Атол 30Ф не включается (заводской брак)
Валерий
14 января 2022
Описание оборудования | ||
---|---|---|
48 V AC ... 253 V AC/20 V DC ... 90 V DC |
Описание оборудования | ||
---|---|---|
24 V DC |
Описание оборудования | ||
---|---|---|
24 V DC |
Описание оборудования | ||
---|---|---|
48 V AC ... 253 V AC/20 V DC ... 90 V DC |
Описание оборудования | ||
---|---|---|
48 V AC ... 253 V AC/20 V DC ... 90 V DC |
Описание оборудования | ||
---|---|---|
48 V AC ... 253 V AC/20 V DC ... 90 V DC |
Описание оборудования | ||
---|---|---|
115 V AC |
Описание оборудования | ||
---|---|---|
230 V AC |
Описание оборудования | ||
---|---|---|
24 V DC |
Описание оборудования | ||
---|---|---|
24 V DC |
Описание оборудования | ||
---|---|---|
Rotation Speed Monitor |
Описание оборудования | ||
---|---|---|
48 V AC ... 253 V AC/20 V DC ... 90 V DC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Power consumption | max. 1.5 W | |
Input | ||
Connection side | field side | |
Connection | Input I: terminals 1+, 2+, 3- Input II: terminals 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | not available | |
Control input | sensor power supply approx. 8.2 V, impedance 1.2 k&Omega | |
Pulse duration | > 200 µs for standstill monitoring, > 250 µs for rotation direction detecion | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Trip value | for standstill monitoring: 0.1 Hz 0.5 Hz 2 Hz 10 Hz adjustable via DIP switch (S1 and S2) | |
Transfer characteristics | ||
Accuracy | 5 % (S3 = I), 30 % (S3 = II) | |
Start-up override | 5 seconds or 20 seconds, programmable | |
Frequency range | &le 2 kHz | |
Rotation direction detection | 90° phase difference between pulse input signal 1 and 2, overlapping &ge 125 µs | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Power consumption | max. 1.5 W | |
Input | ||
Connection side | field side | |
Connection | Input I: terminals 1+, 2+, 3- Input II: terminals 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Control input | sensor power supply approx. 8.2 V, impedance 1.2 k&Omega | |
Pulse duration | > 200 µs for standstill monitoring, > 250 µs for rotation direction detecion | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Trip value | for standstill monitoring: 0.1 Hz 0.5 Hz 2 Hz 10 Hz adjustable via DIP switch (S1 and S2) | |
Transfer characteristics | ||
Accuracy | 5 % (S3 = I), 30 % (S3 = II) | |
Start-up override | 5 seconds or 20 seconds, programmable | |
Frequency range | &le 2 kHz | |
Rotation direction detection | 90° phase difference between pulse input signal 1 and 2, overlapping &ge 125 µs | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2080 | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
Fault indication output | ||
Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) | |
Certificate | TÜV 99 ATEX 1493 X | |
Marking | II 3G Ex nA nC IIC T4 | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 11.0034 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Supply | ||
---|---|---|
Rated voltage | 20 ... 30 V DC SELV/PELV | |
Power consumption | < 5 W | |
External bus | ||
Connection | screw terminals for - 0.2 ... 4 mm2 (rigid wire) - 0.2 ... 2.5 mm2 (flexible wire) | |
Interface 1 | Ethernet 10 BASE-T/100 BASE-TX , full galvanic isolation | |
Protocol | HART UDP, MODBUS TCP | |
Interface 2 | RS-485 | |
Protocol | HART, MODBUS RTU | |
Transfer rate | max. 115 kBit/s | |
Galvanic isolation | ||
Interface/interface | basic insulation according to IEC 61140, rated insulation voltage 50 Veff | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300328: V2.1.1 EN 301489-17: V1.3.2 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66/IP67 | |
Mass | approx. 1 kg | |
Dimensions | 258 mm x 114 mm x 84 mm without antenna and cable glands | |
Mounting | panel mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | FM 12 ATEX 0061 | |
Marking | II 3 G Ex nA IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
International approvals | ||
FM approval | Coc3042646 | |
Approved for | NI Class I, Div. 2, GPS A-D NI Class II, Class III, Div. 2, GPS E-G | |
IECEx approval | IECEx FMG 12.0002 | |
Approved for | Ex nA IIC T4 Gc , Ex nAc T4 |
Supply | ||
---|---|---|
Rated voltage | 20 ... 30 V DC SELV/PELV | |
Power consumption | < 5 W | |
External bus | ||
Connection | screw terminals for - 0.2 ... 4 mm2 (rigid wire) - 0.2 ... 2.5 mm2 (flexible wire) | |
Interface 1 | Ethernet 10 BASE-T/100 BASE-TX , full galvanic isolation | |
Protocol | HART UDP, EtherNet/IP | |
Interface 2 | RS-485 | |
Protocol | HART | |
Transfer rate | max. 115 kBit/s | |
Galvanic isolation | ||
Interface/interface | basic insulation according to IEC 61140, rated insulation voltage 50 Veff | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Radio and telecommunication terminal equipment | The usage of 2.4 GHz equipment is bound to local restrictions. Ensure that restrictions allow usage of this product before commisioning. | |
Directive 2014/53/EU | EN 300328: V2.1.1 EN 301489-17: V1.3.2 | |
FCC CFR47 Part 15 B and C | ANSI C63.4-2003 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 test setup and execution acc. to EN 60068-2-60 | |
Mechanical specifications | ||
Degree of protection | IP66/IP67 | |
Mass | approx. 1 kg | |
Dimensions | 258 mm x 114 mm x 84 mm without antenna and cable glands | |
Mounting | panel mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | FM 12 ATEX 0061 , for additional certificates see www.pepperl-fuchs.com | |
Marking | II 3 G Ex nA nC IIC T4 Gc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 | |
International approvals | ||
FM approval | Coc3042646 | |
Approved for | NI Class I, Div. 2, GPS A-D NI Class II, Class III, Div. 2, GPS E-G | |
IECEx approval | IECEx FMG 12.0002 | |
Approved for | Ex nA nC IIC T4 Gc Ex nAc nCc T4 |