Атол 30Ф не включается (заводской брак)
Валерий
14 января 2022
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | terminals 23, 24 | |
Rated voltage | 115 V AC ± 10 % | |
Rated current | 35 mA | |
Power consumption | 4 VA | |
Input | ||
Connection side | field side | |
Connection | Input I: terminals 1+, 3- input II: terminals 13+, 14- | |
Input I | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | 8.2 V / 10 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Pulse duration | min. 75 µs / 1 ms see instruction manuals the maximum input frequency has to be observed. | |
Input frequency | 0 ... 80 Hz , pulse divider 0 ... 1 kHz | |
Line fault detection | breakage I &le 0.15 mA short-circuit I > 6.5 mA | |
Input II | reset | |
Active/Passive | I > 3 mA / I < 1.5 mA | |
Open circuit voltage/short-circuit current | 12 V / 3.5 mA | |
Pulse duration | min. 10 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 19+, 20- | |
Output I | signal , Relay output | |
Contact loading | 253 V AC/ 2 A / cos &phi &ge 0.7 40 V DC/ 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output II | signal , electronic unit, isolated | |
Contact loading | 40 V / 50 mA | |
Energized/De-energized delay | after rising input flank 3 ms after falling input flank 2 ms | |
Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current &le 10 µA) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | TÜV 99 ATEX 1408 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1885 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0305 | |
UL approval | E223772 | |
IECEx approval | IECEx TUN 03.0000 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | terminals 23, 24 | |
Rated voltage | 230 V AC ± 10 % | |
Rated current | 15 mA | |
Power consumption | 4 VA | |
Input | ||
Connection side | field side | |
Connection | Input I: terminals 1+, 3- input II: terminals 13+, 14- | |
Input I | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | 8.2 V / 10 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Pulse duration | min. 75 µs / 1 ms see instruction manuals the maximum input frequency has to be observed. | |
Input frequency | 0 ... 80 Hz , pulse divider 0 ... 1 kHz | |
Line fault detection | breakage I &le 0.15 mA short-circuit I > 6.5 mA | |
Input II | reset | |
Active/Passive | I > 3 mA / I < 1.5 mA | |
Open circuit voltage/short-circuit current | 12 V / 3.5 mA | |
Pulse duration | min. 10 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 19+, 20- | |
Output I | signal , Relay output | |
Contact loading | 253 V AC/ 2 A / cos &phi &ge 0.7 40 V DC/ 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output II | signal , electronic unit, isolated | |
Contact loading | 40 V / 50 mA | |
Energized/De-energized delay | after rising input flank 3 ms after falling input flank 2 ms | |
Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current &le 10 µA) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | TÜV 99 ATEX 1408 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1885 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0305 | |
UL approval | E223772 | |
IECEx approval | IECEx TUN 03.0000 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Input | |
Supply | ||
Connection | Power Rail or terminals 23+, 24- | |
Rated voltage | 20 ... 30 V DC | |
Rated current | approx. 100 mA | |
Power consumption | 1.8 W | |
Input | ||
Connection side | field side | |
Connection | Input I: terminals 1+, 3- input II: terminals 13+, 14- | |
Input I | acc. to EN 60947-5-6 (NAMUR), see system description for electrical data | |
Open circuit voltage/short-circuit current | 8.2 V / 10 mA | |
Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA | |
Pulse duration | min. 75 µs / 1 ms see instruction manuals the maximum input frequency has to be observed. | |
Input frequency | 0 ... 80 Hz , pulse divider 0 ... 1 kHz | |
Line fault detection | breakage I &le 0.15 mA short-circuit I > 6.5 mA | |
Input II | reset | |
Active/Passive | I > 4 mA/I < 1.5 mA | |
Open circuit voltage/short-circuit current | 18 V / 5 mA | |
Pulse duration | min. 10 ms | |
Output | ||
Connection side | control side | |
Connection | output I: terminals 10, 11, 12 output II: terminals 19+, 20- | |
Output I | signal , Relay output | |
Contact loading | 253 V AC/ 2 A / cos &phi &ge 0.7 40 V DC/ 2 A | |
Mechanical life | 5 x 107 switching cycles | |
Energized/De-energized delay | approx. 20 ms / approx. 20 ms | |
Output II | signal , electronic unit, isolated | |
Contact loading | 40 V / 50 mA | |
Energized/De-energized delay | after rising input flank 3 ms after falling input flank 2 ms | |
Signal level | 1-signal: (L+) -2.5 V (50 mA, short-circuit/overload proof) 0-signal: blocked output (off-state current &le 10 µA) | |
Indicators/settings | ||
Display elements | LEDs , display | |
Control elements | Control panel | |
Configuration | via operating buttons | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 300 g | |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | TÜV 99 ATEX 1408 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1885 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | ||
Control drawing | 116-0305 | |
UL approval | E223772 | |
IECEx approval | IECEx TUN 03.0000 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Описание оборудования | ||
---|---|---|
current limit 45 mA |
Описание оборудования | ||
---|---|---|
current limit 45 mA |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | terminals 5+, 6- loop powered Power Rail or terminals 9+, 10- bus powered | |
Rated voltage | 19 ... 30 V DC | |
Input current | 75 mA at 24 V, 220 &Omega load | |
Power dissipation | 1.4 W at 24 V, 220 &Omega load | |
Input | ||
Connection side | control side | |
Connection | terminals 5+, 6- | |
Signal level | loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited at 5 mA) 0-signal: 0 ... 5 V DC | |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Internal resistor | 285 &Omega | |
Current | typ. 45 mA | |
Voltage | typ. 10 V | |
Current limit | 45 mA | |
Open loop voltage | typ. 24.6 V | |
Load | nominal 0.05 ... 18 k&Omega | |
Output II | fault signal | |
Connection | terminals 7, 8 , non-intrinsically safe | |
Contact loading | 30 V DC/ 0.5 A resistive load | |
Mechanical life | 105 switching cycles | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Line fault detection | signal at short-circuit RB < 25 &Omega, lead breakage RB > 50 k&Omega test current < 500 µA | |
Galvanic isolation | ||
Output/Other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 For further information see system description. | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 17 ATEX 0002 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 17.0001X | |
Approved for | Ex nC ec [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | terminals 5+, 6- loop powered Power Rail or terminals 9+, 10- bus powered | |
Rated voltage | 19 ... 30 V DC | |
Input current | 80 mA at 24 V | |
Power dissipation | 1.3 W at 24 V | |
Load | 150 &Omega | |
Input | ||
Connection side | control side | |
Connection | terminals 5+, 6- | |
Signal level | loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited at 5 mA) 0-signal: 0 ... 5 V DC | |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Internal resistor | 80 &Omega | |
Current | typ. 65 mA | |
Voltage | typ. 10 V | |
Current limit | 65 mA | |
Open loop voltage | typ. 16.4 V | |
Load | nominal 0.05 ... 18 k&Omega | |
Output II | fault signal | |
Connection | terminals 7, 8 , non-intrinsically safe | |
Contact loading | 30 V DC/ 0.5 A resistive load | |
Mechanical life | 105 switching cycles | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Line fault detection | signal at short-circuit RB < 25 &Omega, lead breakage RB > 50 k&Omega test current < 500 µA | |
Galvanic isolation | ||
Output/Other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 For further information see system description. | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 17 ATEX 0002 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 17.0001X | |
Approved for | Ex nC ec [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 3 | |
Supply | ||
Connection | terminals 5+, 6- loop powered Power Rail or terminals 9+, 10- bus powered | |
Rated voltage | 19 ... 30 V DC | |
Input current | 75 mA at 24 V , 270 &Omega load | |
Power dissipation | 1.3 W at 24 V , 270 &Omega load | |
Input | ||
Connection side | control side | |
Connection | terminals 5+, 6- | |
Signal level | loop powered 1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC bus powered 1-signal: 15 ... 30 V DC (current limited at 5 mA) 0-signal: 0 ... 5 V DC | |
Rated current | 0-signal: typ. 1.6 mA at 1.5 V typ. 8 mA at 3 V (maximum leakage current DO card) 1-signal: &ge 36 mA (minmum load current DO card) | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Internal resistor | 240 &Omega | |
Current | typ. 45 mA | |
Voltage | typ. 12 V | |
Current limit | 50 mA | |
Open loop voltage | typ. 24.6 V | |
Load | nominal 0.05 ... 18 k&Omega | |
Output II | fault signal | |
Connection | terminals 7, 8 , non-intrinsically safe | |
Contact loading | 30 V DC/ 0.5 A resistive load | |
Mechanical life | 105 switching cycles | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Line fault detection | signal at short-circuit RB < 25 &Omega, lead breakage RB > 50 k&Omega test current < 500 µA | |
Galvanic isolation | ||
Output/Other circuits | basic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2012 , EN 61326-3-2:2008 For further information see system description. | |
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | EXA 17 ATEX 0002 X | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx EXA 17.0001X | |
Approved for | Ex nC ec [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I |
Описание оборудования | ||
---|---|---|
current limit: 100 mA |
Описание оборудования | ||
---|---|---|
current limit 45 mA |
Описание оборудования | ||
---|---|---|
current limit 65 mA |
Описание оборудования | ||
---|---|---|
current limit 80 mA |
Описание оборудования | ||
---|---|---|
current limit 45 mA |
Описание оборудования | ||
---|---|---|
current limit 45 mA |
Описание оборудования | ||
---|---|---|
Lead monitoring |
Описание оборудования | ||
---|---|---|
Lead monitoring |
Описание оборудования | ||
---|---|---|
without lead monitoring |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Power dissipation | max. 1.5 W | |
Power consumption | max. 2 W at 45 mA output current | |
Input | ||
Connection side | control side | |
Connection | terminals 7, 8 | |
Input current | approx. 3 mA | |
Signal level | 1-signal: 16 ... 30 V DC 0-signal: 0 ... 5 V DC | |
Output | ||
Connection side | field side | |
Output I | ||
Connection | terminals 1+, 2- or 3- | |
Internal resistor | 270 &Omega | |
Current | max. 45 mA | |
Voltage | min. 11.2 V | |
Open loop voltage | min. 23.5 V | |
Output signal | These values are valid for the rated operating voltage 19 ... 30 V DC. | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Line fault detection | signal at short-circuit RB < 50 &Omega, lead breakage RB > 10 k&Omega test current < 650 µA | |
Output II | fault signal | |
Connection | terminals 10, 11, 12 , non-intrinsically safe | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Mechanical life | 2 x 107 switching cycles | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | ZELM 99 ATEX 0015 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1820 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0362 | |
IECEx approval | IECEx ZLM 14.0001 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Power dissipation | max. 1.5 W | |
Power consumption | max. 2 W at 45 mA output current | |
Input | ||
Connection side | control side | |
Connection | terminals 7, 8 | |
Input current | 1-signal: 3.5 mA over the entire range 0-signal: 1.5 mA at 5 V DC | |
Signal level | 1-signal: 16 ... 30 V DC 0-signal: 0 ... 5 V DC | |
Output | ||
Connection side | field side | |
Output I | ||
Connection | terminals 1+, 2- or 3- | |
Internal resistor | 270 &Omega | |
Current | max. 45 mA | |
Voltage | min. 11.2 V | |
Open loop voltage | min. 23.5 V | |
Output signal | These values are valid for the rated operating voltage 19 ... 30 V DC. | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Line fault detection | signal at short-circuit RB < 50 &Omega, lead breakage RB > 10 k&Omega test current < 650 µA | |
Output II | fault signal | |
Connection | terminals 10, 11, 12 , non-intrinsically safe | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Mechanical life | 2 x 107 switching cycles | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | ZELM 99 ATEX 0015 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1820 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0362 | |
IECEx approval | IECEx ZLM 14.0001 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Power dissipation | max. 1.5 W | |
Power consumption | max. 2 W at 45 mA output current | |
Input | ||
Connection side | control side | |
Connection | terminals 7, 8 | |
Input current | approx. 3 mA | |
Signal level | 1-signal: 16 ... 30 V DC 0-signal: 0 ... 5 V DC | |
Output | ||
Connection side | field side | |
Output I | ||
Connection | terminals 1+, 2- or 3- | |
Internal resistor | 300 &Omega | |
Current | max. 45 mA | |
Voltage | min. 10 V | |
Open loop voltage | min. 23.5 V | |
Output signal | These values are valid for the rated operating voltage 19 ... 30 V DC. | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Line fault detection | signal at short-circuit RB < 50 &Omega, lead breakage RB > 10 k&Omega test current < 650 µA | |
Output II | fault signal | |
Connection | terminals 10, 11, 12 , non-intrinsically safe | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Mechanical life | 2 x 107 switching cycles | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | ZELM 99 ATEX 0015 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1820 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0362 | |
IECEx approval | IECEx ZLM 14.0001 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 19 ... 30 V DC | |
Power dissipation | max. 1.4 W | |
Power consumption | max. 2.3 W at 70 mA output current | |
Input | ||
Connection side | control side | |
Connection | terminals 7, 8 | |
Input current | approx. 3 mA | |
Signal level | 1-signal: 16 ... 30 V DC 0-signal: 0 ... 5 V DC | |
Output | ||
Connection side | field side | |
Output I | ||
Connection | terminals 1+, 2- or 3- | |
Internal resistor | 92 &Omega | |
Current | max. 70 mA | |
Voltage | min. 12.5 V | |
Open loop voltage | min. 19.2 V | |
Output signal | These values are valid for the rated operating voltage 19 ... 30 V DC. | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Line fault detection | signal at short-circuit RB < 50 &Omega, lead breakage RB > 10 k&Omega test current < 650 µA | |
Output II | fault signal | |
Connection | terminals 10, 11, 12 , non-intrinsically safe | |
Contact loading | 253 V AC/2 A/cos &phi > 0.7 40 V DC/2 A resistive load | |
Mechanical life | 2 x 107 switching cycles | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Conformity | ||
Electromagnetic compatibility | NE 21:2007 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | ZELM 99 ATEX 0015 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1820 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0362 | |
IECEx approval | IECEx ZLM 14.0001 | |
Approved for | [Ex ia Ga] IIB, [Ex ia Da] IIIC, [Ex ia Ma] I |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Power consumption | max. 3.3 W at 45 mA output current | |
Input | ||
Connection side | control side | |
Connection | terminals 7, 8, 9 | |
Input current | approx. 3 mA at 24 V DC | |
Signal level | 1-signal: 16 ... 30 V DC 0-signal: 0 ... 5 V DC | |
Output | ||
Connection side | field side | |
Connection | channel 1: terminals 1+, 2-, 3 channel 2: terminals 4+, 5-, 6- | |
Internal resistor | 272 &Omega | |
Current | &le 45 mA | |
Voltage | &ge 11.7 V | |
Open loop voltage | min. 24 V | |
Output signal | These values are valid for the rated operating voltages from 20 ... 30 V DC. | |
Energized/De-energized delay | &le 20 ms / &le 20 ms | |
Line fault detection | signal at short-circuit RB < 50 &Omega, lead breakage RB > 10 k&Omega , test current < 650 µA | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 50 °C (-4 ... 122 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | ZELM 00 ATEX 0024 | |
Marking | ![]() ![]() ![]() | |
Certificate | TÜV 02 ATEX 1820 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 , EN 50303:2000 | |
International approvals | ||
CSA approval | ||
Control drawing | 116-0304 | |
IECEx approval | IECEx TUN 04.0001 | |
Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
Описание оборудования | ||
---|---|---|
without lead monitoring |
Описание оборудования | ||
---|---|---|
Output 22.3 V |
General specifications | ||
---|---|---|
Signal type | Digital Output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 30 V DC | |
Power dissipation | < 2 W supply voltage 30 V, all outputs loaded with 600 mA | |
Input | ||
Connection side | control side | |
Connection | Terminals 7+, 8+, 9+, 10+, 15- | |
Input current | approx. 2 mA at 24 V DC | |
Signal level | 0-signal: 0 ... 5 V DC 1-signal: 16 ... 30 V | |
Output | ||
Connection side | field side | |
Open loop voltage | 24 V DC | |
Connection | terminals 1+, 2+, 3+, 4+, 5-, 6- | |
Switching frequency | 1 kHz | |
Output rated operating current | 600 mA , sustained short-circuit proof and overload-proof | |
Line fault detection | lead breakage: &le 4 mA | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 7+, 8- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Rated current | &le 50 mA | |
Power dissipation | 1.2 W | |
Input | ||
Connection side | control side | |
Connection | terminals 9+, 10-, 11+ | |
Voltage drop | approx. 4 V at 20 mA | |
Limit | Input current: approx. &le40 mA input voltage: &le 35 V | |
Transmission range | 0 ... 20 mA | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Current | 0 ... 20 mA | |
Load | max. 850 &Omega | |
Voltage | 17 V at 20 mA | |
Transfer characteristics | ||
Accuracy | 0.1 % | |
Rise time | < 10 ms | |
Indicators/settings | ||
Display elements | LED | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Insulation coordination | EN 50178 | |
Galvanic isolation | EN 50178 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 | |
Data for application in connection with hazardous areas | ||
Certificate | TÜV 99 ATEX 1499 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-15:2010 |
Описание оборудования | ||
---|---|---|
2-channel |
Описание оборудования | ||
---|---|---|
1-channel |
Описание оборудования | ||
---|---|---|
2-channel |
General specifications | ||
---|---|---|
Signal type | Analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 30 mA | |
Power dissipation | &le 600 mW | |
Power consumption | &le 700 mW | |
Input | ||
Connection side | control side | |
Connection | terminals 5-, 6+ | |
Input signal | 4 ... 20 mA limited to approx. 30 mA | |
Voltage drop | depending on switch configuration open loop voltage of the control system < 23 V: approx. 6 V at 20 mA open loop voltage of the control system < 27 V: approx. 10 V at 20 mA | |
Input resistance | > 100 k&Omega, with field wiring open | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Current | 4 ... 20 mA | |
Load | 0 ... 650 &Omega | |
Voltage | &ge 13 V at 20 mA | |
Ripple | 20 mV rms | |
Transfer characteristics | ||
Accuracy | 0.1 % | |
Deviation | at 20 °C (68 °F), 0/4 ... 20 mA &le ± 0.1 % incl. non-linearity and hysteresis | |
Frequency range | bandwidth at 0.5 Vss signal 0 ... 3 kHz (-3 dB) | |
Rise time | 10 to 90 % &le 100 ms | |
Indicators/settings | ||
Display elements | LED | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Товаров: 0
На сумму: 0