General specifications | ||
---|---|---|
Signal type | Analog input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | terminals 23, 24 | |
Rated voltage | 20 ... 90 V DC / 48 ... 253 V AC | |
Power dissipation/power consumption | &le 2 W 2.5 VA / 2.2 W 3 VA | |
Interface | ||
Programming interface | programming socket | |
Input | ||
Connection side | field side | |
Connection | terminals 1, 2, 3, 4, 6 | |
RTD | Pt100, Pt500, Pt1000, Ni100, Ni1000 | |
Types of measuring | 2-, 3-, 4-wire technology | |
Lead resistance | max. 50 &Omega | |
Measurement loop monitoring | sensor breakage, sensor short-circuit | |
Thermocouples | type B, E, J, K, L, N, R, S, T (IEC 584-1: 1995) | |
Cold junction compensation | external and internal | |
Measurement loop monitoring | sensor breakage | |
Potentiometer | 0.8 ... 20 k&Omega | |
Types of measuring | 2-, 3-, 5-wire technology | |
Voltage | 0 ... 10 V , 2 ... 10 V , 0 ... 1 V , -100 ... 100 mV | |
Input resistance | &ge 250 k&Omega (0 ... 10 V) min. 1 M&Omega (0 ... 1 V, -100 ... 100 mV) | |
Measuring current | approx. 400 µA with resistance measuring sensor | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 16, 17, 18 output III: terminals 8+, 7- | |
Output I, II | relay | |
Contact loading | 250 V AC / 2 A / cos &phi &ge 0.7 40 DC / 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output III | Analog current output | |
Current range | 0 ... 20 mA or 4 ... 20 mA | |
Open loop voltage | max. 24 V DC | |
Load | max. 650 &Omega | |
Fault signal | downscale I &le 3.6 mA, upscale I &ge 21 mA (acc. NAMUR NE43) | |
Transfer characteristics | ||
Sampling rate | approx. 700 ms | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons via PACTware | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | TÜV 03 ATEX 2140 | |
Marking | II (1) G [Ex ia] IIC II (1) D [Ex iaD] | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 |
General specifications | ||
---|---|---|
Signal type | Analog input | |
Supply | ||
Rated voltage | 12 ... 35 V DC loop powered | |
Power dissipation | 0.4 W | |
Input | ||
Connection side | field side | |
Connection | terminals 1+, 2-, 3- thermocouple E, J, K, N, R, S or T, cold junction referenced to 0 °C (32 °F) | |
Lead resistance | max. 100 &Omega per line | |
Current | lead monitoring ON: &le 15 nA OFF: &le 1 nA | |
Output | ||
Connection side | control side | |
Connection | terminals 9+, 8- | |
Load | (U -12 V) / 0.02 A | |
Current output | 4 ... 20 mA , limited to &le 35 mA | |
Fault signal | downscaling &le 3 mA , upscaling &ge 22 mA | |
Transfer characteristics | ||
Measurement range | span 4 ... 100 mV, zero point -12 ... 60 mV , both adjustable | |
Characteristic curve | the output voltage is linearly proportionate to the input voltage (not to temperature) | |
Rise time | 250 ms | |
Indicators/settings | ||
Control elements | DIP-switch rotary switch | |
Configuration | via DIP switches via rotary switch | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Insulation coordination | EN 50178 | |
Galvanic isolation | EN 50178 | |
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | ZELM 00 ATEX 0035 | |
Marking | II (1)GD [EEx ia] IIC | |
Certificate | TÜV 01 ATEX 1777 X | |
Marking | II 3G Ex nA II T4 | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0132 |
Описание оборудования | ||
---|---|---|
Current output 0/4 mA ... 20 mA |
Описание оборудования | ||
---|---|---|
Current output 0/4 mA ... 20 mA |
Описание оборудования | ||
---|---|---|
Voltage output 0/1 V ... 5 V |
Описание оборудования | ||
---|---|---|
Current output 0/4 mA ... 20 mA |
Описание оборудования | ||
---|---|---|
Voltage output 0/1 V ... 5 V |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Rated voltage | loop powered | |
Power dissipation | 0.8 W | |
Input | ||
Connection side | control side | |
Connection | terminals 7, 8, 9 | |
Input current | &le 21 mA per channel | |
Output | ||
Safety note | Attention! Combination of output Ex i with output not Ex i is not permitted. If load voltage > 50 V, de-energize before removing the terminals. | |
Connection side | field side | |
Connection | terminals 1, 2, 3 4, 5, 6 | |
Contact loading | 230 V AC/2 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Energized/De-energized delay | approx. 10 ms / approx. 5 ms | |
Mechanical life | 5 x 106 switching cycles | |
Transfer characteristics | ||
Switching frequency | < 10 Hz | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 65 °C (-4 ... 149 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | DMT 00 ATEX E 016 | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
Certificate | TÜV 00 ATEX 1621 X | |
Marking | II 3G Ex nA nC IIC T4 | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0261 | |
CSA approval | ||
Control drawing | 116-0156 | |
IECEx approval | IECEx BVS 10.0025 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Описание оборудования | ||
---|---|---|
24 V DC |
Описание оборудования | ||
---|---|---|
48 V AC ... 253 V AC/20 V DC ... 90 V DC |
Описание оборудования | ||
---|---|---|
24 V DC |
Описание оборудования | ||
---|---|---|
48 V AC ... 253 V AC/20 V DC ... 90 V DC |
Описание оборудования | ||
---|---|---|
115 V AC |
Описание оборудования | ||
---|---|---|
230 V AC |
Описание оборудования | ||
---|---|---|
24 V DC |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Power consumption | max. 1.5 W | |
Input | ||
Connection side | field side | |
Connection | Input I: terminals 1+, 2+, 3- Input II: terminals 4+, 5+, 6- | |
Rated values | acc. to EN 60947-5-6 (NAMUR) | |
Open circuit voltage/short-circuit current | approx. 8 V DC / approx. 8 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Line fault detection | breakage I &le 0.1 mA , short-circuit I > 6 mA | |
Control input | sensor power supply approx. 8.2 V, impedance 1.2 k&Omega | |
Pulse duration | > 200 µs for standstill monitoring, > 250 µs for rotation direction detecion | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 7, 8, 9 output II: terminals 10, 11, 12 | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 126.5 V AC/4 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Minimum switch current | 2 mA / 24 V DC | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Mechanical life | 107 switching cycles | |
Trip value | for standstill monitoring: 0.1 Hz 0.5 Hz 2 Hz 10 Hz adjustable via DIP switch (S1 and S2) | |
Transfer characteristics | ||
Accuracy | 5 % (S3 = I), 30 % (S3 = II) | |
Start-up override | 5 seconds or 20 seconds, programmable | |
Frequency range | &le 2 kHz | |
Rotation direction detection | 90° phase difference between pulse input signal 1 and 2, overlapping &ge 125 µs | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 00 ATEX 2080 | |
Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I | |
Fault indication output | ||
Maximum safe voltage | 40 V DC (Attention! Um is no rated voltage.) | |
Certificate | TÜV 99 ATEX 1493 X | |
Marking | II 3G Ex nA nC IIC T4 | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0035 | |
CSA approval | ||
Control drawing | 116-0047 | |
IECEx approval | IECEx PTB 11.0034 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Товаров: 0