Атол 30Ф не включается (заводской брак)
Валерий
14 января 2022
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 50 mA | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 10, 11 | |
Signal level | 1-signal: switching voltage - 2.5 V max. at 10 mA switching current or 3 V max. at 100 mA switching current 0-signal: switched off (off-state current &le 10 µA) | |
Output I | signal, passive electronic output | |
Output II | signal or error message passive transistor output | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Galvanic isolation | IEC 62103:2003 | |
Electromagnetic compatibility | NE 21:2004 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2035 | |
Marking | ![]() ![]() | |
EU-Type Examination Certificate | DMT 01 ATEX E 133 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1499 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 05.0011 | |
Approved for | [Ex ia] IIC , [Ex ia] I , [Ex ia] IIIC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 50 mA | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 8, 9 | |
Signal level | 1-signal: switching voltage - 2.5 V max. at 10 mA switching current or 3 V max. at 100 mA switching current 0-signal: switched off (off-state current &le 10 µA) | |
Output I, II | signal electronic output, passive | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Galvanic isolation | ||
Input/input | not available | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Galvanic isolation | IEC 62103:2003 | |
Electromagnetic compatibility | NE 21:2004 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2035 | |
Marking | ![]() ![]() | |
EU-Type Examination Certificate | DMT 01 ATEX E 133 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1499 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 05.0011 | |
Approved for | [Ex ia] IIC , [Ex ia] I , [Ex ia] IIIC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 50 mA | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 10, 11 | |
Signal level | 1-signal: switching voltage - 2.5 V max. at 10 mA switching current or 3 V max. at 100 mA switching current 0-signal: switched off (off-state current &le 10 µA) | |
Output I, II | signal electronic output, passive | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Galvanic isolation | ||
Input/input | not available | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Galvanic isolation | IEC 62103:2003 | |
Electromagnetic compatibility | NE 21:2004 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2035 | |
Marking | ![]() ![]() | |
EU-Type Examination Certificate | DMT 01 ATEX E 133 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1499 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 05.0011 | |
Approved for | [Ex ia] IIC , [Ex ia] I , [Ex ia] IIIC |
Описание оборудования | ||
---|---|---|
24 V DC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | 20 ... 15 mA | |
Power dissipation | &le 1 W including maximum power dissipation in the output | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I &ge 6.5 mA | |
Pulse/Pause ratio | min. 100 µs / min. 100 µs | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 8, 9 | |
Rated voltage | 30 V DC | |
Rated current | 100 mA , short-circuit protected | |
Response time | &le 200 µs | |
Signal level | 1-signal: (external voltage) - 3 V max. for 100 mA 0-signal: blocked output (off-state current &le 10 µA) | |
Output I | signal Transistor | |
Output II | signal or error message Transistor | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 16 ATEX 0016 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 16.0009X | |
Approved for | Ex nA [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I | |
Accessories | ||
Optional accessories | power feed module KFD2-EB2 Universal Power Rail UPR-03 Universal Power Rail UPR-03-S profile rail K-DUCT-BU profile rail K-DUCT-UPR-03 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | 20 ... 15 mA | |
Power dissipation | &le 1 W including maximum power dissipation in the output | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I &ge 6.5 mA | |
Pulse/Pause ratio | min. 100 µs / min. 100 µs | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 10, 11 | |
Rated voltage | 30 V DC | |
Rated current | 100 mA , short-circuit protected | |
Response time | &le 200 µs | |
Signal level | 1-signal: (external voltage) - 3 V max. for 100 mA 0-signal: blocked output (off-state current &le 10 µA) | |
Output I | signal Transistor | |
Output II | signal or error message Transistor | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 16 ATEX 0016 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 16.0009X | |
Approved for | Ex nA [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I | |
Accessories | ||
Optional accessories | power feed module KFD2-EB2 Universal Power Rail UPR-03 Universal Power Rail UPR-03-S profile rail K-DUCT-BU profile rail K-DUCT-UPR-03 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | 30 ... 20 mA | |
Power dissipation | &le 1.1 W including maximum power dissipation in the output | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I &ge 6.5 mA | |
Pulse/Pause ratio | min. 100 µs / min. 100 µs | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 8, 9 | |
Rated voltage | 30 V DC | |
Rated current | 100 mA , short-circuit protected | |
Response time | &le 200 µs | |
Signal level | 1-signal: (external voltage) - 3 V max. for 100 mA 0-signal: blocked output (off-state current &le 10 µA) | |
Output I | signal Transistor | |
Output II | signal Transistor | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 16 ATEX 0016 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 16.0009X | |
Approved for | Ex nA [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I | |
Accessories | ||
Optional accessories | power feed module KFD2-EB2 Universal Power Rail UPR-03 Universal Power Rail UPR-03-S profile rail K-DUCT-BU profile rail K-DUCT-UPR-03 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | 30 ... 20 mA | |
Power dissipation | &le 1.1 W including maximum power dissipation in the output | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I &ge 6.5 mA | |
Pulse/Pause ratio | min. 100 µs / min. 100 µs | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 10, 11 | |
Rated voltage | 30 V DC | |
Rated current | 100 mA , short-circuit protected | |
Response time | &le 200 µs | |
Signal level | 1-signal: (external voltage) - 3 V max. for 100 mA 0-signal: blocked output (off-state current &le 10 µA) | |
Output I | signal Transistor | |
Output II | signal Transistor | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 16 ATEX 0016 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 16.0009X | |
Approved for | Ex nA [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I | |
Accessories | ||
Optional accessories | power feed module KFD2-EB2 Universal Power Rail UPR-03 Universal Power Rail UPR-03-S profile rail K-DUCT-BU profile rail K-DUCT-UPR-03 |
Описание оборудования | ||
---|---|---|
24 V DC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 30 mA | |
Power dissipation | 0.7 W | |
Power consumption | < 0.9 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | terminals 7, 8, 9 | |
Output | signal relay | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Transfer characteristics | ||
Switching frequency | < 10 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2080 | |
Marking | ![]() ![]() ![]() | |
Fault indication output | ||
Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) | |
Certificate | PF 08 CERT 0803 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1493 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 11.0034 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 50 mA | |
Power dissipation | 1 W | |
Power consumption | < 1.3 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Output I | signal relay | |
Output II | signal or error message relay | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Transfer characteristics | ||
Switching frequency | &le 10 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2080 | |
Marking | ![]() ![]() ![]() | |
Fault indication output | ||
Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) | |
Certificate | PF 08 CERT 0803 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1493 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 11.0034 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 50 mA | |
Power dissipation | 1 W | |
Power consumption | < 1.3 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 8, 9 output III: terminals 10, 11 output IV: terminals 11, 12 | |
Output I, II, III, IV | channel 1, 2 relay | |
Contact loading | 50 V AC/1 A/cos &phi > 0.7 40 V DC/1 A resistive load | |
Minimum switch current | 1 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 108 switching cycles | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 10 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2004 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2083 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1493 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
CSA approval | ||
Control drawing | 116-0047 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 50 mA | |
Power dissipation | 1 W | |
Power consumption | < 1.3 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Output I, II | signal, relay | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Transfer characteristics | ||
Switching frequency | &le 10 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2080 | |
Marking | ![]() ![]() ![]() | |
Fault indication output | ||
Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) | |
Certificate | PF 08 CERT 0803 | |
Marking | ![]() | |
Certificate | TÜV 99 ATEX 1493 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 11.0034 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | 30 ... 20 mA | |
Power consumption | < 600 mW | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I &ge 6.5 mA | |
Pulse/Pause ratio | min. 20 ms / min. 20 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 8, 9 output III: terminals 10, 11 output IV: terminals 11, 12 | |
Output I, II, III, IV | channel 1, 2 relay | |
Contact loading | 48 V AC/1 A/cos &phi > 0.7 40 V DC/1 A resistive load | |
Minimum switch current | 1 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 108 switching cycles | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 10 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 16 ATEX 0001 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 16.0001X | |
Approved for | Ex nA nC [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I | |
Accessories | ||
Optional accessories | power feed module KFD2-EB2 Universal Power Rail UPR-03 Universal Power Rail UPR-03-S profile rail K-DUCT-BU profile rail K-DUCT-UPR-03 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | 45 ... 70 mA | |
Power dissipation | 1.2 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1-, 2+, 3- 4-, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Pulse/Pause ratio | min. 35 ms / min. 35 ms (non-AC operation) min. 70 ms / min. 70 ms (AC operation) | |
Line fault detection | breakage I &le 0.15 mA , short-circuit I > 6 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8 output II: terminals 8, 9 output III: terminals 10, 11 output IV: terminals 11, 12 | |
Output I ... IV | Signal I ... Signal IV relay | |
Contact loading | 253 V AC/2 A /cos &phi > 0.7 40 V DC/2 A resistive load | |
Energized/De-energized delay | approx. 30 ms / approx. 30 ms | |
Mechanical life | 5 x 106 switching cycles | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 10 Hz (non-AC operation) &le 3 Hz (AC operation) | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | ZELM 99 ATEX 0009 | |
Marking | ![]() ![]() ![]() | |
Fault indication output | ||
Maximum safe voltage | 40 V DC | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-26:2007 , EN 50303:2000 | |
International approvals | ||
UL approval | ||
Control drawing | 116-0145 | |
IECEx approval | IECEx TUN 04.0003 | |
Approved for | [Ex ia Ga] IIC , [Ex ia Da] IIIC , [Ex ia Ma] I |
Описание оборудования | ||
---|---|---|
24 V DC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 50 mA | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7+ output II: terminals 9+ | |
Signal level | 1-signal: (L+) - 3.5 V (100 mA, short-circuit protected) 0-signal: switched off (off-state current &le 10 µA) | |
Output I, II | signal electronic output, active | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Galvanic isolation | ||
Input/input | not available | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Galvanic isolation | IEC 62103:2003 | |
Electromagnetic compatibility | NE 21:2004 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2035 | |
Marking | ![]() ![]() | |
Certificate | TÜV 99 ATEX 1499 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 50303:2000 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 05.0011 | |
Approved for | [Ex ia] IIC , [Ex ia] I , [Ex ia] IIIC |
Описание оборудования | ||
---|---|---|
24 V DC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | 20 ... 15 mA + Iout | |
Power dissipation | &le 900 mW including maximum power dissipation in the output | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2+, 3- 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 10 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I &ge 6.5 mA | |
Pulse/Pause ratio | min. 100 µs / min. 100 µs | |
Output | ||
Connection side | control side | |
Connection | output I: terminal 7+ output II: terminal 9+ | |
Rated voltage | 30 V DC | |
Rated current | 100 mA | |
Response time | &le 200 µs | |
Signal level | 1-signal: (supply voltage) - 3 V max. for 100 mA 0-signal: blocked output (off-state current &le 10 µA) | |
Output I | signal Transistor | |
Output II | signal Transistor | |
Collective error message | Power Rail | |
Transfer characteristics | ||
Switching frequency | &le 5 kHz | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 16 ATEX 0016 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 16.0009X | |
Approved for | Ex nA [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I | |
Accessories | ||
Optional accessories | power feed module KFD2-EB2 Universal Power Rail UPR-03 Universal Power Rail UPR-03-S profile rail K-DUCT-BU profile rail K-DUCT-UPR-03 |
Описание оборудования | ||
---|---|---|
230 V AC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | terminals 23, 24 | |
Rated voltage | 115 V AC ± 10 % | |
Rated current | 35 mA | |
Power consumption | 4 VA | |
Input | ||
Connection side | field side | |
Connection | Input I: terminals 1+, 3- input II: terminals 13+, 14- | |
Input I | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | 8.2 V / 10 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Pulse duration | min. 75 µs / 1 ms see instruction manuals the maximum input frequency has to be observed. | |
Input frequency | 0 ... 80 Hz , pulse divider 0 ... 1 kHz | |
Line fault detection | breakage I &le 0.15 mA short-circuit I > 6.5 mA | |
Input II | reset | |
Active/Passive | I > 3 mA / I < 1.5 mA | |
Open circuit voltage/short-circuit current | 12 V / 3.5 mA | |
Pulse duration | min. 10 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 19+, 20- | |
Output I | signal , Relay output | |
Contact loading | 253 V AC/ 2 A / cos &phi &ge 0.7 40 V DC/ 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output II | signal , electronic unit, isolated | |
Contact loading | 40 V / 50 mA | |
Energized/De-energized delay | after rising input flank 3 ms after falling input flank 2 ms | |
Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current &le 10 µA) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | TÜV 99 ATEX 1408 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1885 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0305 | |
UL approval | E223772 | |
IECEx approval | IECEx TUN 03.0000 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | terminals 23, 24 | |
Rated voltage | 230 V AC ± 10 % | |
Rated current | 15 mA | |
Power consumption | 4 VA | |
Input | ||
Connection side | field side | |
Connection | Input I: terminals 1+, 3- input II: terminals 13+, 14- | |
Input I | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | 8.2 V / 10 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Pulse duration | min. 75 µs / 1 ms see instruction manuals the maximum input frequency has to be observed. | |
Input frequency | 0 ... 80 Hz , pulse divider 0 ... 1 kHz | |
Line fault detection | breakage I &le 0.15 mA short-circuit I > 6.5 mA | |
Input II | reset | |
Active/Passive | I > 3 mA / I < 1.5 mA | |
Open circuit voltage/short-circuit current | 12 V / 3.5 mA | |
Pulse duration | min. 10 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 19+, 20- | |
Output I | signal , Relay output | |
Contact loading | 253 V AC/ 2 A / cos &phi &ge 0.7 40 V DC/ 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output II | signal , electronic unit, isolated | |
Contact loading | 40 V / 50 mA | |
Energized/De-energized delay | after rising input flank 3 ms after falling input flank 2 ms | |
Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current &le 10 µA) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | TÜV 99 ATEX 1408 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1885 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0305 | |
UL approval | E223772 | |
IECEx approval | IECEx TUN 03.0000 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 20 ... 30 V DC | |
Rated current | approx. 100 mA | |
Power consumption | 1.8 W | |
Input | ||
Connection side | field side | |
Connection | Input I: terminals 1+, 3- input II: terminals 13+, 14- | |
Input I | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | 8.2 V / 10 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Pulse duration | min. 75 µs / 1 ms see instruction manuals the maximum input frequency has to be observed. | |
Input frequency | 0 ... 80 Hz , pulse divider 0 ... 1 kHz | |
Line fault detection | breakage I &le 0.15 mA short-circuit I > 6.5 mA | |
Input II | reset | |
Active/Passive | I > 4 mA/I < 1.5 mA | |
Open circuit voltage/short-circuit current | 18 V / 5 mA | |
Pulse duration | min. 10 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 19+, 20- | |
Output I | signal , Relay output | |
Contact loading | 253 V AC/ 2 A / cos &phi &ge 0.7 40 V DC/ 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output II | signal , electronic unit, isolated | |
Contact loading | 40 V / 50 mA | |
Energized/De-energized delay | after rising input flank 3 ms after falling input flank 2 ms | |
Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current &le 10 µA) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | TÜV 99 ATEX 1408 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1885 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0305 | |
UL approval | E223772 | |
IECEx approval | IECEx TUN 03.0000 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Описание оборудования | ||
---|---|---|
current limit 45 mA |
Описание оборудования | ||
---|---|---|
current limit 45 mA |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | terminals 5+, 6- loop powered Power Rail or terminals 9+, 10- bus powered | |
Rated voltage | 19 ... 30 V DC | |
Input current | 75 mA at 24 V, 220 &Omega load | |
Power dissipation | 1.4 W at 24 V, 220 &Omega load | |
Input | ||
Connection side | control side | |
Connection | terminals 5+, 6- | |
Signal level | loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited at 5 mA) 0-signal: 0 ... 5 V DC | |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Internal resistor | 285 &Omega | |
Current | typ. 45 mA | |
Voltage | typ. 10 V | |
Current limit | 45 mA | |
Open loop voltage | typ. 24.6 V | |
Load | nominal 0.05 ... 18 k&Omega | |
Output II | fault signal | |
Connection | terminals 7, 8 , non-intrinsically safe | |
Contact loading | 30 V DC/ 0.5 A resistive load | |
Mechanical life | 105 switching cycles | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Line fault detection | signal at short-circuit RB < 25 &Omega, lead breakage RB > 50 k&Omega test current < 500 µA | |
Galvanic isolation | ||
Output/Other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 For further information see system description. | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 17 ATEX 0002 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 17.0001X | |
Approved for | Ex nC ec [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | terminals 5+, 6- loop powered Power Rail or terminals 9+, 10- bus powered | |
Rated voltage | 19 ... 30 V DC | |
Input current | 80 mA at 24 V | |
Power dissipation | 1.3 W at 24 V | |
Load | 150 &Omega | |
Input | ||
Connection side | control side | |
Connection | terminals 5+, 6- | |
Signal level | loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited at 5 mA) 0-signal: 0 ... 5 V DC | |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Internal resistor | 80 &Omega | |
Current | typ. 65 mA | |
Voltage | typ. 10 V | |
Current limit | 65 mA | |
Open loop voltage | typ. 16.4 V | |
Load | nominal 0.05 ... 18 k&Omega | |
Output II | fault signal | |
Connection | terminals 7, 8 , non-intrinsically safe | |
Contact loading | 30 V DC/ 0.5 A resistive load | |
Mechanical life | 105 switching cycles | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Line fault detection | signal at short-circuit RB < 25 &Omega, lead breakage RB > 50 k&Omega test current < 500 µA | |
Galvanic isolation | ||
Output/Other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 For further information see system description. | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 17 ATEX 0002 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 17.0001X | |
Approved for | Ex nC ec [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | terminals 5+, 6- loop powered Power Rail or terminals 9+, 10- bus powered | |
Rated voltage | 19 ... 30 V DC | |
Input current | 75 mA at 24 V , 270 &Omega load | |
Power dissipation | 1.3 W at 24 V , 270 &Omega load | |
Input | ||
Connection side | control side | |
Connection | terminals 5+, 6- | |
Signal level | loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited at 5 mA) 0-signal: 0 ... 5 V DC | |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Internal resistor | 240 &Omega | |
Current | typ. 45 mA | |
Voltage | typ. 12 V | |
Current limit | 50 mA | |
Open loop voltage | typ. 24.6 V | |
Load | nominal 0.05 ... 18 k&Omega | |
Output II | fault signal | |
Connection | terminals 7, 8 , non-intrinsically safe | |
Contact loading | 30 V DC/ 0.5 A resistive load | |
Mechanical life | 105 switching cycles | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Line fault detection | signal at short-circuit RB < 25 &Omega, lead breakage RB > 50 k&Omega test current < 500 µA | |
Galvanic isolation | ||
Output/Other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 For further information see system description. | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 17 ATEX 0002 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 17.0001X | |
Approved for | Ex nC ec [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I |
Описание оборудования | ||
---|---|---|
current limit: 100 mA |
Описание оборудования | ||
---|---|---|
current limit 45 mA |
Товаров: 0