | 75 mA | |
| Internal resistor | 329 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 25 &Omega | |
| Open-circuit | > 3.5 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault, per channel LED yellow: signal (status), per channel | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 110 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC | |
| Input | ||
| Voltage | 14 V | |
| Current | 16 mA | |
| Power | 55 mW (linear characteristic) | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Output | ||
| Voltage | 27.8 V | |
| Current | 108 mA | |
| Power | 751 mW | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X PTB 03 ATEX 2042 | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 1.5 W | |
| Power consumption | 1.5 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 2 | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 2+, 5- channel II: 3+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Digital output | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4- | |
| Open loop voltage | 26.7 V | |
| Current limit | 50 mA | |
| Internal resistor | 509 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 40 &Omega | |
| Open-circuit | > 7 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault, per channel LED yellow: signal (status), per channel | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 110 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (1) G [Ex ia] IIC II (1) D [Ex ia] IIIC | |
| Input | ||
| Voltage | 14 V | |
| Current | 16 mA | |
| Power | 55 mW (linear characteristic) | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Output | ||
| Voltage | 28.7 V | |
| Current | 68 mA | |
| Power | 485 mW | |
| Internal capacitance | 1.65 µF | |
| Internal inductance | 0 mH | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X PTB 03 ATEX 2042 | |
| UL approval | E106378 | |
| Control drawing | 116-0321 | |
| Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ia Ga] IIC T4 Gc [Ex ia Da] IIIC | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | Use only in connection with the power supplies LB9*** | |
| Power dissipation | 1.3 W | |
| Power consumption | 1.8 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 2+, 5- channel II: 3+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Digital output | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4- | |
| Open loop voltage | 23 V | |
| Current limit | 50 mA | |
| Internal resistor | 258 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | > 10 k&Omega | |
| Response time | 10 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (O: output, I1: input 1, I2: input 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 150 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | EXA 16 ATEX 0025X | |
| Marking | II 3(1) G Ex nA [ia Ga] IIC T4 Gc II (1) D [Ex ia Da] IIICI (M1) [Ex ia Ma] I | |
| Input | ||
| Voltage | 10 V | |
| Current | 13 mA | |
| Power | 33 mW (linear characteristic) | |
| Internal capacitance | 1.2 nF | |
| Internal inductance | 0 mH | |
| Output | ||
| Voltage | 24.2 V | |
| Current | 108 mA | |
| Power | 654 mW | |
| Internal capacitance | 12 nF | |
| Internal inductance | 0 mH | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | EXA 16 ATEX 0025X | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | Use only in connection with the power supplies LB9*** | |
| Power dissipation | 1.3 W | |
| Power consumption | 1.8 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 2+, 5- channel II: 3+, 6- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | 1 ms | |
| Digital output | ||
| Number of channels | 1 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4- | |
| Open loop voltage | 16.5 V | |
| Current limit | 50 mA | |
| Internal resistor | 131 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | > 10 k&Omega | |
| Response time | 10 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (O: output, I1: input 1, I2: input 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 110 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | EXA 16 ATEX 0025X | |
| Marking | II 3(1) G Ex nA [ia Ga] IIC T4 Gc II (1) D [Ex ia Da] IIICI (M1) [Ex ia Ma] I | |
| Input | ||
| Voltage | 10 V | |
| Current | 13 mA | |
| Power | 33 mW (linear characteristic) | |
| Internal capacitance | 1.2 nF | |
| Internal inductance | 0 mH | |
| Output | ||
| Voltage | 17.8 V | |
| Current | 162 mA | |
| Power | 751 mW | |
| Internal capacitance | 12 nF | |
| Internal inductance | 0 mH | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | EXA 16 ATEX 0025X | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 2.2 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 8 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 2- channel II: 3+, 4- channel III: 5+, 6- channel IV: 7+, 8- channel V: 9+, 10- channel VI: 11+, 12- channel VII: 13+, 14- channel VIII: 15+, 16- | |
| Current limit | 8 mA | |
| Open loop voltage | 20 V | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Test current | 0.33 mA | |
| Short-circuit | < 300 &Omega | |
| Open-circuit | > 50 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault , red flashing: communication error | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 160 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Output | ||
| Voltage | 28 V | |
| Current | 13.5 mA | |
| Power | 376 mW | |
| Internal capacitance | 3.6 nF | |
| Internal inductance | 0 mH | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ic] IIC T4 Gc | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Supply | ||
|---|---|---|
| Connection | backplane bus | |
| Rated voltage | Use only in connection with the power supplies LB9*** | |
| Power dissipation | 2 W | |
| Power consumption | 3 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 2 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4/5/6/8- channel II: 7+, 4/5/6/8- | |
| Current limit | 40 mA both channels parallel 80 mA | |
| Internal resistor | 258 &Omega , both channels parallel 129 &Omega | |
| Open loop voltage | 23 V , both channels parallel 23 V | |
| Line fault detection | can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | > 10 k&Omega | |
| Response time | 10 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1, 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Mode LED (M) white: Parallel operation of outputs | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 150 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | EXA 16 ATEX 0035X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Output | ||
| Voltage | 24.2 V | |
| Current | 108 mA | |
| Power | 654 mW | |
| Internal capacitance | 12 nF | |
| Internal inductance | 0 mH | |
| Output (both channels parallel) | ||
| Voltage | 24.2 V | |
| Current | 216 mA | |
| Power | 1307 mW | |
| Internal capacitance | 24 nF | |
| Internal inductance | 0 mH | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | EXA 16 ATEX 0035X | |
| Supply | ||
|---|---|---|
| Connection | backplane bus | |
| Rated voltage | Use only in connection with the power supplies LB9*** | |
| Power dissipation | 1.5 W | |
| Power consumption | 2.5 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 2 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4/5/6/8- channel II: 7+, 4/5/6/8- | |
| Current limit | 50 mA both channels parallel 100 mA | |
| Internal resistor | 131 &Omega , both channels parallel 66 &Omega | |
| Open loop voltage | 16.5 V , both channels parallel 16.5 V | |
| Line fault detection | can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | > 10 k&Omega | |
| Response time | 10 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1, 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Mode LED (M) white: Parallel operation of outputs | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 150 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | EXA 16 ATEX 0035X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Output | ||
| Voltage | 17.8 V | |
| Current | 162 mA | |
| Power | 721 mW | |
| Internal capacitance | 12 nF | |
| Internal inductance | 0 mH | |
| Output (both channels parallel) | ||
| Voltage | 17.8 V | |
| Current | 324 mA | |
| Power | 1442 mW | |
| Internal capacitance | 24 nF | |
| Internal inductance | 0 mH | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | EXA 16 ATEX 0035X | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 2.2 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 8 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 2- channel II: 3+, 4- channel III: 5+, 6- channel IV: 7+, 8- channel V: 9+, 10- channel VI: 11+, 12- channel VII: 13+, 14- channel VIII: 15+, 16- | |
| Current limit | 8 mA | |
| Open loop voltage | 20 V | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Test current | 0.33 mA | |
| Short-circuit | < 300 &Omega | |
| Open-circuit | > 50 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault , communication error red flashing | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 160 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (2) G [Ex ib] IIC II (2) D [Ex ib] IIIC | |
| Output | ||
| Voltage | 28 V | |
| Current | 13.5 mA | |
| Power | 376 mW (characteristic curve rectangular type) | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X PTB 03 ATEX 2042 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ib Gb] IIC T4 Gc [Ex ib Db] IIIC | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 2 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 2.2 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 8 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 2- channel II: 3+, 4- channel III: 5+, 6- channel IV: 7+, 8- channel V: 9+, 10- channel VI: 11+, 12- channel VII: 13+, 14- channel VIII: 15+, 16- | |
| Current limit | 5.2 mA | |
| Open loop voltage | 21.6 V | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Test current | 0.33 mA | |
| Short-circuit | < 300 &Omega | |
| Open-circuit | > 50 k&Omega | |
| Response time | 20 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | LED green: supply LED red: line fault , communication error red flashing | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 160 g | |
| Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | PTB 03 ATEX 2042 | |
| Marking | II (2) G [Ex ib] IIC II (2) D [Ex ib] IIIC | |
| Output | ||
| Voltage | 30 V | |
| Current | 13.5 mA | |
| Power | 404 mW (characteristic curve rectangular type) | |
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA IIC T4 Gc | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | PF 08 CERT 1234 X PTB 03 ATEX 2042 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ib Gb] IIC T4 Gc [Ex ib Db] IIIC | |
| EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| American Bureau of Shipping | T1450280/UN | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Supply | ||
|---|---|---|
| Connection | backplane bus | |
| Rated voltage | Use only in connection with the power supplies LB9*** | |
| Power dissipation | 2 W | |
| Power consumption | 3 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 2 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4/5/6/8- channel II: 7+, 4/5/6/8- | |
| Current limit | 40 mA both channels parallel 80 mA | |
| Internal resistor | 258 &Omega , both channels parallel 129 &Omega | |
| Open loop voltage | 23 V , both channels parallel 23 V | |
| Line fault detection | can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | > 10 k&Omega | |
| Response time | 10 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1, 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Mode LED (M) white: Parallel operation of outputs | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 150 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | EXA 16 ATEX 0025X | |
| Marking | II 3(1) G Ex nA [ia Ga] IIC T4 Gc II (1) D [Ex ia Da] IIICI (M1) [Ex ia Ma] I | |
| Output | ||
| Voltage | 24.2 V | |
| Current | 108 mA | |
| Power | 654 mW | |
| Internal capacitance | 12 nF | |
| Internal inductance | 0 mH | |
| Output (both channels parallel) | ||
| Voltage | 24.2 V | |
| Current | 216 mA | |
| Power | 1307 mW | |
| Internal capacitance | 24 nF | |
| Internal inductance | 0 mH | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | EXA 16 ATEX 0025X | |
| Supply | ||
|---|---|---|
| Connection | backplane bus | |
| Rated voltage | Use only in connection with the power supplies LB9*** | |
| Power dissipation | 1.5 W | |
| Power consumption | 2.5 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital output | ||
| Number of channels | 2 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | channel I: 1+, 4/5/6/8- channel II: 7+, 4/5/6/8- | |
| Current limit | 50 mA both channels parallel 100 mA | |
| Internal resistor | 131 &Omega , both channels parallel 66 &Omega | |
| Open loop voltage | 16.5 V , both channels parallel 16.5 V | |
| Line fault detection | can be switched on/off for each channel via configuration tool also when turned off (every 2.5 s the valve is turned on for 2 ms) | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | > 10 k&Omega | |
| Response time | 10 ms (depending on bus cycle time) | |
| Watchdog | within 0.5 s the device goes in safe state, e.g. after loss of communication | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1, 2) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Mode LED (M) white: Parallel operation of outputs | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 150 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | EXA 16 ATEX 0025X | |
| Marking | II 3(1) G Ex nA [ia Ga] IIC T4 Gc II (1) D [Ex ia Da] IIICI (M1) [Ex ia Ma] I | |
| Output | ||
| Voltage | 17.8 V | |
| Current | 162 mA | |
| Power | 721 mW | |
| Internal capacitance | 12 nF | |
| Internal inductance | 0 mH | |
| Output (both channels parallel) | ||
| Voltage | 17.8 V | |
| Current | 324 mA | |
| Power | 1442 mW | |
| Internal capacitance | 24 nF | |
| Internal inductance | 0 mH | |
| Galvanic isolation | ||
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 61241-11:2006 | |
| International approvals | ||
| ATEX approval | EXA 16 ATEX 0025X | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 2 W | |
| Power consumption | 3 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Analog input | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | pressure converter | |
| Field device [2] | flow converter | |
| Field device [3] | level converter | |
| Field device [4] | Temperature Converter | |
| Field device interface | ||
| Connection | 2-wire transmitter | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
| Input resistance | 15 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: > 21 mA Can be parameterized in the range 0 ... 22 mA | |
| Open-circuit | factory setting: < 3.6 mA Can be parameterized in the range 0 ... 22 mA | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Analog output | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | Proportional Valve | |
| Field device [2] | I/P converters | |
| Field device [3] | on-site display | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: < 50 &Omega configurable between 0 ... 26 mA | |
| Open-circuit | deviation of preset output value > 0.5 mA | |
| Load | 750 &Omega max. | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Watchdog | output off 0.5 s after serious fault | |
| Digital input | ||
| Number of channels | 4 | |
| Sensor interface | ||
| Connection [2] | volt-free contact | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Digital signals (active) | ||
| Switching point: ON | > 2.1 mA | |
| Switching point: OFF | < 1.2 mA | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) | |
| Short-circuit | > 7 mA | |
| Open-circuit | < 0.1 mA | |
| Digital output | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8- | |
| Drive capability | 12 V / 22 mA | |
| Open loop voltage | min. 22.7 V | |
| Current limit | 22 mA | |
| Internal resistor | 385 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Test current | 0.4 mA | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | < 0.2 mA | |
| Transfer characteristics | ||
| Deviation | ||
| After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
| Refresh time | approx. 100 ms (4 channels) | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Configuration LED (AI, AO, DI, DO) white: selected channel mode | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2000 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 (module) , mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 100 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | BVS 12 ATEX E 115 X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Galvanic isolation | ||
| Rated voltage | 250 V field circuits to control and supply circuits | |
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | BVS 12 ATEX E 115 X | |
| IECEx approval | BVS 11.0068X | |
| Approved for | Ex nAc [ic] IIC T4 | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power dissipation | 2 W | |
| Power consumption | 3 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Analog input | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | pressure converter | |
| Field device [2] | flow converter | |
| Field device [3] | level converter | |
| Field device [4] | Temperature Converter | |
| Field device interface | ||
| Connection | 2-wire transmitter | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Transmitter supply voltage | min. 15 V at 20 mA 21.5 V at 4 mA | |
| Input resistance | 15 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: > 21 mA Can be parameterized in the range 0 ... 22 mA | |
| Open-circuit | factory setting: < 3.6 mA Can be parameterized in the range 0 ... 22 mA | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Analog output | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | Proportional Valve | |
| Field device [2] | I/P converters | |
| Field device [3] | on-site display | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Line fault detection | can be switched on/off for each channel via configuration tool , configurable via configuration tool | |
| Short-circuit | factory setting: < 50 &Omega configurable between 0 ... 26 mA | |
| Open-circuit | deviation of preset output value > 0.5 mA | |
| Load | 750 &Omega max. | |
| HART communication | yes | |
| HART secondary variable | yes | |
| Watchdog | output off 0.5 s after serious fault | |
| Digital input | ||
| Number of channels | 4 | |
| Sensor interface | ||
| Connection [2] | volt-free contact | |
| Connection | terminals 1+, 2- 3+, 4- 5+, 6- 7+, 8- | |
| Digital signals (active) | ||
| Switching point: ON | > 2.1 mA | |
| Switching point: OFF | < 1.2 mA | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) | |
| Short-circuit | > 7 mA | |
| Open-circuit | < 0.1 mA | |
| Digital output | ||
| Number of channels | 4 | |
| Suitable field devices | ||
| Field device | Solenoid Valve | |
| Field device [2] | audible alarm | |
| Field device [3] | visual alarm | |
| Connection | terminals 1+, 2-, 3+, 4-, 5+, 6-, 7+, 8- | |
| Drive capability | 12 V / 22 mA | |
| Open loop voltage | min. 22.7 V | |
| Current limit | 22 mA | |
| Internal resistor | 385 &Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Test current | 0.4 mA | |
| Short-circuit | < 50 &Omega | |
| Open-circuit | < 0.2 mA | |
| Transfer characteristics | ||
| Deviation | ||
| After calibration | 0.1 % of the signal range at 20 °C (68 °F) | |
| Refresh time | approx. 100 ms (4 channels) | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Diagnostic LED (I) red: module fault , red flashing: communication error , white: fixed parameter set (parameters from com unit are ignored) , white flashing: requests parameters from com unit Status LED (1-4) red: line fault (lead breakage or short circuit) , yellow: state of digital I/O (0/1) Configuration LED (AI, AO, DI, DO) white: selected channel mode | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1:2006 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21:2007 | |
| Degree of protection | IEC 60529:2000 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 100 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| EU-Type Examination Certificate | BVS 11 ATEX E 116 X | |
| Marking | II 3(1) G Ex nA [ia Ga] IIC T4 Gc I (M1) [Ex ia Ma] I II (1) D [Ex ia Da] IIIC | |
| Input | ||
| Voltage | 27 V | |
| Current | 87 mA | |
| Power | 575 mW (linear characteristic) | |
| Output | ||
| Voltage | 27 V | |
| Current | 87 mA | |
| Power | 575 mW (linear characteristic) | |
| Galvanic isolation | ||
| Rated voltage | 250 V field circuits to control and supply circuits | |
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Output/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 EN 60079-26:2007 EN 61241-11:2006 EN 50303:2000 | |
| International approvals | ||
| ATEX approval | BVS 11 ATEX E 116X | |
| UL approval | E106378 | |
| IECEx approval | BVS 11.0068X | |
| Approved for | Ex nAc [ia] IIC T4 [Ex ia] IIIC [Ex ia] I | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 0.6 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 1 | |
| Function | ||
| Function | Counter  | |
| Function [2] | frequency | |
| Function [3] | direction of rotation | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 1+, 2- direction: 4+, 5- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | in frequency + counter mode: 12.5 ms otherwise 20 µs | |
| Operating frequency | 0 ... 15 kHz in frequency + counter mode ... 40 Hz | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Status LED (1) red: line fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PTB 03 ATEX 2042 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ic] IIC T4 Gc | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| Bureau Veritas Marine | 22449/B0 BV | |
| Slots | ||
|---|---|---|
| Occupied slots | 1 | |
| Supply | ||
| Connection | backplane bus | |
| Rated voltage | 12 V DC , only in connection with the power supplies LB9*** | |
| Power consumption | 0.6 W | |
| Internal bus | ||
| Connection | backplane bus | |
| Interface | manufacturer-specific bus to standard com unit | |
| Digital input | ||
| Number of channels | 1 | |
| Function | ||
| Function | Counter  | |
| Function [2] | frequency | |
| Function [3] | direction of rotation | |
| Sensor interface | ||
| Connection | NAMUR sensor | |
| Connection [2] | volt-free contact | |
| Connection [3] | active binary signal 24 V DC | |
| Connection | channel I: 1+, 2- direction: 4+, 5- | |
| Rated values | acc. to EN 60947-5-6 (NAMUR) | |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / ± 0.2 mA | |
| Voltage | 8.2 V | |
| Internal resistor | 1 k&Omega | |
| Line fault detection | can be switched on/off for each channel via configuration tool | |
| Connection | mechanical switch with additional resistors (see connection diagram) proximity switches without additional wiring | |
| Short-circuit | < 360 &Omega | |
| Open-circuit | < 0.35 mA | |
| Minimum pulse duration | in frequency + counter mode: 12.5 ms otherwise 20 µs | |
| Operating frequency | 0 ... 400 Hz in frequency + counter mode ... 40 Hz | |
| Indicators/settings | ||
| LED indicator | Power LED (P) green: supply Status LED (1) red: line fault | |
| Directive conformity | ||
| Electromagnetic compatibility | ||
| Directive 2014/30/EU | EN 61326-1 | |
| Conformity | ||
| Electromagnetic compatibility | NE 21 | |
| Degree of protection | IEC 60529 | |
| Ambient conditions | ||
| Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) , 70 °C (non-Ex) | |
| Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
| Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
| Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
| Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
| Mechanical specifications | ||
| Degree of protection | IP20 when mounted on backplane | |
| Connection | removable front connector with screw flange (accessory) wiring connection via spring terminals (0.14 ... 1.5 mm2) or screw terminals (0.08 ... 1.5 mm2) | |
| Mass | approx. 90 g | |
| Dimensions | 16 x 100 x 102 mm (0.63 x 3.9 x 4 inch) | |
| Data for application in connection with hazardous areas | ||
| Certificate | PF 08 CERT 1234 X | |
| Marking | II 3 G Ex nA [ic] IIC T4 Gc | |
| Galvanic isolation | ||
| Input/power supply, internal bus | safe electrical isolation acc. to EN 60079-11, voltage peak value 375 V | |
| Directive conformity | ||
| Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
| International approvals | ||
| ATEX approval | PTB 03 ATEX 2042 | |
| IECEx approval | BVS 09.0037X | |
| Approved for | Ex nA [ic] IIC T4 Gc | |
| Marine approval | ||
| Lloyd Register | 15/20021 | |
| DNV GL Marine | TAA0000034 | |
| Bureau Veritas Marine | 22449/B0 BV | |