General specifications | ||
---|---|---|
Function principle | ring magnet as switching element in the float, reed contact number of contacts: - version LML1: 1 contact - version LML2: 2 contacts - version LML3: 3 contacts switching function: - version DO: with rising level NC contact - version DS: with rising leve NO contact - version DW: with rising level change-over contact | |
Equipment architecture | A measuring system consists of a magnet-operated immersion probe LML*S*-**S-**-Ex and a (up to 3) isolated amplifier(s) with certified intrinsically safe circuit, for example KFD2-SR2-Ex1.W. | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61000-6-2:2006 , EN 61000-6-4:2011 | |
Conformity | ||
Degree of protection | IEC 60529:2000 | |
Operating conditions | ||
Process conditions | ||
Process temperature | -30 ... 150 °C (-22 ... 302 °F) | |
Process pressure (static pressure) | &le 25 bar (362.6 psi) | |
Density | version S2: &ge 0.8 g/cm3 version S3: &ge 0.7 g/cm3 | |
Ambient conditions | ||
Ambient temperature | terminal box: -50 ... 60 °C (-58 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP65 | |
Connection | max. 6 terminals, max. 2.5 mm2 | |
Material | float, guide tube, process connection: stainless steel 1.4571/316Ti terminal box: aluminum die-casting | |
Dimensions | float: - version S2: cylinder &empty44 mm x 52 mm - version S3: ball &empty52 mm guide tube: &empty12 mm, max. length 3000 mm terminal box: 80 x 75 x 57 mm | |
Process connection | thread G1-1/2A, G2A to DIN/ISO 228/1 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | KEMA 03 ATEX 1496 X | |
Group, category, type of protection, temperature class | II 1/2G EEx ia IIC T3...T6 | |
Voltage | 36 V | |
Current | 100 mA | |
Internal capacitance | 0 nF | |
Internal inductance | 0 µH | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012, EN 60079-11:2012, EN 60079-26:2007 | |
Accessories | ||
Optional accessories | LML-Z11 set collar, 1.4571/316Ti LML-FS2 float, cylinder, Ø44 mm x 52 mm, 1.4571/316Ti LML-FS3 float, ball, Ø52 mm, 1.4571/316Ti |
General specifications | ||
---|---|---|
Function principle | ring magnet as switching element in the float, reed contact, change-over contact number of contacts: - version LML1: 1 contact - version LML2: 2 contacts - version LML3: 3 contacts | |
Supply | ||
Rated voltage | 250 V AC/DC | |
Current consumption | 1 A | |
Output | ||
Connection | This device may be used with any sequential circuit, as long as the circuit can support the electrical circuit values of the switching elements. | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Degree of protection | IEC 60529:2000 | |
Operating conditions | ||
Process conditions | ||
Process temperature | version PP: -10 ... 80 °C (14 ... 176 °F) version PVDF: -10 ... 100 °C (14 ... 212 °F) | |
Process pressure (static pressure) | &le 3 bar (43.5 psi) | |
Density | &ge 0.8 g/cm3 | |
Ambient conditions | ||
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP65 | |
Connection | version LML: terminal box, max. 9 terminals version LML-PVC1: connection cable 1 m (3.3 ft), 0.75 mm2 | |
Material | float, guide tube, process connection: - version PP: PP (Polypropylene) - version PVDF: PVDF (Polyvinylidenfluoride) connection cable: PVC terminal box: Polyester | |
Dimensions | float: - version PP: cylinder &empty44 mm x 44 mm - version PVDF: cylinder &empty55 mm x 70 mm guide tube: - version D: &empty12 mm, max. length 1000 mm - version P: &empty16 mm, max. length 1000 mm terminal box: 80 x 82 x 55 mm | |
Process connection | thread G3/8A, G1-1/2A, G2A to DIN/ISO 228/1 | |
Accessories | ||
Optional accessories | LML-Z21 set collar, PP LML-Z22 set collar, PVDF LML-FD5 float, cylinder, Ø55 mm x 70 mm, PVDF LML-FP7 float, cylinder, Ø44 mm x 44 mm, PP |
General specifications | ||
---|---|---|
Function principle | ring magnet as switching element in the float, reed contact, change-over contact number of contacts: - version LML1: 1 contact - version LML2: 2 contacts - version LML3: 3 contacts | |
Supply | ||
Rated voltage | 250 V AC/DC | |
Current consumption | 1 A | |
Output | ||
Connection | This device may be used with any sequential circuit, as long as the circuit can support the electrical circuit values of the switching elements. | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Degree of protection | IEC 60529:2000 | |
Operating conditions | ||
Process conditions | ||
Process temperature | version LML: -30 ... 150 °C (-22 ... 302 °F) version LML-PVC1: -10 ... 80 °C (14 ... 176 °F) | |
Process pressure (static pressure) | &le 25 bar (362.6 psi) | |
Density | version S2: &ge 0.8 g/cm3 version S3: &ge 0.7 g/cm3 | |
Ambient conditions | ||
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP65 | |
Connection | version LML: terminal box, max. 9 terminals version LML-PVC1: connection cable 1 m (3.3 ft), 0.75 mm2 | |
Material | float, guide tube, process connection: stainless steel 1.4571/316Ti connection cable: PVC terminal box: aluminum die-casting | |
Dimensions | float: - version S2: cylinder &empty44 mm x 52 mm - version S3: ball &empty52 mm guide tube: &empty12 mm, max. length 3000 mm terminal box: 80 x 75 x 55 mm | |
Process connection | thread G3/8A, G1-1/2A, G2A to DIN/ISO 228/1 | |
Accessories | ||
Optional accessories | LML-Z11 set collar, 1.4571/316Ti LML-FS2 float, cylinder, Ø44 mm x 52 mm, 1.4571/316Ti LML-FS3 float, ball, Ø52 mm, 1.4571/316Ti |
General specifications | ||
---|---|---|
Measuring method | The tuning fork is brought to its resonance frequency by means of a piezoelectric drive. If the tuning fork is covered by liquid, this frequency changes. The electronics monitor the resonance frequency and indicate whether the tuning fork is freely vibrating or is covered by liquid. | |
Construction type | compact device device with short tube | |
Operating mode | MAX = maximum safety: The device keeps the electronic switch closed as long as the liquid level is below the fork. example application: overspill protection MIN = minimum safety: The device keeps the electronic switch closed as long as the fork is immersed in liquid. example application: dry running protection of pumps The electronic switch opens if the limit is reached, if a fault occurs or in the event of a power fails (quiescent current principle) | |
Supply | ||
Rated voltage | - DC-PNP: 10 ... 35 V DC, 3-wire - AC/DC: 20 ... 253 V AC/DC, 2-wire | |
Current consumption | - DC-PNP: < 15 mA - AC/DC: < 3.8 mA | |
Input | ||
Measured variable | density | |
Measurement range | min. 0.7 g/cm3, optional> 0.5 g/cm3 | |
Output | ||
Output type | switch output | |
Switching current | max. 250 mA | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-64 | |
Climate class | DIN EN 60068-2-38/IEC 68-2-38 | |
Measurement accuracy | ||
Reference operating conditions | - ambient temperature: 25 °C (+77 °F) - process pressure: 1 bar (14.5 psi) - fluid: water (density: approx. 1 g/cm3, viscosity: 1 mm2/s) - medium temperature: 25 °C (+77 °F) - density setting: > 0.7 g/cm3 - switching time delay: standard (0,5 s, 1 s) | |
Measured value resolution | < 0.5 mm | |
Measuring frequency | approx. 1100 Hz in air | |
Switching point | 13 mm ± 1 mm | |
Non-repeatability | ± 1 mm acc. to DIN 61298-2 | |
Hysteresis | max. 3 mm | |
Influence of ambient temperature | negligible | |
Influence of medium temperature | -25 µm/°C | |
Influence of medium pressure | -20 µm/bar | |
Switching time | - 0.5 s when tuning fork is covered - 1.0 s when tuning fork is uncovered - other switching times on request | |
Operating conditions | ||
Installation conditions | ||
Installation position | see section mounting position | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Shock resistance | a = 300 m/s2 = 30 g, 3 planes x 2 directions x 3 shocks x 18 ms, as per test Ea | |
Vibration resistance | a(RMS) = 50 m/s2, ASD = 1.25 (m/s2)2/Hz, f = 5 to 2000 Hz, t = 3 x 2 h | |
Process conditions | ||
Medium temperature | -40 ... +100 °C (-40 ... +212 °F) -40 ... +150 °C (-40 ... +302 °F) | |
Process pressure (static pressure) | -1 ... +40 bar (-14.5 ... +580 psi) | |
State of aggregation | liquid | |
Density | min. 0.7 g/cm3, optional> 0.5 g/cm3 | |
Viscosity | 1 ... 10000 mPa/s, dynamic viscosity | |
Solid contents | < &empty5 mm | |
Mechanical specifications | ||
Degree of protection | - IP65/67, NEMA 4X enclosure (plug M12) - IP65, NEMA 4X enclosure (valve plug) - IP65/68, NEMA 4X/6P enclosure (cable) | |
Connection | - cable 5 m - valve plug NPT1/2 - valve plug QUICKON - valve plug M16 - plug M12 | |
Material | see technical information (TI) | |
Surface quality | Ra < 3.2 µm | |
Mass | see technical information (TI) | |
Dimensions | see technical information (TI) | |
Process connection | - thread ISO 228 G1/2, G3/4, G1 - thread EN 10226 R1/2, R3/4, R1 - thread ASME MNPT1/2, MNPT3/4, MNPT1 | |
Certificates and approvals | ||
Overspill protection | Z-65.11-554 (overspill protection acc. to WHG) Z-65.40-555 (leak detection system acc. to WHG) If you need the approvals also in paper form, select the option WH in the type code. | |
Accessories | ||
Designation | see technical information (TI) |
General specifications | ||
---|---|---|
Measuring method | The tuning fork is brought to its resonance frequency by means of a piezoelectric drive. If the tuning fork is covered by liquid, this frequency changes. The electronics monitor the resonance frequency and indicate whether the tuning fork is freely vibrating or is covered by liquid. | |
Construction type | compact device device with short tube | |
Operating mode | MAX = maximum safety: The device keeps the electronic switch closed as long as the liquid level is below the fork. example application: overspill protection MIN = minimum safety: The device keeps the electronic switch closed as long as the fork is immersed in liquid. example application: dry running protection of pumps The electronic switch opens if the limit is reached, if a fault occurs or in the event of a power fails (quiescent current principle) | |
Supply | ||
Rated voltage | - DC-PNP: 10 ... 35 V DC, 3-wire - AC/DC: 20 ... 253 V AC/DC, 2-wire | |
Current consumption | - DC-PNP: < 15 mA - AC/DC: < 3.8 mA | |
Input | ||
Measured variable | density | |
Measurement range | min. 0.7 g/cm3, optional> 0.5 g/cm3 | |
Output | ||
Output type | switch output | |
Switching current | max. 250 mA | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-64 | |
Climate class | DIN EN 60068-2-38/IEC 68-2-38 | |
Measurement accuracy | ||
Reference operating conditions | - ambient temperature: 25 °C (+77 °F) - process pressure: 1 bar (14.5 psi) - fluid: water (density: approx. 1 g/cm3, viscosity: 1 mm2/s) - medium temperature: 25 °C (+77 °F) - density setting: > 0.7 g/cm3 - switching time delay: standard (0,5 s, 1 s) | |
Measured value resolution | < 0.5 mm | |
Measuring frequency | approx. 1100 Hz in air | |
Switching point | 13 mm ± 1 mm | |
Non-repeatability | ± 1 mm acc. to DIN 61298-2 | |
Hysteresis | max. 3 mm | |
Influence of ambient temperature | negligible | |
Influence of medium temperature | -25 µm/°C | |
Influence of medium pressure | -20 µm/bar | |
Switching time | - 0.5 s when tuning fork is covered - 1.0 s when tuning fork is uncovered - other switching times on request | |
Operating conditions | ||
Installation conditions | ||
Installation position | see section mounting position | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Shock resistance | a = 300 m/s2 = 30 g, 3 planes x 2 directions x 3 shocks x 18 ms, as per test Ea | |
Vibration resistance | a(RMS) = 50 m/s2, ASD = 1.25 (m/s2)2/Hz, f = 5 to 2000 Hz, t = 3 x 2 h | |
Process conditions | ||
Medium temperature | -40 ... +100 °C (-40 ... +212 °F) -40 ... +150 °C (-40 ... +302 °F) | |
Process pressure (static pressure) | -1 ... +40 bar (-14.5 ... +580 psi) | |
State of aggregation | liquid | |
Density | min. 0.7 g/cm3, optional> 0.5 g/cm3 | |
Viscosity | 1 ... 10000 mPa/s, dynamic viscosity | |
Solid contents | < &empty5 mm | |
Mechanical specifications | ||
Degree of protection | - IP65/67, NEMA 4X enclosure (plug M12) - IP65, NEMA 4X enclosure (valve plug) - IP65/68, NEMA 4X/6P enclosure (cable) - IP66/68/69, NEMA 4X/6P Enclosure (M12 plug for metal housing cover) | |
Connection | - cable 5 m - valve plug NPT1/2 - valve plug QUICKON - valve plug M16 - plug M12 | |
Material | see technical information (TI) | |
Surface quality | Ra < 1.5 µm (EHEDG) Ra < 0.76 µm (EHEDG, 3-A) | |
Mass | see technical information (TI) | |
Dimensions | see technical information (TI) | |
Process connection | - thread ISO 228 G1/2, G3/4, G1 - DIN 11851 DN25 PN40, DN32 PN40, DN40 PN40 - thread ASME MNPT1/2, MNPT3/4, MNPT1 - thread M24 x 1,5 for flush-mounted installation in adapter - DIN 11851 DN25 PN40, DN32 PN40, DN40 PN40 (dairy pipe) - Tri-Clamp ISO 2852 DN25-38, DN40-51 - Flush-mounting in weld-in adapter Rd52, tuning fork can be aligned | |
Certificates and approvals | ||
Sanitary compatibility | EHEDG , see approval (ZE) | |
Overspill protection | Z-65.11-554 (overspill protection acc. to WHG) Z-65.40-555 (leak detection system acc. to WHG) If you need the approvals also in paper form, select the option WH in the type code. | |
Accessories | ||
Designation | see technical information (TI) |
General specifications | ||
---|---|---|
Measuring method | A piezoelectric drive excites the vibrating rod of the device to its resonance frequency. If medium covers the vibrating rod, the rod's vibrating amplitude changes (the vibration is damped). The electronics of the device compare the actual amplitude with a target value and indicates whether the vibrating rod is vibrating freely or whether it is covered by medium. | |
Equipment architecture | The measuring system consists of: - the device with electronic insert - a supply point - the connected control systems, switching units, signalling systems (e. g. lamps, horns, PCS, PLC, etc.) | |
Construction type | compact device | |
Operating mode | MAX = maximum safety: The device switches if the probe is covered or if the supply voltage is disconnected in a safety-oriented manner (signal on alarm). example application: overspill protection MIN = minimum safety: The device switches if the probe is uncovered or if the supply voltage is disconnected in a safetyoriented manner (signal on alarm). example application: dry-running protection | |
Supply | ||
Rated voltage | electronic insert FEM22 (E5): 10 ... 45 V DC electronic insert FEM24 (WA): 19 ... 253 V AC, 50/60 Hz or 19 ... 55 V DC | |
Ripple | electronic insert FEM22 (E5): max. 5 V, 0 ... 400 Hz | |
Current consumption | electronic insert FEM22 (E5): max. 18 mA | |
Reverse polarity protection | separation voltage 2.2 kV | |
Electrical specifications | ||
Surge protection | electronic insert FEM22 (E5) : overvoltage category III | |
Input | ||
Input signal | probe covered - small amplitude probe not covered - large amplitude | |
Measured variable | level (according to the mounting location and the overall length) | |
Measurement range | The measuring range depends on the mounting location of the device | |
Output | ||
Output signal | digital | |
Galvanic isolation | ||
Input/Other circuits | electronic insert FEM24 (WA) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | electronic insert FEM24 (WA) : EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529:2001 | |
Vibration resistance | EN 60068-2-27 | |
Climate class | EN 60068, part 2-38, fig. 2a | |
Measurement accuracy | ||
Measuring frequency | 700 ... 800 Hz | |
Switching time | when covering the sensor approx. 0.5 s, when uncovering the sensor approx. 1.0 s | |
Operating conditions | ||
Installation conditions | ||
Installation position | see section mounting position | |
Process conditions | ||
Process temperature | -40 ... 150 °C (-40 ... 302 °F) | |
Medium pressure limits | -1 ... 25 bar max. working pressure 25 bar, burst pressure 100 bar | |
Thermal shock resistance | max. 120 K | |
State of aggregation | solids | |
Solid contents | &le &empty25 mm | |
Bulk density | &ge 200 g/l, not fluidised | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP66/IP67, NEMA 4X | |
Connection | gland M20 thread G1/2, NPT1/2 | |
Material | F16 housing: PTB-FR, cover with transparent glass made of PA12, EPDM cover seal F18 housing: aluminum EN-AC-AlSi10Mg, plastic coated cover seal: EPDM process connections, sensor: stainless steel 1.4435/316L | |
Mass | device with F16 housing, electronic insert FEM24 (WA) and R1 thread: approx. 1.0 kg | |
Dimensions | max. &empty85 mm (3.3 inch), length 372 mm (14.6 inch) | |
Process connection | thread R1, R1-1/2 acc. to DIN 2999 thread 1-1/4 - 11-1/2 NPT, 1-1/2 - 11-1/2 NPT acc. to ANSI B 1.20.1 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | KEMA 06 ATEX 0055 | |
Group, category, type of protection | II 1/3D Ex ta/tc IIIC T170°C Da/Dc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-31:2009 | |
International approvals | ||
IECEx approval | IECEx DEK 11.0068 | |
Approved for | Ex ta/tc IIIC T170°C Da/Dc |
General specifications | ||
---|---|---|
Measuring method | A piezoelectric drive excites the vibrating rod of the device to its resonance frequency. If medium covers the vibrating rod, the rod's vibrating amplitude changes (the vibration is damped). The electronics of the device compare the actual amplitude with a target value and indicates whether the vibrating rod is vibrating freely or whether it is covered by medium. | |
Equipment architecture | The measuring system consists of: - the device with electronic insert - a supply point - the connected control systems, switching units, signalling systems (e. g. lamps, horns, PCS, PLC, etc.) | |
Construction type | device with pipe extension | |
Operating mode | MAX = maximum safety: The device switches if the probe is covered or if the supply voltage is disconnected in a safety-oriented manner (signal on alarm). example application: overspill protection MIN = minimum safety: The device switches if the probe is uncovered or if the supply voltage is disconnected in a safetyoriented manner (signal on alarm). example application: dry-running protection | |
Supply | ||
Rated voltage | electronic insert FEM22 (E5): 10 ... 45 V DC electronic insert FEM24 (WA): 19 ... 253 V AC, 50/60 Hz or 19 ... 55 V DC | |
Ripple | electronic insert FEM22 (E5): max. 5 V, 0 ... 400 Hz | |
Current consumption | electronic insert FEM22 (E5): max. 18 mA | |
Reverse polarity protection | separation voltage 2.2 kV | |
Electrical specifications | ||
Surge protection | electronic insert FEM22 (E5) : overvoltage category III | |
Input | ||
Input signal | probe covered - small amplitude probe not covered - large amplitude | |
Measured variable | level (according to the mounting location and the overall length) | |
Measurement range | The measuring range depends on the mounting location of the device and the length of the pipe extension selected. The pipe extension is available in the following lengths: 500 mm, 1000 mm, 1500 mm, 20 inch, 40 inch, 60 inch | |
Output | ||
Output signal | digital | |
Galvanic isolation | ||
Input/Other circuits | electronic insert FEM24 (WA) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | electronic insert FEM24 (WA) : EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529:2001 | |
Vibration resistance | EN 60068-2-27 | |
Climate class | EN 60068, part 2-38, fig. 2a | |
Measurement accuracy | ||
Measuring frequency | 700 ... 800 Hz | |
Switching time | when covering the sensor approx. 0.5 s, when uncovering the sensor approx. 1.0 s | |
Operating conditions | ||
Installation conditions | ||
Installation position | see section mounting position | |
Process conditions | ||
Process temperature | -40 ... 150 °C (-40 ... 302 °F) | |
Medium pressure limits | -1 ... 25 bar max. working pressure 25 bar, burst pressure 100 bar | |
Thermal shock resistance | max. 120 K | |
State of aggregation | solids | |
Solid contents | &le &empty25 mm | |
Bulk density | &ge 200 g/l, not fluidised | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Mechanical specifications | ||
Degree of protection | IP66/IP67, NEMA 4X | |
Connection | gland M20 thread G1/2, NPT1/2 | |
Material | F16 housing: PTB-FR, cover with transparent glass made of PA12, EPDM cover seal F18 housing: aluminum EN-AC-AlSi10Mg, plastic coated cover seal: EPDM process connections, sensor: stainless steel 1.4435/316L | |
Mass | device with F16 housing, electronic insert FEM24 (WA) and R1 thread: - 500 mm (20 inch) = approx. 1.3 kg - 1000 mm (40 inch) = approx. 2.0 kg - 1500 mm (60 inch) = approx. 2.6 kg | |
Dimensions | max. &empty85 mm (3.3 inch), length 160 mm (6.3 inch) + L L = 500 mm, 1000 mm, 1500 mm, 20 inch, 40 inch, 60 inch | |
Process connection | thread R1, R1-1/2 acc. to DIN 2999 thread 1-1/4 - 11-1/2 NPT, 1-1/2 - 11-1/2 NPT acc. to ANSI B 1.20.1 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | KEMA 06 ATEX 0055 | |
Group, category, type of protection | II 1/3D Ex ta/tc IIIC T170°C Da/Dc | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-31:2009 | |
International approvals | ||
IECEx approval | IECEx DEK 11.0068 | |
Approved for | Ex ta/tc IIIC T170°C Da/Dc | |
Accessories | ||
Optional accessories | LVL-Z200 sliding sleeve for pressurized containerLVL-Z201 sliding sleeve for pressurized container LVL-Z202 sliding sleeve for unpressurized container LVL-Z203 sliding sleeve for unpressurized container |
General specifications | ||
---|---|---|
Function principle | limit detection Maximum or minimum detection in tanks or pipelines containing all types of liquids including use in explosion hazardous areas. Particularly suited to very aggressive liquids thanks to high degree of corrosion protection. | |
Measuring method | The forks of the sensors vibrate at their intrinsic frequency. This frequency is reduced when covered with liquid. The change in frequency then activates the limit switch. | |
Construction type | compact device | |
Supply | ||
Rated voltage | electronic insert FEL50A (PA): 9 ... 32 V DC electronic insert FEL51 (AC): 253 V AC, 50/60 Hz electronic insert FEL52 (E5): 10 ... 55 V DC electronic insert FEL54 (WA): 19 ... 253 V AC, 50/60 Hz or 19 ... 55 V DC electronic insert FEL55 (SI): 11 ... 36 V DC, PLC electronic insert FEL56 (N1), FEL58 (N2): isolating amplifier acc. to EN 60947-5-6 (NAMUR) | |
Current consumption | electronic insert FEL52 (E5): max. 15 mA | |
Electrical specifications | ||
Surge protection | electronic insert FEL51 (AC), electronic insert FEL52 (E5), electronic insert FEL54 (WA), electronic insert FEL55 (SI): overvoltage category III | |
Input | ||
Switching point | see section switch point | |
Measured variable | limit level (limit value) | |
Measurement range | depends on mounting point | |
Output | ||
Switching delay | when fork is covered: approx. 0.5 s, when fork is exposed: approx. 1.0 s (other switching times on request) additionally configurable for PROFIBUS PA (electronic insert FEL50A (PA)): 0.5 ... 60 s | |
Switch behaviour | switch-over for minimum/maximum residual current safety on electronic insert MAX = maximum safety: The output switches to the power fail response when the fork is covered. for use with overspill protection for example MIN = minimum safety: The output switches to the power fail response when the fork is exposed. for use with dry running protection for example When switching on the power supply the output assumes the alarm signal. After max. 2 s it assumes the correct switching mode. | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Vibration resistance | EN 60068-2-6 | |
Climate class | DIN EN 60068-2-38/IEC 68-2-38 | |
Measurement accuracy | ||
Reference operating conditions | ambient temperature: 23 °C (73.4 °F), medium temperature: 23 °C (73.4 °F), product density: 1 g/cm3 (water), viscosity: 1 mm2/s, medium pressure pe: 0 bar, sensor mounting: vertical from above, density switch: to > 0.7 g/cm3 | |
Maximum measured error | max. ± 1 mm, specified by mounting position | |
Non-repeatability | 0.1 mm | |
Hysteresis | approx. 2 mm | |
Influence of medium density | max. +4.8 ... -3.5 mm (0.5 ... 1.5 g/cm3) | |
Influence of medium temperature | max. +1.4 ... -2.8 mm (-40 ... 150 °C (-40 ... 302 °F)) | |
Influence of medium pressure | max. 0 ... -2.5 mm (-1 ... 64 bar) | |
Operating conditions | ||
Installation conditions | ||
Installation position | any position | |
Process conditions | ||
Medium temperature | -50 ... 150 °C (-58 ... 302 °F) , exceptions see process connections | |
Medium pressure | pe = -1 ... 64 bar (-14.5 ... 928.3 psi) over the entire temperature range , exceptions see process connections | |
Test pressure | max. 100 bar (1.5 times the medium pressure pe), no function during test pressure, burst pressure of diaphragm 200 bar | |
Thermal shock resistance | max. 120 °C/s (max. 120 K/s) | |
State of aggregation | liquid | |
Density | min. 0.5 g/cm3 (compact housing 0.7 g/cm3), other density settings on request | |
Viscosity | max. 10000 mm2/s (max. 10000 cSt) | |
Solid contents | < &empty5 mm | |
Ambient conditions | ||
Ambient temperature | -50 ... 70 °C (-58 ... 158 °F) , function with reduced data values see section ambient temperature | |
Storage temperature | -50 ... 80 °C (-58 ... 176 °F) | |
Vibration resistance | 10 ... 50 Hz, 0.15 mm, 100 cycles | |
Mechanical specifications | ||
Degree of protection | polyester, steel, and aluminum housing: IP66/IP67 compact housing: - IP65 with valve connector PG11 or 1/2NPT - IP66/IP68 with M12 x 1 connector without LEDs (1.4435/316L) - IP69K with M12 x 1 connector with LEDs (1.4435/316L) | |
Connection | electronic inserts: cross section max. 2.5 mm2, lace in end splice in acc. with DIN 46228 ground lead in housing: cross section max. 2.5 mm2 external equipotential bonding: cross section 4 mm2 | |
Material | wetted parts: - process connection: 1.4435/316L or 2.4610/Alloy C4 - vibration fork: 1.4435/316L or 2.4610/Alloy C4 - flat seal for process connection G2* or G3*: elastomer fibre, asbestos-free housings: - polyester housing: PBT-FR with PBT-FR cover or with PA12 cover with sight glass, cover seal: EPDM - stainless steel housing: 1.4435/316L, cover seal: silicone - aluminum housing: EN-AC-AlSi10Mg, plastic-coated, cover seal: EPDM - compact housing with valve connector or M12 connector: 1.4435/316L cable gland: polyamide or brass, nickel-plated temperature spacer: 1.4435/316L flameproof bushing: 1.4435/316L | |
Surface quality | Ra < 3.2 µm/80 grit: length, spacer, bushings *A, *B, *E | |
Mass | 600 g , basic weight: compact sensor, electronic insert, stainless steel housing, process connection G2*, additional weight is dependent on housing and process connection process connections: - A31 1000 g, A41 1200 g, A51 1500 g, A6* 2400 g, A81 4900 g, A91 7000 g - C45 1400 g, C51 1200 g, C71 1600 g, C75 3200 g, C95 5900 g, CA3 5600 g - D45 1400 g, D51 1200 g, D71 1600 g, D75 3200 g, D95 5900 g, DA3 5600 g - F45 1400 g, F51 1200 g, F55 2000 g, F61 1400 g, F65 2400 g, F71 1600 g, F75 3200 g, F7F 2600 g, F81 2400 g, F85 4300 g, F93 4800 g, F95 5900 g, FA3 5600 g, FA5 7500 g - G3* 200 g - J13 no information, J16 no information, J17 1700 g, J19 no information, J1A no information, J1C 1700 g - N3* 200 g, N75 2900 g - R3* 200 g - T51 no information, T61 100 g temperature spacer, flameproof bushing: - IA 600 g, QA 700 g | |
Dimensions | housing: diameter max. 85 mm, height max. 173 mm temperature separator, flameproof bushing: additional length L 140 mm process connection: length L 66.5 ... 80 mm extension: length type II, for vertical installation from above same switching point as Vibracon LVL1, LVL2 vibration fork: width 17.5 mm, fork width 10 mm, length 25 mm | |
Process connection | - cylindrical thread G3/4A, G1A to DIN ISO 228/1 with flat seal to DIN 7603 - conical thread R3/4, R1 to DIN 2999, part 1 - conical thread 3/4NPT, 1NPT to ANSI B 1.20.1 - flush-mounted with welding sleeve to factory standard (G3/4A, G1A) - Triclamp 1-1/2 inch, 2 inch to ISO 2852 - flanges to EN 1092-1 from DN25, to ANSI B 16.5 from 1 inch, to JIS B 2238 (RF) from DN25 For further information see type code. | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | see instruction manuals (SI) | |
International approvals | ||
FM approval | see control drawings (ZD) | |
CSA approval | see control drawings (ZD) | |
IECEx approval | see instruction manuals (SI) | |
Certificates and approvals | ||
SIL classification | up to SIL2 acc. to IEC 61508 | |
Overspill protection | see approval (ZE) | |
Accessories | ||
Designation | see technical information (TI) |
General specifications | ||
---|---|---|
Function principle | limit detection Maximum or minimum detection in tanks or pipelines containing all types of liquids including use in explosion hazardous areas. Particularly suited to very aggressive liquids thanks to high degree of corrosion protection. | |
Measuring method | The forks of the sensors vibrate at their intrinsic frequency. This frequency is reduced when covered with liquid. The change in frequency then activates the limit switch. | |
Construction type | device with extension tube | |
Supply | ||
Rated voltage | electronic insert FEL50A (PA): 9 ... 32 V DC electronic insert FEL51 (AC): 253 V AC, 50/60 Hz electronic insert FEL52 (E5): 10 ... 55 V DC electronic insert FEL54 (WA): 19 ... 253 V AC, 50/60 Hz or 19 ... 55 V DC electronic insert FEL55 (SI): 11 ... 36 V DC, PLC electronic insert FEL56 (N1), FEL58 (N2): isolating amplifier acc. to EN 60947-5-6 (NAMUR) | |
Current consumption | electronic insert FEL52 (E5): max. 15 mA | |
Electrical specifications | ||
Surge protection | electronic insert FEL51 (AC), electronic insert FEL52 (E5), electronic insert FEL54 (WA), electronic insert FEL55 (SI): overvoltage category III | |
Input | ||
Switching point | see section switch point | |
Measured variable | limit level (limit value) | |
Measurement range | depends on mounting point and pipe extension up to 3000 mm , larger sizes on request | |
Output | ||
Switching delay | when fork is covered: approx. 0.5 s, when fork is exposed: approx. 1.0 s (other switching times on request) additionally configurable for PROFIBUS PA (electronic insert FEL50A (PA)): 0.5 ... 60 s | |
Switch behaviour | switch-over for minimum/maximum residual current safety on electronic insert MAX = maximum safety: The output switches to the power fail response when the fork is covered. for use with overspill protection for example MIN = minimum safety: The output switches to the power fail response when the fork is exposed. for use with dry running protection for example When switching on the power supply the output assumes the alarm signal. After max. 2 s it assumes the correct switching mode. | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Vibration resistance | EN 60068-2-6 | |
Climate class | DIN EN 60068-2-38/IEC 68-2-38 | |
Measurement accuracy | ||
Reference operating conditions | ambient temperature: 23 °C (73.4 °F), medium temperature: 23 °C (73.4 °F), product density: 1 g/cm3 (water), viscosity: 1 mm2/s, medium pressure pe: 0 bar, sensor mounting: vertical from above, density switch: to > 0.7 g/cm3 | |
Maximum measured error | max. ± 1 mm, specified by mounting position | |
Non-repeatability | 0.1 mm | |
Hysteresis | approx. 2 mm | |
Influence of medium density | max. +4.8 ... -3.5 mm (0.5 ... 1.5 g/cm3) | |
Influence of medium temperature | max. +1.4 ... -2.8 mm (-40 ... 150 °C (-40 ... 302 °F)) | |
Influence of medium pressure | max. 0 ... -2.5 mm (-1 ... 64 bar) | |
Operating conditions | ||
Installation conditions | ||
Installation position | any position | |
Process conditions | ||
Medium temperature | -50 ... 150 °C (-58 ... 302 °F) , exceptions see process connections | |
Medium pressure | pe = -1 ... 64 bar (-14.5 ... 928.3 psi) over the entire temperature range , exceptions see process connections | |
Test pressure | max. 100 bar (1.5 times the medium pressure pe), no function during test pressure, burst pressure of diaphragm 200 bar | |
Thermal shock resistance | max. 120 °C/s (max. 120 K/s) | |
State of aggregation | liquid | |
Density | min. 0.5 g/cm3 (compact housing 0.7 g/cm3), other density settings on request | |
Viscosity | max. 10000 mm2/s (max. 10000 cSt) | |
Solid contents | < &empty5 mm | |
Ambient conditions | ||
Ambient temperature | -50 ... 70 °C (-58 ... 158 °F) , function with reduced data values see section ambient temperature | |
Storage temperature | -50 ... 80 °C (-58 ... 176 °F) | |
Vibration resistance | 10 ... 50 Hz, 0.15 mm, 100 cycles | |
Mechanical specifications | ||
Degree of protection | polyester, steel, and aluminum housing: IP66/IP67 compact housing: - IP65 with valve connector PG11 or 1/2NPT - IP66/IP68 with M12 x 1 connector without LEDs (1.4435/316L) - IP69K with M12 x 1 connector with LEDs (1.4435/316L) | |
Connection | electronic inserts: cross section max. 2.5 mm2, lace in end splice in acc. with DIN 46228 ground lead in housing: cross section max. 2.5 mm2 external equipotential bonding: cross section 4 mm2 | |
Material | wetted parts: - process connection: 1.4435/316L - vibration fork: 1.4435/316L - flat seal for process connection G2* or G3*: elastomer fibre, asbestos-free housings: - polyester housing: PBT-FR with PBT-FR cover or with PA12 cover with sight glass, cover seal: EPDM - stainless steel housing: 1.4435/316L, cover seal: silicone - aluminum housing: EN-AC-AlSi10Mg, plastic-coated, cover seal: EPDM - compact housing with valve connector or M12 connector: 1.4435/316L cable gland: polyamide or brass, nickel-plated temperature spacer: 1.4435/316L flameproof bushing: 1.4435/316L | |
Surface quality | Ra < 1.5 µm/120 grit: length, spacer, bushings *C Ra < 0.3 µm/320 grit: length, spacer, bushings *D | |
Mass | 700 g , basic weight: compact sensor, electronic insert, stainless steel housing, process connection G2*, additional weight is dependent on extension tube, housing and process connection process connections: - A31 1000 g, A41 1200 g, A51 1500 g, A6* 2400 g, A81 4900 g, A91 7000 g - C45 1400 g, C51 1200 g, C71 1600 g, C75 3200 g, C95 5900 g, CA3 5600 g - D75 3200 g, D7A 300 g, D7D 300 g, D95 5900 g, DA3 5600 g - F45 1400 g, F51 1200 g, F55 2000 g, F61 1400 g, F65 2400 g, F71 1600 g, F75 3200 g, F81 2400 g, F85 4300 g, F93 4800 g, F95 5900 g, FA3 5600 g, FA5 7500 g - G3E 200 g - J13 no information, J16 no information, J17 1700 g, J19 no information, J1A no information, J1C 1700 g - R*R no information - S13 300 g, S61 200 g, SV1 no information - T51 no information, T61 100 g temperature spacer, flameproof bushing: - I* 600 g, Q* 700 g | |
Dimensions | housing: diameter max. 85 mm, height max. 173 mm temperature separator, flameproof bushing: additional length L 140 mm process connection: length L 55.5 ... 80 mm extension: any length L from 148 ... 3000 mm, larger sizes on request extension: length type II, for vertical installation from above same switching point as Vibracon LVL1, LVL2 vibration fork: width 17.5 mm, fork width 10 mm, length 25 mm | |
Process connection | - cylindrical thread G3/4A, G1A to DIN ISO 228/1 with flat seal to DIN 7603 - conical thread R3/4, R1 to DIN 2999, part 1 - flush-mounted with welding sleeve to factory standard (G3/4A, G1A) - flush-mounted with welding neck to factory standard (1 inch), sensor can be positioned - Triclamp 1-1/2 inch, 2 inch to ISO 2852 - threaded pipe joint DN32, DN40, DN50 to DIN 1185 - aseptic connection DN50 to DIN 11864-1 form A for pipe DIN 11850 - SMS connection 2 inch (DN51) - DRD flange, 65 mm - Varivent® DN50 (50/40) to factory standard Tuchenhagen - flanges to EN 1092-1 from DN25, to ANSI B 16.5 from 1 inch, to JIS B 2238 (RF) from DN25 For further information see type code. | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | see instruction manuals (SI) | |
International approvals | ||
FM approval | see control drawings (ZD) | |
CSA approval | see control drawings (ZD) | |
IECEx approval | see instruction manuals (SI) | |
Certificates and approvals | ||
SIL classification | up to SIL2 acc. to IEC 61508 | |
Overspill protection | see approval (ZE) | |
Accessories | ||
Designation | see technical information (TI) |
General specifications | ||
---|---|---|
Function principle | limit detection Maximum or minimum detection in tanks or pipelines containing all types of liquids including use in explosion hazardous areas. Particularly suited to very aggressive liquids thanks to high degree of corrosion protection. | |
Measuring method | The forks of the sensors vibrate at their intrinsic frequency. This frequency is reduced when covered with liquid. The change in frequency then activates the limit switch. | |
Construction type | compact device | |
Supply | ||
Rated voltage | electronic insert FEL50A (PA): 9 ... 32 V DC electronic insert FEL51 (AC): 253 V AC, 50/60 Hz electronic insert FEL52 (E5): 10 ... 55 V DC electronic insert FEL54 (WA): 19 ... 253 V AC, 50/60 Hz or 19 ... 55 V DC electronic insert FEL55 (SI): 11 ... 36 V DC, PLC electronic insert FEL56 (N1), FEL58 (N2): isolating amplifier acc. to EN 60947-5-6 (NAMUR) | |
Current consumption | electronic insert FEL52 (E5): max. 15 mA | |
Electrical specifications | ||
Surge protection | electronic insert FEL51 (AC), electronic insert FEL52 (E5), electronic insert FEL54 (WA), electronic insert FEL55 (SI): overvoltage category III | |
Input | ||
Switching point | see section switch point | |
Measured variable | limit level (limit value) | |
Measurement range | depends on mounting point | |
Output | ||
Switching delay | when fork is covered: approx. 0.5 s, when fork is exposed: approx. 1.0 s (other switching times on request) additionally configurable for PROFIBUS PA (electronic insert FEL50A (PA)): 0.5 ... 60 s | |
Switch behaviour | switch-over for minimum/maximum residual current safety on electronic insert MAX = maximum safety: The output switches to the power fail response when the fork is covered. for use with overspill protection for example MIN = minimum safety: The output switches to the power fail response when the fork is exposed. for use with dry running protection for example When switching on the power supply the output assumes the alarm signal. After max. 2 s it assumes the correct switching mode. | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Vibration resistance | EN 60068-2-6 | |
Climate class | DIN EN 60068-2-38/IEC 68-2-38 | |
Measurement accuracy | ||
Reference operating conditions | ambient temperature: 23 °C (73.4 °F), medium temperature: 23 °C (73.4 °F), product density: 1 g/cm3 (water), viscosity: 1 mm2/s, medium pressure pe: 0 bar, sensor mounting: vertical from above, density switch: to > 0.7 g/cm3 | |
Maximum measured error | max. ± 1 mm, specified by mounting position | |
Non-repeatability | 0.1 mm | |
Hysteresis | approx. 2 mm | |
Influence of medium density | max. +4.8 ... -3.5 mm (0.5 ... 1.5 g/cm3) | |
Influence of medium temperature | max. +1.4 ... -2.8 mm (-40 ... 150 °C (-40 ... 302 °F)) | |
Influence of medium pressure | max. 0 ... -2.5 mm (-1 ... 64 bar) | |
Operating conditions | ||
Installation conditions | ||
Installation position | with short pipe (up to 500 mm (19.7 inch)) any position, with long pipe vertical | |
Process conditions | ||
Medium temperature | -50 ... 150 °C (-58 ... 302 °F) , exceptions see process connections | |
Medium pressure | pe = -1 ... 64 bar (-14.5 ... 928.3 psi) over the entire temperature range , exceptions see process connections | |
Test pressure | max. 100 bar (1.5 times the medium pressure pe), no function during test pressure, burst pressure of diaphragm 200 bar | |
Thermal shock resistance | max. 120 °C/s (max. 120 K/s) | |
State of aggregation | liquid | |
Density | min. 0.5 g/cm3 (compact housing 0.7 g/cm3), other density settings on request | |
Viscosity | max. 10000 mm2/s (max. 10000 cSt) | |
Solid contents | < &empty5 mm | |
Ambient conditions | ||
Ambient temperature | -50 ... 70 °C (-58 ... 158 °F) , function with reduced data values see section ambient temperature | |
Storage temperature | -50 ... 80 °C (-58 ... 176 °F) | |
Vibration resistance | 10 ... 50 Hz, 0.15 mm, 100 cycles | |
Mechanical specifications | ||
Degree of protection | polyester, steel, and aluminum housing: IP66/IP67 compact housing: - IP65 with valve connector PG11 or 1/2NPT - IP66/IP68 with M12 x 1 connector without LEDs (1.4435/316L) - IP69K with M12 x 1 connector with LEDs (1.4435/316L) | |
Connection | electronic inserts: cross section max. 2.5 mm2, lace in end splice in acc. with DIN 46228 ground lead in housing: cross section max. 2.5 mm2 external equipotential bonding: cross section 4 mm2 | |
Material | wetted parts: - process connection and extension tube: 1.4435/316L or 2.4610/Alloy C4 - vibration fork: 1.4435/316L or 2.4610/Alloy C4 - flat seal for process connection G2* or G3*: elastomer fibre, asbestos-free housings: - polyester housing: PBT-FR with PBT-FR cover or with PA12 cover with sight glass, cover seal: EPDM - stainless steel housing: 1.4435/316L, cover seal: silicone - aluminum housing: EN-AC-AlSi10Mg, plastic-coated, cover seal: EPDM - compact housing with valve connector or M12 connector: 1.4435/316L cable gland: polyamide or brass, nickel-plated temperature spacer: 1.4435/316L flameproof bushing: 1.4435/316L | |
Surface quality | Ra < 3.2 µm/80 grit: length, spacer, bushings *A, *B, *E | |
Mass | 600 g , basic weight: compact sensor, electronic insert, stainless steel housing, process connection G2*, additional weight is dependent on housing and process connection process connections: - A31 1000 g, A4* 1200 g, A5* 1500 g, A6* 2400 g, A72 4800 g, A81 4900 g, A82 6800 g, A91 7000 g, A92 11,5 kg, A93 17,3 kg - - C45 1400 g, C51 1200 g, C71 1600 g, C75 3200 g, C95 5900 g, CA3 5600 g - D45 1400 g, D51 1200 g, D71 1600 g, D75 3200 g, D95 5900 g, DA3 5600 g - F45 1400 g, F51 1200 g, F55 2000 g, F61 1400 g, F65 2400 g, F71 1600 g, F75 3200 g, F7F 2600 g, F81 2400 g, F85 4300 g, F93 4800 g, F95 5900 g, FA3 5600 g, FA5 7500 g - G3* 200 g - J13 no information, J16 no information, J17 1700 g, J19 no information, J1A no information, J1C 1700 g - N3* 200 g, N75 2900 g - R3* 200 g - T51 no information, T61 100 g extension tube, tempeprature spacers, flameproof bushings: - B* 900 g/m, C* 2300 g/100 inch - D* 100 g - J* 900 g/m and 600 g, K* 2300 g/100 inch and 600 g - L* 700 g - R* 900 g/m and 700 g, S* 2300 g/100 inch and 700 g - T* 800 g | |
Dimensions | housing: diameter max. 85 mm, height max. 173 mm temperature separator, flameproof bushing: additional length L 140 mm process connection: length L 66.5 ... 80 mm extension: length type II, for vertical installation from above same switching point as Vibracon LVL1, LVL2 vibration fork: width 17.5 mm, fork width 10 mm, length 25 mm | |
Process connection | - cylindrical thread G3/4A, G1A to DIN ISO 228/1 with flat seal to DIN 7603 - conical thread R3/4, R1 to DIN 2999, part 1 - conical thread 3/4NPT, 1NPT to ANSI B 1.20.1 - flush-mounted with welding sleeve to factory standard (G3/4A, G1A) - Triclamp 1-1/2 inch, 2 inch to ISO 2852 - flanges to EN 1092-1 from DN25, to ANSI B 16.5 from 1 inch, to JIS B 2238 (RF) from DN25 For further information see type code. | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | see instruction manuals (SI) | |
International approvals | ||
FM approval | see control drawings (ZD) | |
CSA approval | see control drawings (ZD) | |
IECEx approval | see instruction manuals (SI) | |
Certificates and approvals | ||
SIL classification | up to SIL2 acc. to IEC 61508 | |
Overspill protection | see approval (ZE) | |
Accessories | ||
Designation | see technical information (TI) |
General specifications | ||
---|---|---|
Function principle | limit detection Maximum or minimum detection in tanks or pipelines containing all types of liquids including use in explosion hazardous areas. Particularly suited to very aggressive liquids thanks to high degree of corrosion protection. | |
Measuring method | The forks of the sensors vibrate at their intrinsic frequency. This frequency is reduced when covered with liquid. The change in frequency then activates the limit switch. | |
Construction type | device with extension tube, coated with ECTFE | |
Supply | ||
Rated voltage | electronic insert FEL50A (PA): 9 ... 32 V DC electronic insert FEL51 (AC): 253 V AC, 50/60 Hz electronic insert FEL52 (E5): 10 ... 55 V DC electronic insert FEL54 (WA): 19 ... 253 V AC, 50/60 Hz or 19 ... 55 V DC electronic insert FEL55 (SI): 11 ... 36 V DC, PLC electronic insert FEL56 (N1), FEL58 (N2): isolating amplifier acc. to EN 60947-5-6 (NAMUR) | |
Current consumption | electronic insert FEL52 (E5): max. 15 mA | |
Electrical specifications | ||
Surge protection | electronic insert FEL51 (AC), electronic insert FEL52 (E5), electronic insert FEL54 (WA), electronic insert FEL55 (SI): overvoltage category III | |
Input | ||
Switching point | see section switch point | |
Measured variable | limit level (limit value) | |
Measurement range | depends on mounting point and pipe extension up to 3000 mm , larger sizes on request | |
Output | ||
Switching delay | when fork is covered: approx. 0.5 s, when fork is exposed: approx. 1.0 s (other switching times on request) additionally configurable for PROFIBUS PA (electronic insert FEL50A (PA)): 0.5 ... 60 s | |
Switch behaviour | switch-over for minimum/maximum residual current safety on electronic insert MAX = maximum safety: The output switches to the power fail response when the fork is covered. for use with overspill protection for example MIN = minimum safety: The output switches to the power fail response when the fork is exposed. for use with dry running protection for example When switching on the power supply the output assumes the alarm signal. After max. 2 s it assumes the correct switching mode. | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Vibration resistance | EN 60068-2-6 | |
Climate class | DIN EN 60068-2-38/IEC 68-2-38 | |
Measurement accuracy | ||
Reference operating conditions | ambient temperature: 23 °C (73.4 °F), medium temperature: 23 °C (73.4 °F), product density: 1 g/cm3 (water), viscosity: 1 mm2/s, medium pressure pe: 0 bar, sensor mounting: vertical from above, density switch: to > 0.7 g/cm3 | |
Maximum measured error | max. ± 1 mm, specified by mounting position | |
Non-repeatability | 0.1 mm | |
Hysteresis | approx. 2 mm | |
Influence of medium density | max. +4.8 ... -3.5 mm (0.5 ... 1.5 g/cm3) | |
Influence of medium temperature | max. 1.4 ... -2.8 mm (-40 ... 120 °C (-40 ... 248 °F)) | |
Influence of medium pressure | max. 0 ... -2 mm (0 ... 40 bar) | |
Operating conditions | ||
Installation conditions | ||
Installation position | with short pipe (up to 500 mm (19.7 inch)) any position, with long pipe vertical | |
Process conditions | ||
Medium temperature | -50 ... 150 °C (-58 ... 302 °F) , exceptions see process connections | |
Medium pressure | pe = -1 ... 40 bar (-14.5 ... 580.2 psi) over the entire temperature range , exceptions see process connections | |
Test pressure | max. 100 bar (1.5 times the medium pressure pe), no function during test pressure, burst pressure of diaphragm 200 bar | |
Pressure surge | max. 20 bar/s | |
Thermal shock resistance | max. 120 °C/s | |
State of aggregation | liquid | |
Density | min. 0.5 g/cm3 , other density settings on request | |
Viscosity | max. 10000 mm2/s | |
Solid contents | < &empty5 mm | |
Ambient conditions | ||
Ambient temperature | -50 ... 70 °C (-58 ... 158 °F) , function with reduced data values see section ambient temperature | |
Storage temperature | -50 ... 80 °C (-58 ... 176 °F) | |
Vibration resistance | 10 ... 50 Hz, 0.15 mm, 100 cycles | |
Mechanical specifications | ||
Degree of protection | polyester, steel, and aluminum housing: IP66/IP67 | |
Connection | electronic inserts: cross section max. 2.5 mm2, lace in end splice in acc. with DIN 46228 ground lead in housing: cross section max. 2.5 mm2 external equipotential bonding: cross section 4 mm2 | |
Material | wetted parts: - process connection and extension pipe: 1.4435/316L with ECTFE coating - vibration fork: 1.4435/316L with ECTFE coating housings: - polyester housing: PBT-FR with PBT-FR cover or with PA12 cover with sight glass, cover seal: EPDM - stainless steel housing: 1.4301/304, cover seal: silicone - aluminum housing: EN-AC-AlSi10Mg, plastic-coated, cover seal: EPDM cable gland: polyamide or brass, nickel-plated temperature spacer: 1.4435/316L flameproof bushing: 1.4435/316L | |
Surface quality | Ra < 3.2 µm | |
Mass | 800 g , basic weight: compact version (length type II), electronic insert, plastic housing, without flange, additional weight is dependent on extension tube, housing and process connection process connections: - A3H 1000 g, A5H 1500 g, A6H 2400 g, A6I 3200 g, A8H 4900 g - H35 1400 g, H65 2400 g, H71 1600 g, H75 3200 g, H95 5900 g, HA3 5600 g - J1H 1700 g extension tube, temperature spacer, flameproof bushing: - BK* 900 g/m - CK* 2300 g/100 in - DKA 100 g, DKB 700 g, DKC 800 g | |
Dimensions | housing: diameter max. 85 mm, height max. 173 mm temperature separator, flameproof bushing: additional length L 140 mm process connection: length L min. 115 mm extension: any length L from 148 ... 3000 mm, larger sizes on request extension: length type II, for vertical installation from above same switching point as Vibracon LVL2 vibration fork: width 20.6 mm, fork width 6.5 mm, length 25 mm | |
Process connection | flanges to EN 1092-1 from DN25, to ANSI B 16.5 from 1 inch, to JIS B 2238 (RF) from DN50 For further information see type code. | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | see instruction manuals (SI) | |
International approvals | ||
FM approval | see control drawings (ZD) | |
CSA approval | see control drawings (ZD) | |
IECEx approval | see instruction manuals (SI) | |
Certificates and approvals | ||
SIL classification | up to SIL2 acc. to IEC 61508 | |
Overspill protection | see approval (ZE) | |
Accessories | ||
Designation | see technical information (TI) |
General specifications | ||
---|---|---|
Function principle | limit detection Maximum or minimum detection in tanks or pipelines containing all types of liquids including use in explosion hazardous areas. Particularly suited to very aggressive liquids thanks to high degree of corrosion protection. | |
Measuring method | The forks of the sensors vibrate at their intrinsic frequency. This frequency is reduced when covered with liquid. The change in frequency then activates the limit switch. | |
Construction type | device with extension tube | |
Supply | ||
Rated voltage | electronic insert FEL50A (PA): 9 ... 32 V DC electronic insert FEL51 (AC): 253 V AC, 50/60 Hz electronic insert FEL52 (E5): 10 ... 55 V DC electronic insert FEL54 (WA): 19 ... 253 V AC, 50/60 Hz or 19 ... 55 V DC electronic insert FEL55 (SI): 11 ... 36 V DC, PLC electronic insert FEL56 (N1), FEL58 (N2): isolating amplifier acc. to EN 60947-5-6 (NAMUR) | |
Current consumption | electronic insert FEL52 (E5): max. 15 mA | |
Electrical specifications | ||
Surge protection | electronic insert FEL51 (AC), electronic insert FEL52 (E5), electronic insert FEL54 (WA), electronic insert FEL55 (SI): overvoltage category III | |
Input | ||
Switching point | see section switch point | |
Measured variable | limit level (limit value) | |
Measurement range | depends on mounting point and pipe extension up to 3000 mm , larger sizes on request | |
Output | ||
Switching delay | when fork is covered: approx. 0.5 s, when fork is exposed: approx. 1.0 s (other switching times on request) additionally configurable for PROFIBUS PA (electronic insert FEL50A (PA)): 0.5 ... 60 s | |
Switch behaviour | switch-over for minimum/maximum residual current safety on electronic insert MAX = maximum safety: The output switches to the power fail response when the fork is covered. for use with overspill protection for example MIN = minimum safety: The output switches to the power fail response when the fork is exposed. for use with dry running protection for example When switching on the power supply the output assumes the alarm signal. After max. 2 s it assumes the correct switching mode. | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Vibration resistance | EN 60068-2-6 | |
Climate class | DIN EN 60068-2-38/IEC 68-2-38 | |
Measurement accuracy | ||
Reference operating conditions | ambient temperature: 23 °C (73.4 °F), medium temperature: 23 °C (73.4 °F), product density: 1 g/cm3 (water), viscosity: 1 mm2/s, medium pressure pe: 0 bar, sensor mounting: vertical from above, density switch: to > 0.7 g/cm3 | |
Maximum measured error | max. ± 1 mm, specified by mounting position | |
Non-repeatability | 0.1 mm | |
Hysteresis | approx. 2 mm | |
Influence of medium density | max. +4.8 ... -3.5 mm (0.5 ... 1.5 g/cm3) | |
Influence of medium temperature | max. +1.4 ... -2.8 mm (-40 ... 150 °C (-40 ... 302 °F)) | |
Influence of medium pressure | max. 0 ... -2.5 mm (-1 ... 64 bar) | |
Operating conditions | ||
Installation conditions | ||
Installation position | with short pipe (up to 500 mm (19.7 inch)) any position, with long pipe vertical | |
Process conditions | ||
Medium temperature | -50 ... 150 °C (-58 ... 302 °F) , exceptions see process connections | |
Medium pressure | pe = -1 ... 64 bar (-14.5 ... 928.3 psi) over the entire temperature range , exceptions see process connections | |
Test pressure | max. 100 bar (1.5 times the medium pressure pe), no function during test pressure, burst pressure of diaphragm 200 bar | |
Thermal shock resistance | max. 120 °C/s (max. 120 K/s) | |
State of aggregation | liquid | |
Density | min. 0.5 g/cm3 (compact housing 0.7 g/cm3), other density settings on request | |
Viscosity | max. 10000 mm2/s (max. 10000 cSt) | |
Solid contents | < &empty5 mm | |
Ambient conditions | ||
Ambient temperature | -50 ... 70 °C (-58 ... 158 °F) , function with reduced data values see section ambient temperature | |
Storage temperature | -50 ... 80 °C (-58 ... 176 °F) | |
Vibration resistance | 10 ... 50 Hz, 0.15 mm, 100 cycles | |
Mechanical specifications | ||
Degree of protection | polyester, steel, and aluminum housing: IP66/IP67 compact housing: - IP65 with valve connector PG11 or 1/2NPT - IP66/IP68 with M12 x 1 connector without LEDs (1.4435/316L) - IP69K with M12 x 1 connector with LEDs (1.4435/316L) | |
Connection | electronic inserts: cross section max. 2.5 mm2, lace in end splice in acc. with DIN 46228 ground lead in housing: cross section max. 2.5 mm2 external equipotential bonding: cross section 4 mm2 | |
Material | wetted parts: - process connection and extension tube: 1.4435/316L - vibration fork: 1.4435/316L - flat seal for process connection G2* or G3*: elastomer fibre, asbestos-free housings: - polyester housing: PBT-FR with PBT-FR cover or with PA12 cover with sight glass, cover seal: EPDM - stainless steel housing: 1.4435/316L, cover seal: silicone - aluminum housing: EN-AC-AlSi10Mg, plastic-coated, cover seal: EPDM - compact housing with valve connector or M12 connector: 1.4435/316L cable gland: polyamide or brass, nickel-plated temperature spacer: 1.4435/316L flameproof bushing: 1.4435/316L | |
Surface quality | Ra < 1.5 µm/120 grit: length, spacer, bushings *C Ra < 0.3 µm/320 grit: length, spacer, bushings *D | |
Mass | 700 g , basic weight: compact sensor, electronic insert, stainless steel housing, process connection G2*, additional weight is dependent on extension tube, housing and process connection process connections: - A31 1000 g, A41 1200 g, A51 1500 g, A6* 2400 g, A72 4800 g, A81 4900 g, A82 6800 g, A91 7000 g, A92 11.5 kg - D75 3200 g, D95 5900 g, DA3 5600 g, D7A 300 g, D7D 300 g - F45 1400 g, F51 1200 g, F55 2000 g, F61 1400 g, F65 2400 g, F71 1600 g, F75 3200 g, F81 2400 g, F85 4300 g, F93 4800 g, F95 5900 g, FA3 5600 g, FA5 7500 g - G3E 200 g - J13 no information, J16 no information, J17 1700 g, J19 no information, J1A no information, J1C 1700 g - R*R no information - S13 300 g, S61 200 g, SV1 no information - T51 no information, T61 100 g extension tube, tempeprature spacers, flameproof bushings: - B* 900 g/m, C* 2300 g/100 inch - D* 100 g - J* 900 g/m and 600 g, K* 2300 g/100 inch and 600 g - L* 700 g - R* 900 g/m and 700 g, S* 2300 g/100 inch and 700 g - T* 800 g | |
Dimensions | housing: diameter max. 85 mm, height max. 173 mm temperature separator, flameproof bushing: additional length L 140 mm process connection: length L 55.5 ... 80 mm extension: any length L from 148 ... 3000 mm, larger sizes on request extension: length type II, for vertical installation from above same switching point as Vibracon LVL1, LVL2 vibration fork: width 17.5 mm, fork width 10 mm, length 25 mm | |
Process connection | - cylindrical thread G3/4A, G1A to DIN ISO 228/1 with flat seal to DIN 7603 - conical thread R3/4, R1 to DIN 2999, part 1 - flush-mounted with welding sleeve to factory standard (G3/4A, G1A) - flush-mounted with welding neck to factory standard (1 inch), sensor can be positioned - Triclamp 1-1/2 inch, 2 inch to ISO 2852 - threaded pipe joint DN32, DN40, DN50 to DIN 1185 - aseptic connection DN50 to DIN 11864-1 form A for pipe DIN 11850 - SMS connection 2 inch (DN51) - DRD flange, 65 mm - Varivent® DN50 (50/40) to factory standard Tuchenhagen - flanges to EN 1092-1 from DN25, to ANSI B 16.5 from 1 inch, to JIS B 2238 (RF) from DN25 For further information see type code. | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | see instruction manuals (SI) | |
International approvals | ||
FM approval | see control drawings (ZD) | |
CSA approval | see control drawings (ZD) | |
IECEx approval | see instruction manuals (SI) | |
Certificates and approvals | ||
SIL classification | up to SIL2 acc. to IEC 61508 | |
Overspill protection | see approval (ZE) | |
Accessories | ||
Designation | see technical information (TI) |
Application | ||
---|---|---|
Function principle | Limit detection Maximum or minimum detection in silos with all types of solid granulates, even in dust explosion hazardous areas. | |
Function and system design | ||
Measuring principle | A metal plate at the end of the probe, within the insulation, and the surroundings (e. g. the silo walls) combine to form the two electrodes of a capacitor. If the probe is covered or free of material, then the capacitance changes and the LCL switches. | |
Input characteristics | ||
Measured variable | limit level (limit value) | |
Measurement range | LCL1: dielectric constant &ge 1.6 LCL2: dielectric constant &ge 1.5 | |
Output characteristics | ||
Output signal | connection E5: switching PNP, Imax = 200 mA - overload and short circuit protection - residual voltage at transistor at Imax < 2.9 V connection WA: contact change-over, potential-free - Umax = 253 V - Imax = 4 A (AC) - Pmax = 1000 VA, cos &phi = 1, Pmax = 500 VA, cos &phi > 0.7 | |
Auxiliary energy | ||
Electrical connection | see section electrical connection | |
Supply voltage | electrical connection E5: 10.8 ... 45 V DC, short-term pulse on 55 V DC electrical connection WA: 20 ... 235 V AC, 50/60 Hz or 20 ... 55 V DC | |
Current consumption | electrical connection E5: max. 30 mA, reverse-polarity-proof electrical connection WA: max. 130 mA | |
Measurement accuracy | ||
Reference operating conditions | vessel type: plastic vessel, ambient temperature: 73 °F (23 °C, 296 K), medium temperature: 73 °F (23 °C, 296 K) medium pressure pe: 0 bar, medium: dielectric constant = 2.6, conductivity: < 1 µS sensitivity setting: C | |
Hysteresis | LCL1: horizontal 4 mm (0.16 inch), vertical 7 mm (0.28 inch) LCL2: vertical 5 mm (0.2 inch) | |
Long-term drift | LCL1: horizontal 3 mm (0.12 inch), vertical 6 mm (0.24 inch) LCL2: vertical 6 mm (0.24 inch) | |
Influence of medium temperature | depending on the filling material | |
Operating conditions | ||
Installation conditions | ||
Installation position | LCL1: optional LCL2: vertically down Note the angle of the material mounds and the outlet funnel when determining the mounting point or probe length. The limit switch switches when the probe tip is covered by a few centimetres of material or when it is free material flow should not be directed at the probe. | |
Mounting location | The capacitive limit switch can be installed in silos made of different materials (e. g. metal, plastic, concrete). | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) (-40 ... 140 °F (-40 ... 60 °C, 233 ... 333 K), dust-Ex version) see section temperature ranges | |
Ambient temperature limits | -40 ... 80 °C (-40 ... 176 °F) (-40 ... +140 °F (-40 ... +60 °C, 233 ... 333 K), Dust-Ex version) see section temperature ranges , grey background | |
Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Shock resistance | probe: 7J | |
Overvoltage protected | overvoltage category III | |
Process conditions | ||
Process temperature | LCL1: -40 ... 120 °C (233 ... 393 K) (-40 ... 80 °C (233 ... 353 K), dust-Ex version) LCL2: -20 ... 70 °C (253 ... 343 K) see section temperature ranges | |
Process temperature limits | LCL1: -40 ... 130 °C (233 ... 403 K) (-40 ... 80 °C (233 ... 353 K), dust-Ex version) LCL2: -40 ... 80 °C (233 ... 353 K) see section temperature ranges , grey background | |
Medium pressure limits | LCL1: -1 ... 25 bar LCL2: -1 ... 6 bar | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Mechanical construction | ||
Dimensions | housing: LCL1 Ø94 x 140 mm (3.7 x 5.5 inch), LCL2 Ø94 x 145 mm (3.7 x 5.7 inch) process connections: see section dimensions probe: LCL1 length 140 mm (5.5 inch), LCL2 length 500 ... 6000 mm (1.7 ... 20 ft) | |
Mass | LCL1: 560 g LCL2: 1230 g (basic weight for 500 mm probe length) | |
Material | housing: PBT-FR with cover in PBT-FR or with transparent cover in PA12, seal of cover: EPDM cable gland: polyamide or brass, nickel-plated wetted parts: - rod probe: PPS Polyphenylenesulphide (glass fiber content 40 %) - rope probe: armoured steel with HD-PE coating - other probe components: PPS Polyphenylenesulphide (glass fiber content 40 %) | |
Certificates and approvals | ||
Explosion-hazardous area | LCL1: DMT 01 ATEX E 122, LCL2: KEMA 01 ATEX 1149 , for additional certificates see www.pepperl-fuchs.com | |
Type of protection | II 1/3D IP66 T97°C (DMT 01 ATEX E122) II 1/3D [EEx ia] IIB T97°C (KEMA 01 ATEX 1149) | |
Overspill protection | LCL1: Z-65.13-313 (overspill protection in acc. with WHG) |
General specifications | ||
---|---|---|
Measuring method | A metal plate at the end of the probe, within the insulation, and the surroundings (e. g. the silo walls) combine to form the two electrodes of a capacitor. If the probe is covered or free of material, then the capacitance changes and the LCL switches. | |
Equipment architecture | The measuring system consists of: - the device - a supply point - the connected control systems, switching units, signalling systems (e. g. lamps, horns, PCS, PLC, etc.) | |
Construction type | device with rod probe | |
Operating mode | MAX = maximum safety: The device switches if the probe is covered or if the supply voltage is disconnected in a safety-oriented manner (signal on alarm). example application: overspill protection MIN = minimum safety: The device switches if the probe is uncovered or if the supply voltage is disconnected in a safetyoriented manner (signal on alarm). example application: dry-running protection | |
Supply | ||
Rated voltage | electrical connection E5: 10.8 ... 45 V DC, short-term pulse on 55 V DC electrical connection WA: 20 ... 235 V AC, 50/60 Hz or 20 ... 55 V DC | |
Current consumption | electrical connection E5: max. 30 mA, reverse-polarity-proof electrical connection WA: max. 130 mA | |
Electrical specifications | ||
Surge protection | overvoltage category III | |
Input | ||
Measured variable | limit level (limit value) | |
Measurement range | dielectric constant &ge 1.6 | |
Output | ||
Output signal | connection E5: switching PNP, Imax = 200 mA - overload and short circuit protection - residual voltage at transistor at Imax < 2.9 V connection WA: contact change-over, potential-free - Umax = 253 V - Imax = 4 A (AC) - Pmax = 1000 VA, cos &phi = 1, Pmax = 500 VA, cos &phi > 0.7 | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529:2001 | |
Vibration resistance | EN 60068-2-64 | |
Climate class | EN 60068, part 2-38 (test Z/AD) | |
Measurement accuracy | ||
Reference operating conditions | vessel type: plastic vessel, ambient temperature: 73 °F (23 °C, 296 K), medium temperature: 73 °F (23 °C, 296 K) medium pressure pe: 0 bar, medium: dielectric constant = 2.6, conductivity: < 1 µS sensitivity setting: C | |
Hysteresis | horizontal 4 mm (0.16 inch), vertical 7 mm (0.28 inch) | |
Long-term drift | horizontal 3 mm (0.12 inch), vertical 6 mm (0.24 inch) | |
Influence of medium temperature | depending on the filling material | |
Switching time | approx. 0.5 s when covering and uncovering the sensor | |
Operating conditions | ||
Installation conditions | ||
Installation position | any position | |
Mounting location | The capacitive limit switch can be installed in silos made of different materials (e. g. metal, plastic, concrete). | |
Process conditions | ||
Process temperature | -40 ... 130 °C (-40 ... 266 °F) -40 ... 80 °C (-40 ... 176 °F) (Dust-Ex version) | |
Medium pressure limits | -1 ... 25 bar | |
State of aggregation | fluids and solids | |
Solid contents | &le &empty 30 mm | |
Bulk density | &le 200 g/l | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) -40 ... 60 °C (-40 ... 140 °F) (Dust-Ex version) | |
Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Shock resistance | device with F34 housing: 7 J | |
Vibration resistance | a(RMS) = 50 m/s2, ASD = 1.25 (m/s2)2/Hz, f = 5 to 2000 Hz, t = 3 x 2 h | |
Mechanical specifications | ||
Degree of protection | IP66, NEMA 4 | |
Connection | gland M20 thread G1/2, NPT1/2 | |
Material | F14 housing: polyester PBT-FR F34 housing F34: aluminum Probe: PPS GF40 | |
Dimensions | max. &empty94 mm (3.7 inch), length 391 mm (15.4 inch) | |
Process connection | thread R1 acc. to EN 10226, BSPT, adapter for R1-1/2 and G1-1/2 see accessories thread NPT1 to ANSI B 1.20.1, adapter for NPT1-1/4 see accessories | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | see instruction manuals (SI) | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-31:2009 | |
Accessories | ||
Optional accessories | LCL-Z10 cover with sight glass for F14 housing LCL-Z11 adapter for R1-1/2, EN 10226 LCL-Z12 adapter for G1-1/2, DIN ISO 228 LCL-Z13 adapter for NPT1-1/4, steel LCL-Z15 adapter for NPT1-1/4, 1.4571 |
General specifications | ||
---|---|---|
Measuring method | A metal plate at the end of the probe, within the insulation, and the surroundings (e. g. the silo walls) combine to form the two electrodes of a capacitor. If the probe is covered or free of material, then the capacitance changes and the LCL switches. | |
Equipment architecture | The measuring system consists of: - the device - a supply point - the connected control systems, switching units, signalling systems (e. g. lamps, horns, PCS, PLC, etc.) | |
Construction type | device rope probe | |
Operating mode | MAX = maximum safety: The device switches if the probe is covered or if the supply voltage is disconnected in a safety-oriented manner (signal on alarm). example application: overspill protection MIN = minimum safety: The device switches if the probe is uncovered or if the supply voltage is disconnected in a safetyoriented manner (signal on alarm). example application: dry-running protection | |
Supply | ||
Rated voltage | electrical connection E5: 10.8 ... 45 V DC, short-term pulse on 55 V DC electrical connection WA: 20 ... 235 V AC, 50/60 Hz or 20 ... 55 V DC | |
Current consumption | electrical connection E5: max. 30 mA, reverse-polarity-proof electrical connection WA: max. 130 mA | |
Input | ||
Measured variable | limit level (limit value) | |
Measurement range | dielectric constant &ge 1.6 | |
Output | ||
Output signal | connection E5: switching PNP, Imax = 200 mA - overload and short circuit protection - residual voltage at transistor at Imax < 2.9 V connection WA: contact change-over, potential-free - Umax = 253 V - Imax = 4 A (AC) - Pmax = 1000 VA, cos &phi = 1, Pmax = 500 VA, cos &phi > 0.7 | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529:2001 | |
Vibration resistance | EN 60068-2-64 | |
Climate class | EN 60068, part 2-38 (test Z/AD) | |
Measurement accuracy | ||
Reference operating conditions | vessel type: plastic vessel, ambient temperature: 73 °F (23 °C, 296 K), medium temperature: 73 °F (23 °C, 296 K) medium pressure pe: 0 bar, medium: dielectric constant = 2.6, conductivity: < 1 µS sensitivity setting: C | |
Hysteresis | vertical 5 mm (0.2 inch) | |
Long-term drift | vertical 6 mm (0.24 inch) | |
Influence of medium temperature | depending on the filling material | |
Switching time | approx. 0.8 s when covering and uncovering the sensor | |
Operating conditions | ||
Installation conditions | ||
Installation position | vertically down | |
Mounting location | The capacitive limit switch can be installed in silos made of different materials (e. g. metal, plastic, concrete). | |
Process conditions | ||
Process temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Medium pressure limits | -1 ... 6 bar | |
State of aggregation | solids | |
Solid contents | &le &empty 30 mm | |
Bulk density | &le 200 g/l | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) -40 ... 60 °C (-40 ... 140 °F) (Dust-Ex version) | |
Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Shock resistance | device with F34 housing: 7 J | |
Vibration resistance | a(RMS) = 50 m/s2, ASD = 1.25 (m/s2)2/Hz, f = 5 to 2000 Hz, t = 3 x 2 h | |
Mechanical specifications | ||
Degree of protection | IP66, NEMA 4 | |
Connection | gland M20 thread G1/2, NPT1/2 | |
Material | F14 housing: polyester PBT-FR F34 housing F34: aluminum Probe: PPS GF40 probe rope: PE-HD probe rope seal: VMQ | |
Dimensions | max. &empty94 mm (3.7 inch), length 140 mm (5.5 inch) + L L = 500 ... 6000 mm (19.7 ... 236 inch) | |
Process connection | thread R1-1/2 acc. to EN 10226, BSPT thread NPT1-1/2 to ANSI B 1.20.1 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | see instruction manuals (SI) | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-31:2009 | |
Accessories | ||
Optional accessories | LCL-Z10 cover with sight glass for F14 housing LCL-Z14 rope shortening set |
General specifications | ||
---|---|---|
Type | sensor for conductive limit value detection | |
Equipment architecture | A measuring system consists of a rod electrode HR-6**1** with electrode relay KFA6-ER 1.6, KFD2-ER 1.6, KFD2-ER-Ex1.W.LB or KFA6-ER-Ex1.W.LB. | |
Input | ||
Measured variable | measuring voltage directly from the electrode relay | |
Output | ||
Output signal | electrode relay creates switch signal corresponding to the selected responsiveness. | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Operating conditions | ||
Process conditions | ||
Process temperature | process connection 6: <= 150 °C (423 K) process connection 7: <= 90 °C (363 K) process connection 8: <= 150 °C (423 K) | |
Process pressure (static pressure) | process connection 6: &le 30 bar process connection 7: &le 16 bar process connection 8: &le 6 bar | |
Mechanical specifications | ||
Degree of protection | IP65 with terminal box IP52 with plug connector | |
Connection | terminals in plug connector or in terminal box plug connector: terminal, max. 1 mm2 terminal box: terminal, max. 2.5 mm2 | |
Material | housing: stainless steel 1.4571/316Ti, PP or PTFE process connection: stainless steel 1.4571/316Ti, PP or PTFE electrode rod: stainless steel 1.4571/316Ti, Hastelloy C, titanium or tantalum | |
Dimensions | housing: max. Ø43 mm (1.7 inch), height max. 55 mm (2.2 inch) rod: length L max. 3000 mm (10 foot) | |
Process connection | thread G1/2 to ISO 228 |
General specifications | ||
---|---|---|
Type | sensor for conductive limit value detection | |
Input | ||
Measured variable | Measuring voltage from the switch amplifier via converter | |
Output | ||
Output signal | electrode relay creates switch signal corresponding to the selected responsiveness. | |
Operating conditions | ||
Process conditions | ||
Process temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Process pressure (static pressure) | process connection 6: &le 30 bar process connection 7: &le 16 bar process connection 8: &le 6 bar | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) use thermal protection tube for medium temperatures between +60 ... +150 ° C | |
Mechanical specifications | ||
Degree of protection | IP65 with terminal box | |
Connection | electrodes - converter: connection to the converter via connector plug in the terminal box converter - switch amplifier: terminals in the terminal box below the converter | |
Material | housing: PBT process connection: stainless steel 1.4571/316Ti, PP or PTFE electrode rod: stainless steel 1.4571/316Ti, Hastelloy C, titanium or tantalum | |
Dimensions | housing: max. Ø65 mm (2.6 inch), height max. 75 mm (3 inch) rods: length L max. 3000 mm (10 foot) | |
Process connection | thread G1-1/4A to DIN/ISO 228/1 | |
Certificates and approvals | ||
Overspill protection | Z-65.13-6 (overspill protection in acc. with WHG) | |
Accessories | ||
Designation | - spacer, PTFE for Ø4 mm (0.16 inch) rods - spacer with clamp screw, PTFE, for Ø4 mm (0.16 inch) rods - spacer with clamp screw, PTFE, for Ø6 mm (0.24 inch) rods - counter nut G1-1/4A made of PVC - counter nut G1-1/4A made of stainless steel - LZ-1201, mounting angle of stainless steel 1.4571/316Ti with drilling for G1/2A - LZ-1203, mounting angle of stainless steel 1.4571/316Ti with drilling for G1-1/4A - electronical converter HR-011420 |
General specifications | ||
---|---|---|
Type | sensor for conductive limit value detection | |
Input | ||
Measured variable | Measuring voltage from the switch amplifier via converter | |
Output | ||
Output signal | electrode relay creates switch signal corresponding to the selected responsiveness. | |
Operating conditions | ||
Process conditions | ||
Process temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Process pressure (static pressure) | &le 30 bar | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP65 with terminal box | |
Connection | electrodes - converter: connection to the converter via connector plug in the terminal box converter - switch amplifier: terminals in the terminal box below the converter | |
Material | housing: PBT process connection: stainless steel 1.4571/316Ti electrode rod: stainless steel 1.4571/316Ti, Hastelloy C or tantalum | |
Dimensions | housing: max. Ø65 mm (2.6 inch), height max. 75 mm (3 inch) rods: length L max. 3000 mm (10 foot) | |
Process connection | thread G1-1/4A to DIN/ISO 228/1 | |
Data for application in connection with hazardous areas | ||
Certificate of Compliance | PTB Nr. Ex-88.B:2003 | |
Group, category, type of protection | EEx ia IIC T6 | |
Certificates and approvals | ||
Overspill protection | 01/PTB Nr.: Ex-79/2011X (overspill protection acc. to VbF) | |
Accessories | ||
Designation | - spacer, PTFE for Ø4 mm (0.16 inch) rods - spacer with clamp screw, PTFE, for Ø4 mm (0.16 inch) rods - spacer with clamp screw, PTFE, for Ø6 mm (0.24 inch) rods - counter nut G1-1/4A made of PVC - counter nut G1-1/4A made of stainless steel - LZ-1201, mounting angle of stainless steel 1.4571/316Ti with drilling for G1/2A - LZ-1203, mounting angle of stainless steel 1.4571/316Ti with drilling for G1-1/4A - electronical converter HR-011420 |
Directive conformity | ||
---|---|---|
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2001 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529:2001 | |
Vibration resistance | EN 60068-2-64 | |
Climate class | EN 60068, part 2-38 (test Z/AD) | |
Function and system design | ||
Measuring principle | An alternating voltage exists between the probes in an empty tank. As soon as the conductive liquid in the tank creates a connection between the ground probe and, for example, the maximum probe, a measurable current flows and the device switches. With level limit detection, the device switches back as soon as the liquid clears the maximum probe. With two-point control, the device does not switch back until the max and min probe is cleared. Using alternating voltage prevents corrosion of the probes and electrolytic destruction of the product. The material used for the tank walls is not important for measurement because the system is designed as a closed potential-free circuit between the probes and the electronics. There is absolutely no danger if the probes are touched during operation. | |
Equipment architecture | probe with integrated electronic insert (compact instrument version) probe without integrated electronic insert (separate instrument version) for one, two or multiple point detection respectively, see section measuring system | |
Input characteristics | ||
Measured variable | resistance change between two conductors caused by the presence or absence of a conductive product. | |
Measurement range | The measuring range is dependent on the mounting location of the probes. Rod probes can have a max. length of 4000 mm (13 ft) and rope probes up to 15000 mm (49 ft). | |
Output characteristics | ||
Output signal | see section electrical connection | |
Measurement range | A total of four measuring ranges (100 &Omega, 1 k&Omega, 10 k&Omega, 100 k&Omega) can be set via two DIL switches (SENS). The setting on delivery is 100 k&Omega. | |
Auxiliary energy | ||
Electrical connection | see section electrical connection | |
Supply voltage | Output E5 (FEW52): supply voltage 10.8 ... 45 V DC load connection: open collector PNP switching voltage: max. 45 V Output WA (FEW54): supply voltage 20 ... 55 V DC or 20 ... 253 V AC, 50/60 Hz peak inrush current: max. 2 A, max. 400 µs output: two potential-free change-over contacts output N1 (FEW58): refer to datasheet of the connected switch amplifier acc. to IEC 60947-5-6 (NAMUR) | |
Power consumption | Output E5 (FEW52): P < 1.1 W output WA (FEW54): P < 2.0 W | |
Current consumption | Output E5 (FEW52): I < 25 mA (without load) output WA (FEW54): 60 mA | |
Measurement accuracy | ||
Reference operating conditions | ambient temperature: 23 °C (296 K), medium temperature: 23 °C (296 K), medium viscosity: medium must release the probe again (drain off), medium pressure pe: 0 bar, probe installation: vertically from above | |
Maximum measured error | ± 10 % at 0.1 ... 100 k&Omega ± 5 % at 1 ... 10 k&Omega | |
Non-repeatability | ± 5 % at 0.1 ... 100 k&Omega ± 1 % at 1 ... 10 k&Omega | |
Hysteresis | -10 % for the max probe, in reference to the switch point, &Deltas function deactivated | |
Influence of ambient temperature | < 0.05 %/K | |
Switching time | < 3 s | |
Operating conditions | ||
Installation conditions | ||
Mounting location | The rod and rope probes are mounted predominantly in tanks made of plastic or metal. | |
Mounting examples | see section example applications | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) -40 ... 60 °C (233 ... 333 K) for output N1 (FEW58) | |
Storage temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Climate class | tropicalized | |
Shock resistance | practical test | |
Vibration resistance | 20 ... 2000 Hz, 1 (m/s2)2/Hz | |
Process conditions | ||
Medium temperature | -40 ... 100 °C (-40 ... 212 °F) | |
Medium pressure | -1 ... 10 bar (-14.5 ... 145 psi) | |
Conductivity | &ge 10 µS | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | TÜV 03 ATEX 2295 | |
Group, category, type of protection | II 2G Ex ia/ib IIC T4 | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 , EN 60079-11:2007 | |
Mechanical construction | ||
Dimensions | LKL-P1: - housing: max. Ø85 mm (3.3 inch), height max. 145 mm (5.7 inch) - rod: length 100 ... 4000 mm (4 in ... 13 ft) LKL-P2: - housing: max. Ø85 mm (3.3 inch), height max. 145 mm (5.7 inch) - rope: length 250 ... 15000 mm (10 in ... 49 ft) | |
Mass | separate instrument version: - rod, 1 m (3 ft) long, LKL-P1 with 2, 3 or 5 rods: 415 g, 530 g, 760 g - rope, 1 m (3 ft) long, LKL-P2 with 2, 3 or 5 ropes: 390 g, 470 g, 640 g compact instrument version: - rod, 1 m (3 ft) long, LKL-P1 with 2 or 3 rods (600 g/720 g) - rope, 1 m (3 ft) long, LKL-P2 with 2 or 3 ropes (710 g/800 g) | |
Material | probes: - rods: rod 1.4404/316L, insulation: PP - ropes: rope 1.4571/316Ti, insulation FEP, weight 1.4435/316L housing: - output NA (separate instrument version): housing PPS, cover PBT - output E5/WA/N1 (compact instrument version): housing PBT, cover PBT, adapter PBT process connections: PPS | |
Certificates and approvals | ||
Overspill protection | see approval (ZE) |
General specifications | ||
---|---|---|
Equipment architecture | switching element: changeover switching on point: 15 mbar ± 3 mbar, switching off point: 9 mbar ± 3 mbar max. hydrostatic pressure: 500 mbar | |
Supply | ||
Rated voltage | 253 V AC , 50/60 Hz | |
Current consumption | max. 1 A | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Operating conditions | ||
Process conditions | ||
Process temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Ambient conditions | ||
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | IP54 | |
Connection | flat plug 6.3 x 0.8 mm (0.25 x 0.03 inch), DIN 46244 | |
Material | housing: PA pipe: stainless steel 1.4571/316Ti or PVC | |
Dimensions | housing: 100 x 75 x 80 mm (4 x 3 x 3.1 inch) pipe: length L 180 ... 5000 mm (0.6 ... 16.5 ft) | |
Process connection | thread G1/2 to ISO 228 |
General specifications | ||
---|---|---|
Type | sensor for conductive limit value detection | |
Equipment architecture | A measuring system consists of a rod electrode HR-6*5*** with electrode relay KFA6-ER 1.6, KFD2-ER 1.6, KFD2-ER-Ex1.W.LB or KFA6-ER-Ex1.W.LB. | |
Input | ||
Measured variable | measuring voltage directly from the electrode relay | |
Output | ||
Output signal | electrode relay creates switch signal corresponding to the selected responsiveness. | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Operating conditions | ||
Process conditions | ||
Process temperature | process connection 6: <= 150 °C (423 K) process connection 7: <= 90 °C (363 K) process connection 8: <= 150 °C (423 K) | |
Process pressure (static pressure) | process connection 6: <= 40 bar process connection 7: <= 10 bar process connection 8: <= 6 bar | |
Mechanical specifications | ||
Degree of protection | IP65 with terminal box | |
Connection | terminals in the terminal box: connection, max. 2.5 mm2 | |
Material | housing: stainless steel 1.4571/316Ti, PP or PTFE process connection: stainless steel 1.4571/316Ti, PP or PTFE electrode rod: stainless steel 1.4571/316Ti, Hastelloy C, titanium or tantalum | |
Dimensions | housing: max. Ø65 mm (2.6 inch), height max. 75 mm (3 inch) rods: length L1 ... L5 max. 3000 mm (10 foot) | |
Process connection | thread G1-1/4A to DIN/ISO 228/1 | |
Accessories | ||
Designation | - spacer, PTFE for Ø4 mm (0.16 inch) rods - spacer with clamp screw, PTFE, for Ø4 mm (0.16 inch) rods - spacer with clamp screw, PTFE, for Ø6 mm (0.24 inch) rods - counter nut G1-1/4A made of PVC - counter nut G1-1/4A made of stainless steel - LZ-1201, mounting angle of stainless steel 1.4571/316Ti with drilling for G1/2A - LZ-1203, mounting angle of stainless steel 1.4571/316Ti with drilling for G1-1/4A |
General specifications | ||
---|---|---|
Type | sensor for conductive limit value detection | |
Equipment architecture | A measuring system consists of a suspension electrode HR-690121 with electrode relay KFA6-ER 1.6, KFD2-ER 1.6, KFD2-ER-Ex1.W.LB or KFA6-ER-Ex1.W.LB. | |
Versions | HR-690121/05, suspension electrode, 5 m (5.5 yd) cable, PVC HR-690121/10, suspension electrode, 10 m (11 yd) cable, PVC HR-690121/20, suspension electrode, 20 m (22 yd) cable, PVC | |
Input | ||
Measured variable | measuring voltage directly from the electrode relay | |
Output | ||
Output signal | electrode relay creates switch signal corresponding to the selected responsiveness. | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2006 , EN 61326-2-3:2006 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Operating conditions | ||
Process conditions | ||
Process temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Material | thread, cable insulation and electrode: PVC electrode tip: stainless steel 1.4571/316Ti | |
Dimensions | electrode: Ø20 mm (0.8 inch), length 160 mm (6.3 inch) cable: length max. 20 m (21.9 yard) |
Supply | ||
---|---|---|
Rated voltage | see datasheets of float switches | |
Electrical specifications | ||
Contact loading | see datasheets of float switches | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | see datasheets of float switches | |
Low voltage | ||
Directive 2014/35/EU | see datasheets of float switches | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Application | ||
Description | switching element: LFL1: floating up closing, normally open LFL2: microswitch with switching ball, change-over contact LFL3: mercury (Hg) change-over contact | |
Operating conditions | ||
Installation conditions | ||
Installation instructions | range of application and minimum length between mounting and float: - PVC version: &ge 50 mm (2 inch), preferred for water - PUR version: &ge 100 mm (4 inch), preferred for fuels, heating oils, oily fluids - CSM/CM version: &ge 100 mm (4 inch), preferred for many acids and lyes Float switches are fastened onto the lower end of the guide pipe in the factory. The position of the switch points required for the application must be adjusted by the user by moving the set collars (in some cases, it may be necessary to shorten the float switch wire). | |
Process conditions | ||
Process pressure (static pressure) | &le 1 bar at 20 °C (68 °F) | |
Ambient conditions | ||
Ambient temperature | 5 ... 70 °C (41 ... 158 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Mechanical specifications | ||
Degree of protection | Float Switch : IP68 terminal box: IP66 | |
Mechanical construction | ||
Dimensions | guide tube: &empty16 mm (0.6 inch), Lmax = 3000 mm (10 feet) | |
Material | float: PP (Polypropylene) guide tube: PVC process connection: PVC set collars and clamping screw: PVC |
Supply | ||
---|---|---|
Rated voltage | 8.2 V ± 2 V | |
Current consumption | < 1.0 mA unswitched (de-energized at the bottom), > 2.2 mA switched (floated up at the top) | |
Reverse polarity protection | yes | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 60947-5-2:2007+A1:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Application | ||
Description | Proximity switch with operation ball | |
Function and system design | ||
Equipment architecture | A measuring system consists of a float switch LFL1-**-N and a transformer isolated barrier, e. g. KFD2-SR2-Ex1.W. | |
Operating conditions | ||
Installation conditions | ||
Installation instructions | range of application and minimum length between mounting and float: - PVC version: &ge 50 mm (2 inch), preferred for water - PUR version: &ge 100 mm (4 inch), preferred for fuels, heating oils, oily fluids - CSM/CM version: &ge 100 mm (4 inch), preferred for many acids and lyes mounting: - The float switch is mounted either from sidewards through a cable gland &ge G1A into the vessel or - by means of a counter weight or rods (e. g. float switch combination) from the top. The pivot of the cable should always be horizontal. | |
Process conditions | ||
Process pressure (static pressure) | sleeve design: &le 3 bar at 20 °C (68 °F) ball design: &le 2 bar at 20 °C (68 °F) | |
Density | sleeve design: &ge 0.8 g/cm3 ball design: &ge 0.6 g/cm3 | |
Ambient conditions | ||
Ambient temperature | -20 ... 70 °C (-4 ... 158 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Altitude | &le 2000 m above MSL | |
Mechanical specifications | ||
Degree of protection | IP68 | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | TÜV 99 ATEX 1407 | |
Group, category, type of protection | II 2G Ex ia IIB T5 | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 | |
Mechanical construction | ||
Material | float: PP (Polypropylene) cable: - PVC version: PVC cable, highly flexible (2 x 0.75 mm2) - PUR version: PUR cable, highly flexible (2 x 0.50 mm2) - CSM/CM version: CSM/CM cable (chlorinated polyethylene, (2 x 0.75 mm2)) |
Electrical specifications | ||
---|---|---|
Contact loading | 250 V AC/3 A 150 V DC/0.25 A resistive load 60 V DC/1 A resistive load | |
Rated insulation voltage | 300 V | |
Pulse withstand voltage | 4 kV | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 60947-5-1:2004 + Cor.:2005 + A1:2009 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Application | ||
Description | microswitch with switching ball, change-over contact | |
Function and system design | ||
Equipment architecture | This device may be used with any sequential circuit, as long as the circuit can support the electrical circuit values of the switching elements. | |
Operating conditions | ||
Installation conditions | ||
Installation instructions | range of application and minimum length between mounting and float: - PVC version: &ge 50 mm (2 inch), preferred for water - PUR version: &ge 100 mm (4 inch), preferred for fuels, heating oils, oily fluids - CSM/CM version: &ge 100 mm (4 inch), preferred for many acids and lyes mounting: - The float switch is mounted either from sidewards through a cable gland &ge G1A into the vessel or - by means of a counter weight or rods (e. g. float switch combination) from the top. The pivot of the cable should always be horizontal. | |
Process conditions | ||
Process pressure (static pressure) | sleeve design: &le 3 bar at 20 °C (68 °F) ball design: &le 2 bar at 20 °C (68 °F) | |
Density | sleeve design: &ge 0.8 g/cm3 ball design: &ge 0.6 g/cm3 | |
Ambient conditions | ||
Ambient temperature | PVC version: 5 ... 70 °C (41 ... 158 °F) PUR version: 5 ... 70 °C (41 ... 158 °F) CSM/CM version: -20 ... 70 °C (-4 ... 158 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Altitude | &le 2000 m above MSL | |
Mechanical specifications | ||
Degree of protection | IP68 | |
Mechanical construction | ||
Material | float: PP (Polypropylene) cable: - PVC version: PVC cable, highly flexible (3 x 0.75 mm2) - PUR version: PUR cable, highly flexible (3 x 0.50 mm2) - CSM/CM version: CSM/CM cable (chlorinated polyethylene, (3 x 0.75 mm2)) |
Electrical specifications | ||
---|---|---|
Contact loading | 230 V AC/3 A/200 VA 150 V DC/3 A/100 W resistive load | |
Rated insulation voltage | 300 V | |
Pulse withstand voltage | 4 kV | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 60947-5-1:2004 + Cor.:2005 + A1:2009 | |
Conformity | ||
Degree of protection | IEC 60529:2001 | |
Application | ||
Description | mercury (Hg) change-over contact | |
Function and system design | ||
Equipment architecture | This device may be used with any sequential circuit, as long as the circuit can support the electrical circuit values of the switching elements. | |
Operating conditions | ||
Installation conditions | ||
Installation instructions | range of application and minimum length between mounting and float: - PVC version: &ge 50 mm (2 inch), preferred for water - PUR version: &ge 100 mm (4 inch), preferred for fuels, heating oils, oily fluids - CSM/CM version: &ge 100 mm (4 inch), preferred for many acids and lyes - TPK version: &ge 100 mm (4 inch), preferred for many acids and lyes mounting: - The float switch is mounted either from sidewards through a cable gland &ge G1A into the vessel or - by means of a counter weight or rods (e. g. float switch combination) from the top. The pivot of the cable should always be horizontal. | |
Process conditions | ||
Process pressure (static pressure) | sleeve design: &le 3 bar at 20 °C (68 °F) ball design: &le 2 bar at 20 °C (68 °F) | |
Density | sleeve design: &ge 0.8 g/cm3 ball design: &ge 0.6 g/cm3 | |
Ambient conditions | ||
Ambient temperature | PVC version: 5 ... 70 °C (41 ... 158 °F) PUR version: 5 ... 70 °C (41 ... 158 °F) CSM/CM version: -20 ... 70 °C (-4 ... 158 °F) TPK version: 5 ... 70 °C (41 ... 158 °F) | |
Storage temperature | -25 ... 70 °C (-13 ... 158 °F) | |
Altitude | &le 2000 m above MSL | |
Mechanical specifications | ||
Degree of protection | IP68 | |
Mechanical construction | ||
Material | float: PP (Polypropylene) cable: - PVC version: PVC cable, highly flexible (3 x 0.75 mm2) - PUR version: PUR cable, highly flexible (3 x 0.50 mm2) - CSM/CM version: CSM/CM cable (chlorinated polyethylene, (3 x 0.75 mm2)) - TPK version: TPK cable, (3 x 0.75 mm2) |