General specifications | ||
---|---|---|
Signal type | Analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 9+, 10- | |
Rated voltage | 19 ... 30 V DC | |
Ripple | &le 10 % | |
Rated current | &le 30 mA | |
Power dissipation | &le 600 mW | |
Power consumption | &le 700 mW | |
Input | ||
Connection side | control side | |
Connection | terminals 5-, 6+ | |
Input signal | 4 ... 20 mA limited to approx. 30 mA | |
Voltage drop | depending on switch configuration open loop voltage of the control system < 23 V: approx. 6 V at 20 mA open loop voltage of the control system < 27 V: approx. 10 V at 20 mA | |
Input resistance | > 100 k&Omega, with field wiring open | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Current | 4 ... 20 mA | |
Load | 0 ... 650 &Omega | |
Voltage | &ge 13 V at 20 mA | |
Ripple | 20 mV rms | |
Transfer characteristics | ||
Accuracy | 0.1 % | |
Deviation | at 20 °C (68 °F), 0/4 ... 20 mA &le ± 0.1 % incl. non-linearity and hysteresis | |
Frequency range | bandwidth at 0.5 Vss signal 0 ... 3 kHz (-3 dB) | |
Rise time | 10 to 90 % &le 100 ms | |
Indicators/settings | ||
Display elements | LED | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IP20 according to EN 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | spring terminals | |
Mass | approx. 100 g | |
Dimensions | 12.5 x 114 x 124 mm (0.5 x 4.5 x 4.9 inch) , housing type A2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 0.8 W at 20 mA into 10 V (equivalent to 500 &Omega) load | |
Power consumption | 1 W at 20 mA | |
Input | ||
Connection side | control side | |
Connection | terminals 7-, 8+, (9+) | |
Voltage drop | approx. 4 V or internal resistance 200 &Omega at 20 mA | |
Input resistance | > 100 k&Omega, when wiring resistance in the field > 16 V (equivalent to 800 &Omega at 20 mA) | |
Current | 4 ... 20 mA limited to approx. 25 mA | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- | |
Current | 4 ... 20 mA | |
Load | 100 ... 700 &Omega | |
Voltage | &ge 14 V at 20 mA | |
Transfer characteristics | ||
Accuracy | 0.05 % | |
Rise time | < 100 µs , 10 ... 90 % step change | |
Indicators/settings | ||
Display elements | LEDs | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Signal type | Analog output | |
Functional safety related parameters | ||
Safety Integrity Level (SIL) | SIL 2 | |
Supply | ||
Connection | Power Rail or terminals 14+, 15- | |
Rated voltage | 20 ... 35 V DC | |
Ripple | within the supply tolerance | |
Power dissipation | 1.4 W at 20 mA into 10 V (equivalent to 500 &Omega) load | |
Power consumption | 1.8 W at 20 mA | |
Input | ||
Connection side | control side | |
Connection | terminals 7-, 8+, (9+) 10-, 11+, (12+) | |
Voltage drop | approx. 4 V or internal resistance 200 &Omega at 20 mA | |
Input resistance | > 100 k&Omega, when wiring resistance in the field > 16 V (equivalent to 800 &Omega at 20 mA) | |
Current | 4 ... 20 mA limited to approx. 25 mA | |
Output | ||
Connection side | field side | |
Connection | terminals 1+, 2- 4+, 5- | |
Current | 4 ... 20 mA | |
Load | 100 ... 700 &Omega | |
Voltage | &ge 14 V at 20 mA | |
Transfer characteristics | ||
Accuracy | 0.05 % | |
Rise time | < 100 µs , 10 ... 90 % step change | |
Indicators/settings | ||
Display elements | LEDs | |
Control elements | DIP-switch | |
Configuration | via DIP switches | |
Labeling | space for labeling at the front | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) | |
Conformity | ||
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529:2001 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Connection | screw terminals | |
Mass | approx. 150 g | |
Dimensions | 20 x 124 x 115 mm (0.8 x 4.9 x 4.5 inch) , housing type B2 | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Supply | ||
---|---|---|
Rated voltage | 19.2 ... 35 V DC | |
Rated current | 150 ... 100 mA | |
Power dissipation | 3 W | |
Ethernet Interface | ||
Intrinsically safe port | 10 BASE-T/100 BASE-TX | |
Non-intrinsically safe port | 10 BASE-T/100 BASE-TX | |
Connection type | 2 x RJ-45 , IEC 60603-7 | |
Connector pinout | socket TIA/EIA-568-B | |
Transfer rate | 10/100 Mbit/s , Auto-Negotiation | |
Operating mode | Half/Full Duplex | |
Cable type | CAT5e S/FTP AWG 24, Installation cable, L/R ratio max. 10 µH/&Omega of all strand combinations | |
I.S. cable length | typ. 100 m/20 °C | |
Total cable length | typ. 200 m/20 °C | |
Number of isolators | max. 2 in series connection | |
Indicators/operating means | ||
LED PWR | green: Power on | |
LED ACT | yellow: communication active | |
LED 10/100 | yellow ON: Transfer rate 100 MBit/s , OFF: 10 MBit/s | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Galvanic isolation | EN 50020 | |
Degree of protection | IEC 60529 | |
Climatic conditions | DIN IEC 721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ethernet | IEEE 802.3 , IEEE 802.3u | |
Ambient conditions | ||
Ambient temperature | -40 ... 60 °C (-40 ... 140 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g 10 ... 150 Hz | |
Pollution degree | max. 2, according to IEC 60664 | |
Mechanical specifications | ||
Connection type | Terminals | |
Core cross-section | up to 2.5 mm2 | |
Housing material | Polyamide PA 66 | |
Degree of protection | IP20 according to EN 60529 | |
Mass | 195 g | |
Mounting | DIN rail mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 2025 X | |
Marking | ![]() ![]() ![]() ![]() ![]() | |
Supply | ||
Maximum safe voltage | 253 V AC | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
CSA approval | CSA 15.70016295 | |
Control drawing | 116-B032 | |
Approved for | Class I, Zone 2, AEx/Ex nA [ia Ga] IIB T4 Gc Class I, Zone 2, AEx/Ex nA [ia Da IIIC] IIB T4 Gc | |
IECEx approval | IECEx PTB 09.0053X | |
Approved for | [Ex ia Ga] IIB [Ex ia Da] IIIC Ex nA [ia Ga] IIB T4 Gc Ex nA [ia IIIC Da] IIB T4 Gc [Ex ia Ma] I | |
Certificates and approvals | ||
Patents | This product may be covered by the following patent: US7,687,791 |
Supply | ||
---|---|---|
Rated voltage | 19.2 ... 35 V DC | |
Rated current | 150 ... 100 mA | |
Power dissipation | 3 W | |
Ethernet Interface | ||
Intrinsically safe port | 10 BASE-T/100 BASE-TX | |
Non-intrinsically safe port | 10 BASE-T/100 BASE-TX | |
Connection type | 2 x RJ-45 , IEC 60603-7 | |
Connector pinout | socket TIA/EIA-568-B | |
Transfer rate | 10/100 Mbit/s , Auto-Negotiation | |
Operating mode | Half/Full Duplex | |
Cable type | CAT5e S/FTP AWG 24, Installation cable, L/R ratio max. 10 µH/&Omega of all strand combinations | |
I.S. cable length | typ. 100 m/20 °C | |
Total cable length | typ. 200 m/20 °C | |
Number of isolators | max. 2 in series connection | |
Indicators/operating means | ||
LED PWR | green: Power on | |
LED ACT | yellow: communication active | |
LED 10/100 | yellow ON: Transfer rate 100 MBit/s , OFF: 10 MBit/s | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Galvanic isolation | EN 50020 | |
Degree of protection | IEC 60529 | |
Climatic conditions | DIN IEC 721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ethernet | IEEE 802.3 , IEEE 802.3u | |
Ambient conditions | ||
Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g 10 ... 150 Hz | |
Pollution degree | max. 2, according to IEC 60664 | |
Mechanical specifications | ||
Connection type | Terminals | |
Core cross-section | up to 2.5 mm2 | |
Housing material | Polyamide PA 66 | |
Degree of protection | IP20 according to EN 60529 | |
Mass | 195 g | |
Mounting | DIN rail mounting | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | PTB 07 ATEX 2025 X | |
Group, category, type of protection, temperature class | ![]() ![]() ![]() | |
Supply | ||
Maximum safe voltage | 253 V AC | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
Certificates and approvals | ||
Patents | This product may be covered by the following patent: US7,687,791 |
Supply | ||
---|---|---|
Connection | backplane LB9035A | |
Rated voltage | 24 V DC | |
Power consumption | max. 39 W , available output power for Zone 2 applications 5 W (5V), 20 W (12V), else 5 W (5V), 35 W (12V) | |
Auxiliary energy | 24 V DC Trunk load 10 mA according to FF standard. | |
Fieldbus interface | ||
FOUNDATION Fieldbus | ||
Connection | plug-in screw connector on the backplane | |
Baud rate | 31.25 kBit/s , MBP | |
Protocol | H1 to IEC 1158-2 | |
Station connection | directly at the trunk or via spur protector | |
Number of stations per bus line | 1 or 2, depending on the required response times | |
Number of channels per station | max. 20 analog, max. 40 digital | |
Bus length | max. 1900 m (must not be exceeded by the sum of all trunk and spur lines) | |
Spur length | max. 120 m (depending on the number of field devices. Modular I/O station = 1 field device) | |
Addressing | via PCS (software) | |
Indicators/settings | ||
LED indicator | Com unit LB8110*: LED green (power supply): on = operating, fast flash = cold start LED red (collective alarm): on = internal fault, flashing = no fieldbus LED yellow (operating mode): flashing = active Power supply LB9006C: LED green (power supply): off in case of loss of 24 V or 12 V or 5 V I/O modules (refer to the table with compatible modules for order codes): Power LED green: supply Diagnostic LED red: module fault, red flashing: communication error Status LED red: line fault Status LED yellow: signal (Live Zero status) | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2004/108/EC | EN 61326-1 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Dimensions | 275 x 127 mm (10.8 x 5 inch) | |
Data for application in connection with hazardous areas | ||
Statement of conformity | PF 08 CERT 1234 X | |
Group, category, type of protection, temperature class | ![]() | |
Directive conformity | ||
Directive 94/9/EC | EN 60079-0 , EN 60079-15 |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Fieldbus interface | ||
Fieldbus type | FOUNDATION Fieldbus | |
Physical layer profile | profile type 511 (FISCO), profile type 111 (Entity) | |
ITK version | 6.1.1 | |
Implementation | resource block 1x RS function block 4x DO, 12x DI, 1x AI, 2x MDI, 1x MDO transducer block 4x TB | |
FDE (Fault Disconnect Equipment) | 6.7 mA | |
Polarity | not polarity sensitive | |
Rated voltage | 9 ... 32 V | |
Rated current | max. 23 mA | |
Indicators/operating means | ||
LED PWR | green: on, bus voltage existent | |
LED COM ERR | red, continuous lightning: hardware error red, flashing: no bus activities or bus fault off: no error | |
LED CHANNEL ERROR | red, flashing: lead breakage/short circuit off: no error | |
DIP switch | Address setting , write protection , simulation | |
Analog input | ||
Number of inputs | 1 | |
Input type | Frequency input / Counter Input , channel 1 | |
Switching frequency | min. 0.1 Hz max. 5 kHz | |
Pulse duration | min. 80 µs | |
Supply voltage | 5 V | |
Supply current | 5 mA | |
Line fault detection | lead breakage , short circuit (not in counter mode) | |
Digital input | ||
Number of inputs | 12 | |
Input type | Sensor input , channels 1, 4, 7, 10 multiplexed , cycle adjustable | |
Supply voltage | 6.6 V | |
Supply current | 5 mA | |
Line fault detection | lead breakage , short circuit | |
Input type | Sensor input , channels 2, 3, 5, 6, 8, 9, 11, 12 multiplexed , cycle fixed | |
Supply voltage | 5 V | |
Supply current | 5 mA | |
Time delay before availability | 2 ms | |
Line fault detection | lead breakage , short circuit | |
Digital output | ||
Number of outputs | 4 | |
Output type | Low power valve , channels 1, 4, 7, 10 | |
Supply voltage | 6.6 V | |
Supply current | 1.5 mA | |
Line fault detection | lead breakage , short circuit | |
Galvanic isolation | ||
Foundation Fieldbus/Field circuit | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Standard conformity | ||
Galvanic isolation | EN 60079-11 | |
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC/EN 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -50 ... 75 °C (-58 ... 167 °F) hazardous area -50 ... 85 °C (-58 ... 185 °F) safe area | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 5 g , 10 ... 150 Hz | |
Pollution degree | 2 | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | plug-in terminals , spring terminal and screw terminal | |
Core cross-section | ||
Bus | up to 2.5 mm2 | |
Inputs | up to 2.5 mm2 | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | approx. 290 g | |
Mounting | mounting on DIN rail in cabinet | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 16 ATEX E 075 X | |
Marking | ![]() ![]() ![]() ![]() ![]() | |
Field-side | ||
Voltage | 9 V | |
Current | 43 mA | |
Power | 96 mW | |
FOUNDATION Fieldbus | ||
Maximum safe voltage | 253 V | |
Voltage | 24 V | |
Current | 380 mA | |
Power | 5.32 W | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-7:2015 | |
International approvals | ||
IECEx approval | IECEx BVS 16.0051X | |
Approved for | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ec [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I | |
Certificates and approvals | ||
Marine approval | pending |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Fieldbus interface | ||
Fieldbus type | PROFIBUS PA | |
FDE (Fault Disconnect Equipment) | 6.7 mA | |
Polarity | not polarity sensitive | |
Rated voltage | 9 ... 32 V | |
Rated current | max. 23 mA | |
Indicators/operating means | ||
LED PWR | green: on, bus voltage existent | |
LED COM ERR | red, continuous lightning: hardware error red, flashing: no bus activities or bus fault off: no error | |
LED CHANNEL ERROR | red, flashing: lead breakage/short circuit off: no error | |
DIP switch | Address setting , write protection , simulation | |
Analog input | ||
Number of inputs | 1 | |
Input type | Frequency input / Counter Input , channel 1 | |
Switching frequency | min. 0.1 Hz max. 5 kHz | |
Pulse duration | min. 80 µs | |
Supply voltage | 5 V | |
Supply current | 5 mA | |
Line fault detection | lead breakage , short circuit (not in counter mode) | |
Digital input | ||
Number of inputs | 12 | |
Input type | Sensor input , channels 1, 4, 7, 10 multiplexed , cycle adjustable | |
Supply voltage | 6.6 V | |
Supply current | 5 mA | |
Line fault detection | lead breakage , short circuit | |
Input type | Sensor input , channels 2, 3, 5, 6, 8, 9, 11, 12 multiplexed , cycle fixed | |
Supply voltage | 5 V | |
Supply current | 5 mA | |
Time delay before availability | 2 ms | |
Line fault detection | lead breakage , short circuit | |
Digital output | ||
Number of outputs | 4 | |
Output type | Low power valve , channels 1, 4, 7, 10 | |
Supply voltage | 6.6 V | |
Supply current | 1.5 mA | |
Line fault detection | lead breakage , short circuit | |
Galvanic isolation | ||
Foundation Fieldbus/Field circuit | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Standard conformity | ||
Galvanic isolation | EN 60079-11 | |
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC/EN 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -50 ... 75 °C (-58 ... 167 °F) hazardous area -50 ... 85 °C (-58 ... 185 °F) safe area | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 5 g , 10 ... 150 Hz | |
Pollution degree | 2 | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | plug-in terminals , spring terminal and screw terminal | |
Core cross-section | ||
Bus | up to 2.5 mm2 | |
Inputs | up to 2.5 mm2 | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | approx. 290 g | |
Mounting | mounting on DIN rail in cabinet | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 16 ATEX E 075 X | |
Marking | ![]() ![]() ![]() ![]() ![]() | |
PROFIBUS PA | ||
Maximum safe voltage | 253 V | |
Voltage | 24 V | |
Current | 380 mA | |
Power | 5.32 W | |
Field-side | ||
Voltage | 9 V | |
Current | 43 mA | |
Power | 96 mW | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-7:2015 | |
International approvals | ||
IECEx approval | IECEx BVS 16.0051X | |
Approved for | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ec [ia Ga] IIC T4 Gc , [Ex ia Da] IIIC , [Ex ia Ma] I | |
Certificates and approvals | ||
Marine approval | pending |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Electronic component | Binary multi-input/output R8D0-MIO-Ex12.FF* For technical data on installed electronic component see data sheet. | |
Fieldbus interface | ||
Fieldbus type | FOUNDATION Fieldbus | |
Galvanic isolation | ||
Foundation Fieldbus/Field circuit | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Standard conformity | ||
Galvanic isolation | EN 60079-11 | |
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 10 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | plug-in terminals , spring terminal and screw terminal | |
Core cross-section | ||
Bus | up to 2.5 mm2 | |
Inputs | up to 2.5 mm2 | |
Cable diameter | see table 2 | |
Cable gland | sensor inputs M16, fieldbus M20 | |
Housing material | EN 1780-1 46000 , ISO AlSi9Cu3(Fe) , anodized | |
Degree of protection | IP66 | |
Mass | 1800 g | |
Mounting | panel mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 16 ATEX E 075 X | |
Marking | ![]() ![]() ![]() ![]() ![]() ![]() | |
Bus | FISCO see EC-Type Examination Certificate | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx BVS 16.0051X | |
Approved for | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ec [ia Ga] IIC T4 Gc , [Ex ia Ma] I , [Ex ia Da] IIIC , Ex tb [ia Da] IIIC T130 °C Db | |
Certificates and approvals | ||
Marine approval | pending |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Electronic component | Binary multi-input/output R8D0-MIO-Ex12.PA* For technical data on installed electronic component see data sheet. | |
Fieldbus interface | ||
Fieldbus type | PROFIBUS PA | |
Galvanic isolation | ||
Foundation Fieldbus/Field circuit | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Low voltage | ||
Directive 2014/35/EU | EN 61010-1:2010 | |
Standard conformity | ||
Galvanic isolation | EN 60079-11 | |
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 10 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | plug-in terminals , spring terminal and screw terminal | |
Core cross-section | ||
Bus | up to 2.5 mm2 | |
Inputs | up to 2.5 mm2 | |
Cable diameter | see table 2 | |
Cable gland | sensor inputs M16, fieldbus M20 | |
Housing material | EN 1780-1 46000 , ISO AlSi9Cu3(Fe) , anodized | |
Degree of protection | IP66 | |
Mass | 1800 g | |
Mounting | panel mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | BVS 16 ATEX E 075 X | |
Marking | ![]() ![]() ![]() ![]() ![]() ![]() | |
Bus | FISCO see EC-Type Examination Certificate | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx BVS 16.0051X | |
Approved for | Ex ib [ia Ga] IIC T4 Gb , Ex ic [ia Ga] IIC T4 Gc , Ex ec [ia Ga] IIC T4 Gc , [Ex ia Ma] I , [Ex ia Da] IIIC , Ex tb [ia Da] IIIC T130 °C Db | |
Certificates and approvals | ||
Marine approval | pending |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Binary multi-input/output R8D0-MIO-Ex12.FF* , For technical data on installed electronic component see data sheet. | |
Fieldbus interface | ||
Fieldbus type | FOUNDATION Fieldbus | |
Conformity | ||
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Dimensions | (W x H x D) 271 x 271 x 136 mm | |
Mounting | thru-holes Ø6.5 mm | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Certificate | PF 16 CERT 4011 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request | |
INMETRO | TÜV 13.1143 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Binary multi-input/output R8D0-MIO-Ex12.PA* , For technical data on installed electronic component see data sheet. | |
Fieldbus interface | ||
Fieldbus type | PROFIBUS PA | |
Conformity | ||
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Dimensions | (W x H x D) 271 x 271 x 136 mm | |
Mounting | thru-holes Ø6.5 mm | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Certificate | PF 16 CERT 4011 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request | |
INMETRO | TÜV 13.1143 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Binary multi-input/output R8D0-MIO-Ex12.FF* , For technical data on installed electronic component see data sheet. | |
Fieldbus interface | ||
Fieldbus type | FOUNDATION Fieldbus | |
Conformity | ||
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Dimensions | (W x H x D) 300 x 230 x 132 mm | |
Mounting | thru-holes Ø10 mm | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Certificate | PF 16 CERT 4011 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request | |
INMETRO | TÜV 13.1143 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Binary multi-input/output R8D0-MIO-Ex12.PA* , For technical data on installed electronic component see data sheet. | |
Fieldbus interface | ||
Fieldbus type | PROFIBUS PA | |
Conformity | ||
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Dimensions | (W x H x D) 300 x 230 x 132 mm | |
Mounting | thru-holes Ø10 mm | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Certificate | PF 16 CERT 4011 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request | |
INMETRO | TÜV 13.1143 |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Fieldbus interface | ||
Fieldbus type | FOUNDATION Fieldbus | |
Physical layer profile | profile type 511 (FISCO), profile type 111 (Entity) | |
ITK version | 4.51 | |
Implementation | resource block function block transducer block | |
Execution time | AI, MAI 40 ms max. | |
Macro cycle | typical for one device 8xAI or 1xMAI max. 500 ms | |
Firmware update | via separate plug connection | |
FDE (Fault Disconnect Equipment) | 6.7 mA | |
Polarity | not polarity sensitive | |
Rated voltage | 9 ... 32 V | |
Rated current | max. 23 mA | |
Indicators/operating means | ||
LED PWR | green: on, bus voltage existent | |
LED COM ERR | red: continuous lightning: hardware error 2 Hz flashing: no bus activities or bus fault off: no error | |
LED CHANNEL ERROR | red: 2 Hz flashing: lead breakage, overrange off: no error | |
Input | ||
Number | 8 | |
Sensor types | see table 1 | |
Grounding | grounding of thermoelements possible | |
Error detection | lead breakage, wiring error, hardware device error | |
Common mode voltage | Input to Input 600 Vpeak | |
Transfer characteristics | ||
Deviation | ||
Influence of ambient temperature | see table 3 | |
Linearization | T/C input 0.1°C RTD input 0.03°C | |
Internal measurement cycle | for all sensor types max. 1 s | |
Galvanic isolation | ||
Fieldbus/inputs | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Galvanic isolation | EN 60079-11 | |
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area -40 ... 85 °C (-40 ... 185 °F) safe area | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 5 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | plug-in terminals , spring terminal and screw terminal | |
Core cross-section | ||
Bus | up to 2.5 mm2 | |
Inputs | up to 2.5 mm2 | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | 360 g | |
Mounting | mounting on DIN rail in cabinet | |
Data for application in connection with hazardous areas | ||
EC-Type Examination Certificate | PTB 03 ATEX 2237 | |
Group, category, type of protection, temperature class | ![]() ![]() ![]() ![]() | |
Bus | FISCO see EC-Type Examination Certificate | |
Inputs | see EC-Type Examination Certificate | |
Statement of conformity | PTB 03 ATEX 2238 X | |
Group, category, type of protection, temperature class | ![]() | |
Galvanic isolation | ||
Bus | see Statement of Conformity | |
Input | see EC-Type Examination Certificate | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx PTB 05.0001 , IECEx PTB 05.0002X | |
Approved for | Ex ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc | |
Certificates and approvals | ||
Marine approval | DNV A-14038 |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Fieldbus interface | ||
Fieldbus type | PROFIBUS PA | |
Firmware update | via separate plug connection | |
FDE (Fault Disconnect Equipment) | 6.7 mA | |
Polarity | not polarity sensitive | |
Rated voltage | 9 ... 32 V | |
Rated current | max. 23 mA | |
PROFIBUS PA | ||
Profile | 3.02 | |
Indicators/operating means | ||
LED PWR | green: on, bus voltage existent | |
LED COM ERR | red, continuous lightning: hardware error red, flashing: no bus activities or bus fault off: no error | |
LED CHANNEL ERROR | red: 2 Hz flashing: lead breakage, overrange off: no error | |
Input | ||
Number | 8 | |
Sensor types | see table 1 | |
Grounding | grounding of thermoelements possible | |
Error detection | lead breakage, wiring error, hardware device error | |
Common mode voltage | Input to Input 600 Vpeak | |
Transfer characteristics | ||
Deviation | ||
Influence of ambient temperature | see table 3 | |
Linearization | T/C input 0.1°C RTD input 0.03°C | |
Internal measurement cycle | for all sensor types max. 1 s | |
Galvanic isolation | ||
Fieldbus/inputs | safe galvanic isolation acc. to EN 60079-11, voltage peak value 375 V | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Galvanic isolation | EN 60079-11 | |
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) hazardous area -40 ... 85 °C (-40 ... 185 °F) safe area | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 5 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | plug-in terminals , spring terminal and screw terminal | |
Core cross-section | ||
Bus | up to 2.5 mm2 | |
Inputs | up to 2.5 mm2 | |
Housing material | Polycarbonate | |
Degree of protection | IP20 | |
Mass | 360 g | |
Mounting | mounting on DIN rail in cabinet | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 03 ATEX 2237 | |
Marking | ![]() ![]() ![]() ![]() | |
Bus | FISCO see EC-Type Examination Certificate | |
Voltage | 24 V | |
Inputs | see EC-Type Examination Certificate | |
Certificate | PTB 03 ATEX 2238 X | |
Marking | ![]() | |
Galvanic isolation | ||
Bus | see Statement of Conformity | |
Input | see EC-Type Examination Certificate | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | CoC 3025732 | |
CSA approval | CoC 3025732C | |
IECEx approval | IECEx PTB 05.0001 , IECEx PTB 05.0002X | |
Approved for | Ex ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc | |
Certificates and approvals | ||
Marine approval | DNV A-14038 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Electronic component | Temperature Multi-Input Device RD0-TI-Ex8.FF* For technical data on installed electronic component see data sheet. | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Galvanic isolation | EN 60079-11 | |
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | see table 1 | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 10 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | plug-in terminals , spring terminal and screw terminal | |
Core cross-section | ||
Bus | up to 2.5 mm2 | |
Inputs | up to 2.5 mm2 | |
Cable diameter | see table 2 | |
Cable gland | sensor inputs M16, fieldbus M20 | |
Housing material | EN 1780-1 46000 , ISO AlSi9Cu3(Fe) , anodized | |
Degree of protection | IP67 | |
Mass | 1800 g | |
Mounting | panel mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 03 ATEX 2237 | |
Marking | ![]() ![]() ![]() ![]() | |
Bus | FISCO see EC-Type Examination Certificate | |
Inputs | see EC-Type Examination Certificate | |
Certificate | PTB 03 ATEX 2238 X | |
Marking | ![]() | |
Galvanic isolation | ||
Bus | see Statement of Conformity | |
Input | see EC-Type Examination Certificate | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
IECEx approval | IECEx PTB 05.0001 , IECEx PTB 05.0002X | |
Approved for | Ex ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc | |
Certificates and approvals | ||
Marine approval | DNV A-14038 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Electronic component | Temperature Multi-Input Device RD0-TI-Ex8.PA* For technical data on installed electronic component see data sheet. | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Galvanic isolation | EN 60079-11 | |
Electromagnetic compatibility | NE 21:2011 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Ambient conditions | ||
Ambient temperature | see table 1 | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g , 11 ms | |
Vibration resistance | 10 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | plug-in terminals , spring terminal and screw terminal | |
Core cross-section | ||
Bus | up to 2.5 mm2 | |
Inputs | up to 2.5 mm2 | |
Cable diameter | see table 2 | |
Cable gland | sensor inputs M16, fieldbus M20 | |
Housing material | EN 1780-1 46000 , ISO AlSi9Cu3(Fe) , anodized | |
Degree of protection | IP66 | |
Mass | 1800 g | |
Mounting | panel mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 03 ATEX 2237 | |
Marking | ![]() ![]() ![]() ![]() | |
Bus | FISCO see EC-Type Examination Certificate | |
Voltage | 24 V | |
Inputs | see EC-Type Examination Certificate | |
Certificate | PTB 03 ATEX 2238 X | |
Marking | ![]() | |
Galvanic isolation | ||
Bus | see Statement of Conformity | |
Input | see EC-Type Examination Certificate | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 | |
International approvals | ||
FM approval | CoC 3025732 | |
CSA approval | CoC 3025732C | |
IECEx approval | IECEx PTB 05.0001 , IECEx PTB 05.0002X | |
Approved for | Ex ia [ia Ga] IIC T4 Gb , [Ex ia Ga] IIC , [Ex ia Da] IIIC , Ex ic IIC T4 Gc , Ex nA IIC T4 Gc | |
Certificates and approvals | ||
Marine approval | DNV A-14038 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Temperature Multi-Input Device RD0-TI-Ex8.FF.ST For technical data on installed electronic component see data sheet. | |
Conformity | ||
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Dimensions | (W x H x D) 271 x 271 x 136 mm (1 x RD0-TI-Ex8.FF.ST) | |
Mounting | thru-holes Ø6.5 mm | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Certificate | PF 16 CERT 3134 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request | |
INMETRO | TÜV 13.1143 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Temperature Multi-Input Device RD0-TI-Ex8.PA.ST For technical data on installed electronic component see data sheet. | |
Conformity | ||
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Dimensions | (W x H x D) 271 x 271 x 136 mm (1 x RD0-TI-Ex8.FF.ST) | |
Mounting | thru-holes Ø6.5 mm | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Certificate | PF 16 CERT 3134 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request | |
INMETRO | TÜV 13.1143 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Temperature Multi-Input Device RD0-TI-Ex8.FF.ST For technical data on installed electronic component see data sheet. | |
Conformity | ||
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Dimensions | (W x H x D) 300 x 200 x 120 mm (1 x RD0-TI-Ex8.FF.ST) | |
Mounting | thru-holes Ø10 mm | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Certificate | PF 16 CERT 3134 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request | |
INMETRO | TÜV 13.1143 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Temperature Multi-Input Device RD0-TI-Ex8.PA.ST For technical data on installed electronic component see data sheet. | |
Conformity | ||
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -30 ... 55 °C (-22 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Dimensions | (W x H x D) 300 x 200 x 120 mm (1 x RD0-TI-Ex8.FF.ST) | |
Mounting | thru-holes Ø10 mm | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Certificate | PF 16 CERT 3134 X (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Marking | ![]() ![]() ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-31:2014 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 , Zone 1 , suitable Junction Box on request IECEx PTB 09.0016 , Zone 2 , suitable Junction Box on request | |
INMETRO | TÜV 13.1143 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Valve Coupler FD0-VC-Ex4.** For technical data on installed electronic component see data sheet. | |
Conformity | ||
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Dimensions | (W x H x D) 271 x 544 x 136 mm (1 x FD0-VC-Ex4.**) | |
Mounting | thru-holes Ø6.5 mm | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 , suitable Junction Box on request | |
INMETRO | TÜV 13.1143 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Valve Coupler FD0-VC-Ex4.** For technical data on installed electronic component see data sheet. | |
Conformity | ||
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Dimensions | (W x H x D) 271 x 544 x 136 mm (1 x FD0-VC-Ex4.**) | |
Mounting | thru-holes Ø6.5 mm | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 , suitable Junction Box on request | |
INMETRO | TÜV 13.1143 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Valve Coupler FD0-VC-Ex4.** For technical data on installed electronic component see data sheet. | |
Conformity | ||
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Dimensions | (W x H x D) 380 x 380 x 175 mm (1 x FD0-VC-Ex4.**) | |
Mounting | thru-holes Ø10 mm | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 , suitable Junction Box on request | |
INMETRO | TÜV 13.1143 |
General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Installed components | Valve Coupler FD0-VC-Ex4.** For technical data on installed electronic component see data sheet. | |
Conformity | ||
Degree of protection | EN 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 55 °C (-4 ... 131 °F) , (extended temperature range available on request) | |
Storage temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Relative humidity | < 75 % (annual mean) < 95 % (30 d/year), no moisture condensation | |
Mechanical specifications | ||
Degree of protection | IP66 | |
Dimensions | (W x H x D) 380 x 380 x 175 mm (1 x FD0-VC-Ex4.**) | |
Mounting | thru-holes Ø10 mm | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 07 ATEX 1061 (assembled Junction Box) , for additional certificates see www.pepperl-fuchs.com | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 | |
International approvals | ||
IECEx approval | IECEx PTB 07.0036 , suitable Junction Box on request | |
INMETRO | TÜV 13.1143 |
Supply | ||
---|---|---|
Connection | backplane bus | |
Rated voltage | 5 V DC , only in connection with the power supplies FB92** | |
Power consumption | 2 W | |
Auxiliary energy | 24 V DC Trunk load 20 mA | |
Fieldbus interface | ||
Fieldbus type | FOUNDATION Fieldbus H1 | |
FOUNDATION Fieldbus | ||
Connection | wired to Ex e terminals via backplane | |
Baud rate | 31.25 kBit/s , MBP | |
Protocol | H1 to IEC 1158-2 | |
Station connection | directly at the trunk or via spur protector | |
Number of stations per bus line | 1 or 2, depending on the required response times | |
Number of channels per station | max. 20 analog, max. 40 digital | |
Supported I/O modules | 5 slots, to be filled with (combinations possible): 1*08 digital input, 8-channel, NAMUR 3*05 analog input, 4-channel, 20 mA (HART via service bus) 4*05 analog output, 4-channel, 20 mA (HART via service bus) 5204 Pt100 RTD input, 4-channel 5205 thermocouple input, 4-channel 6305 relay output, 4-channel, 230 V 6306 relay output, 8-channel, 24 V 6*08 digital output, 8-channel, Ex i 6210-6215 digital output, 4-channel, Ex i power * = variable (2=IS, 3=Ex e) | |
Bus length | max. 1900 m (must not be exceeded by the sum of all trunk and spur lines) | |
Spur length | max. 120 m (depending on the number of field devices. Modular I/O station = 1 field device) | |
Addressing | via PCS (software) | |
Internal bus | ||
Connection | backplane bus | |
Indicators/settings | ||
LED indicator | LED green (power supply): On = operating, fast flash = cold start LED red (collective alarm): On = internal fault, flashing = no fieldbus LED yellow (operating mode): Flashing = active | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | via backplane | |
Mass | approx. 750 g | |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 97 ATEX 1074 U | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
International approvals | ||
ATEX approval | PTB 97 ATEX 1075 | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
DNV GL Marine | TAA0000034 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |
Supply | ||
---|---|---|
Connection | backplane bus | |
Rated voltage | 5 V DC , only in connection with the power supplies LB9*** | |
Power consumption | 2 W | |
Auxiliary energy | 24 V DC Trunk load 20 mA | |
Fieldbus interface | ||
Fieldbus type | FOUNDATION Fieldbus H1 | |
FOUNDATION Fieldbus | ||
Connection | plug-in screw connector on the backplane | |
Baud rate | 31.25 kBit/s , MBP | |
Protocol | H1 to IEC 1158-2 | |
Station connection | directly at the trunk or via spur protector | |
Number of stations per bus line | 1 or 2, depending on the required response times | |
Number of channels per station | max. 20 analog, max. 40 digital | |
Supported I/O modules | 5 slots, to be filled with (combinations possible): 1*08 digital input, 8-channel, NAMUR 3*05 analog input, 4-channel, 20 mA (HART via service bus) 4*05 analog output, 4-channel, 20 mA (HART via service bus) 5*04 Pt100 RTD input, 4-channel 5*05 thermocouple input, 4-channel 6005 relay output, 4-channel, 230 V 6006 relay output, 8-channel, 24 V 6*08 digital output, 8-channel, Ex i 6*10-6*15 digital output, 4-channel, Ex i power * = variable (0=non-IS, 1=IS) | |
Bus length | max. 1900 m (must not be exceeded by the sum of all trunk and spur lines) | |
Spur length | max. 120 m (depending on the number of field devices. Modular I/O station = 1 field device) | |
Addressing | via PCS (software) | |
Internal bus | ||
Connection | backplane bus | |
Indicators/settings | ||
LED indicator | LED 1 (power supply): On = operating, fast flash = cold start LED 2 (collective alarm): On = internal fault, flashing = no fieldbus LED 3 (operating mode): Flashing = active | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , mounted on backplane | |
Connection | via backplane | |
Mass | approx. 150 g | |
Dimensions | 32.5 x 100 x 102 mm (1.28 x 3.9 x 4 inch) | |
Data for application in connection with hazardous areas | ||
Certificate | PF 08 CERT 1234 X | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-11:2007 EN 60079-15:2010 | |
International approvals | ||
ATEX approval | PF 08 CERT 1234 X | |
UL approval | E106378 | |
Control drawing | 116-0321 | |
Approved for | cUL (Canada): CL I Zn. 2 IIC IS circuits for CL I Zn. 0 IIC ULus (USA): CL I Div. 2 Grp. A, B, C, D IS circuits for CL I, II, III Div. 1 Grp. A, B, C, D, E, F, G | |
IECEx approval | BVS 09.0037X | |
Approved for | Ex nA IIC T4 Gc | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15-20021 | |
DNV GL Marine | TAA0000034 | |
American Bureau of Shipping | T1450280/UN |
Описание оборудования | ||
---|---|---|
Com Unit for MODBUS RTU |
Supply | ||
---|---|---|
Connection | backplane bus | |
Rated voltage | 5 V DC , only in connection with the power supplies FB92** | |
Power consumption | 2 W | |
Fieldbus interface | ||
Fieldbus type | MODBUS RTU | |
MODBUS RTU | ||
Connection | wired to Ex e terminals via backplane | |
Baud rate | max. 38.4 kBit/s | |
Number of stations per bus line | max. 245 (MODBUS), max. 119 (service bus) | |
Number of channels per station | max. 80 analog, max. 184 digital (standard configuration) | |
Number of stations per bus segment | max. 31 (RS-485 standard) | |
Number of repeaters between Master and Slave | max. 3 | |
Supported I/O modules | all FB remote I/O modules | |
Bus length | max. 1200 m (FOL, 38.4 kBd), max. 1200 m (copper cable, 38.4 kBd) | |
FOL (fiber optic link) | additional hardware required | |
Addressing | via configuration software | |
MODBUS address | standard compliant (factory standard setting: 126) | |
Service bus address | max. 119 , redundancy address = base + 128 (automatic) | |
HART communication | via service bus | |
Internal bus | ||
Connection | backplane bus | |
Redundancy | via front connector | |
Indicators/settings | ||
LED indicator | LED green (power supply): On = operating, fast flash = cold start LED red (collective alarm): On = internal fault, flashing = no Modbus RTU connection LED yellow (operating mode): flashing 1 (1:1 ratio) = active, normal operation flashing 2 (7:1 ratio) = active, simulation | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1 | |
Conformity | ||
Electromagnetic compatibility | NE 21 | |
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) | |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) | |
Relative humidity | 95 % non-condensing | |
Shock resistance | shock type I, shock duration 11 ms, shock amplitude 15 g, number of shocks 18 | |
Vibration resistance | frequency range 10 ... 150 Hz transition frequency: 57.56 Hz, amplitude/acceleration ± 0.075 mm/1 g 10 cycles frequency range 5 ... 100 Hz transition frequency: 13.2 Hz amplitude/acceleration ± 1 mm/0.7 g 90 minutes at each resonance | |
Damaging gas | designed for operation in environmental conditions acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Degree of protection | IP20 (module) , a separate housing is required acc. to the system description | |
Connection | via backplane | |
Mass | approx. 750 g | |
Dimensions | 57 x 107 x 132 mm (2.2 x 4.2 x 5.2 inch) | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | PTB 97 ATEX 1074 U | |
Marking | ![]() | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2009 EN 60079-1:2007 EN 60079-11:2007 EN 60079-26:2007 EN 61241-11:2006 | |
International approvals | ||
ATEX approval | PTB 97 ATEX 1075 | |
EAC approval | Russia: RU C-IT.MIII06.B.00129 | |
Marine approval | ||
Lloyd Register | 15/20021 | |
DNV GL Marine | TAA0000034 | |
American Bureau of Shipping | T1450280/UN | |
Bureau Veritas Marine | 22449/B0 BV |