General specifications | ||
---|---|---|
Design / Mounting | Outside installation | |
Electrical specifications | ||
Rated voltage | 32 V | |
Rated current | 550 mA | |
Nominal discharge current (8/20 µs) | ||
per line | 10 kA | |
total | 10 kA | |
Max. surge current (8/20 µs) | 10 kA | |
Voltage protection level at max. rated current | ||
Line/Line | 58 V | |
Line/Earth | 1700 V | |
Voltage protection level at 1 kV/µsec | ||
Line/Line | 50 V | |
Line/Earth | 1.2 kV | |
Reaction time | ||
Line/Line | max. 1 ns | |
Line/Earth | max. 100 ns | |
Capacitance | ||
Line/Line | 25 pF | |
Line/Earth | 15 pF | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NE 21:2006 | |
Degree of protection | IEC/EN 60529 | |
Fieldbus standard | IEC 61158-2 | |
Surge protection | IEC 61643-21 | |
Ambient conditions | ||
Ambient temperature | -50 ... 80 °C (-58 ... 176 °F) | |
Storage temperature | -50 ... 85 °C (-58 ... 185 °F) | |
Mechanical specifications | ||
Core cross-section | 1.3 mm2 | |
Housing material | Stainless steel 1.4401 (AISI 316) surface all over polished | |
Degree of protection | IP00/IP67 if correctly installed | |
Mass | 160 g | |
Mounting | screw mounting | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | KEMA 04 ATEX 1317 X | |
Marking | II 2(1)G Ex ia IIC T4/T5/T6 | |
Voltage | Entity 30 V , FISCO 17.5 V | |
Current | Entity 550 mA , FISCO 380 mA | |
Power | Entity 3 W , FISCO 5.32 W | |
Internal capacitance | negligible 0 nF | |
Internal inductance | negligible 0 µH | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-26:2007 | |
International approvals | ||
IECEx approval | IECEx KEM 09.0081X | |
Approved for | Ex ia [ia Ga] IIC T5/T6 Gb | |
Certificates and approvals | ||
Marine approval | DNV A-14038 |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Fieldbus interface | ||
Self current consumption | max. 6 mA (for version TPH-LBF-IA1.36.DE.1) , max. 0 mA (for version TPH-LBF-IA1.36.DE.0) | |
Indicators/operating means | ||
LED ERR | green flashing: status OK , red flashing: maintenance required , (for version TPH-LBF-IA1.36.DE.1) | |
Electrical specifications | ||
Rated voltage | 36 V | |
Rated current | 600 mA | |
Voltage protection level | ||
Line/Line | max. 50 V category B2 10/700µsec , 25 A max. 52 V category C1 8/20µsec , 300 A max. 55 V category C2 8/20µsec , 5 kA max. 46 V category C3 1kV/µsec , 10 A | |
Line/Earth | max. 1060 V category B2 10/700µsec , 50 A per line max. 800 V category C1 8/20µsec , 300 A per line max. 1450 V category C2 8/20µsec , 5 kA per line max. 1300 V category C3 1kV/µsec , 50 A per line max. 1080 V category D1 10/350µsec , 500 A per line | |
Reaction time | ||
Line/Line | max. 1 ns | |
Line/Earth | max. 100 ns | |
Overstressed fault mode | acc. IEC 61643-21 line inoperable mode 3 | |
Series resistance in line | 2 &Omega +/- 5 % | |
Impulse durability | ||
Per line | 5 kA category C2 8/20µsec | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NAMUR NE 21 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | IEC 60721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Surge protection | IEC 61643-21 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | screw terminals | |
Core cross-section | flexible wire 2.5 mm2 solid wire max. 4 mm2 | |
Housing material | Polyamide PA 6.6 | |
Degree of protection | IP20 | |
Mass | 45 g | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | SIRA 12 ATEX 2128X | |
Marking | II 1G Ex ia IIC T4 | |
Voltage | 24 V | |
Current | 500 mA | |
Internal capacitance | 2 nF | |
Internal inductance | 0.1 µH | |
Certificate | SIRA 12 ATEX 4176X | |
Marking | II 3G Ex nAc IIC T4 , II 3G Ex ic IIC T4 Class I and II, Division 1, Group C - G | |
Voltage | 33 V | |
Current | 600 mA | |
Internal capacitance | 2 nF | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 | |
Supplementary information | FISCO field device | |
International approvals | ||
CSA approval | CoC 2595441 | |
Control drawing | 116-0365 | |
Approved for | Class I, Division 1, Groups A, B, C, D T4 Class I, Zone 1, Ex ia IIC T4 Class I, Zone 2, Ex ic IIC T4 Class I, Zone 0, AEx ia IIC T4 Class I, Zone 2, AEx ic IIC T4 Class I, Division 2, Groups A, B, C, D T4 Class I, Zone 2, Ex nL IIC T4 Class I, Zone 2, Ex na IIC T4 Class I, Zone 2, AEx nAc IIC T4 | |
IECEx approval | IECEx SIR 12.0051X | |
Approved for | Ex ia IIC T4 |
General specifications | ||
---|---|---|
Design / Mounting | Cabinet installation | |
Fieldbus interface | ||
Self current consumption | max. 6 mA (for version TPH-LBF-IA1.36.DE.1) , max. 0 mA (for version TPH-LBF-IA1.36.DE.0) | |
Indicators/operating means | ||
LED ERR | green flashing: status OK , red flashing: maintenance required , (for version TPH-LBF-IA1.36.DE.1) | |
Electrical specifications | ||
Rated voltage | 36 V | |
Rated current | 600 mA | |
Voltage protection level | ||
Line/Line | max. 50 V category B2 10/700µsec , 25 A max. 52 V category C1 8/20µsec , 300 A max. 55 V category C2 8/20µsec , 5 kA max. 46 V category C3 1kV/µsec , 10 A | |
Line/Earth | max. 1060 V category B2 10/700µsec , 50 A per line max. 800 V category C1 8/20µsec , 300 A per line max. 1450 V category C2 8/20µsec , 5 kA per line max. 1300 V category C3 1kV/µsec , 50 A per line max. 1080 V category D1 10/350µsec , 500 A per line | |
Reaction time | ||
Line/Line | max. 1 ns | |
Line/Earth | max. 100 ns | |
Overstressed fault mode | acc. IEC 61643-21 line inoperable mode 3 | |
Series resistance in line | 2 &Omega +/- 5 % | |
Impulse durability | ||
Per line | 5 kA category C2 8/20µsec | |
Directive conformity | ||
Electromagnetic compatibility | ||
Directive 2014/30/EU | EN 61326-1:2013 | |
Standard conformity | ||
Electromagnetic compatibility | NAMUR NE 21 | |
Degree of protection | IEC 60529 | |
Fieldbus standard | IEC 61158-2 | |
Climatic conditions | IEC 60721 | |
Shock resistance | EN 60068-2-27 | |
Vibration resistance | EN 60068-2-6 | |
Surge protection | IEC 61643-21 | |
Ambient conditions | ||
Ambient temperature | -40 ... 70 °C (-40 ... 158 °F) | |
Storage temperature | -40 ... 85 °C (-40 ... 185 °F) | |
Relative humidity | &le 95 % non-condensing | |
Shock resistance | 15 g 11 ms | |
Vibration resistance | 1 g , 10 ... 150 Hz | |
Corrosion resistance | acc. to ISA-S71.04-1985, severity level G3 | |
Mechanical specifications | ||
Connection type | screw terminals | |
Core cross-section | flexible wire 2.5 mm2 solid wire max. 4 mm2 | |
Housing material | Polyamide PA 6.6 | |
Degree of protection | IP20 | |
Mass | 45 g | |
Data for application in connection with hazardous areas | ||
EU-Type Examination Certificate | SIRA 12 ATEX 2128X | |
Marking | II 1G Ex ia IIC T4 | |
Voltage | 24 V | |
Current | 500 mA | |
Internal capacitance | 2 nF | |
Internal inductance | 0.1 µH | |
Certificate | SIRA 12 ATEX 4176X | |
Marking | II 3G Ex nAc IIC T4 , II 3G Ex ic IIC T4 Class I and II, Division 1, Group C - G | |
Voltage | 33 V | |
Current | 600 mA | |
Internal capacitance | 2 nF | |
Directive conformity | ||
Directive 2014/34/EU | EN 60079-0:2012 , EN 60079-11:2012 , EN 60079-15:2010 , EN 60079-26:2007 | |
Supplementary information | FISCO field device | |
International approvals | ||
CSA approval | CoC 2595441 | |
Control drawing | 116-0365 | |
Approved for | Class I, Division 1, Groups A, B, C, D T4 Class I, Zone 1, Ex ia IIC T4 Class I, Zone 2, Ex ic IIC T4 Class I, Zone 0, AEx ia IIC T4 Class I, Zone 2, AEx ic IIC T4 Class I, Division 2, Groups A, B, C, D T4 Class I, Zone 2, Ex nL IIC T4 Class I, Zone 2, Ex na IIC T4 Class I, Zone 2, AEx nAc IIC T4 | |
IECEx approval | IECEx SIR 12.0051X | |
Approved for | Ex ia IIC T4 |
General specifications | ||
---|---|---|
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 1 | |
Electrical specifications | ||
Nominal voltage | 120 V AC | |
Maximum continuous operating voltage | max. 150 V AC max. 200 V DC | |
Nominal discharge current (8/20 µs) | 15 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 50 g | |
Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
Mounting | in the surge protection barrier M-LB-*.****.* |
General specifications | ||
---|---|---|
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 1 | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 275 V AC max. 350 V DC | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 50 g | |
Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
Mounting | in the surge protection barrier M-LB-*.****.* |
General specifications | ||
---|---|---|
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 1 | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 255 V AC | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 50 g | |
Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
Mounting | in the surge protection barrier M-LB-*.****.* |
General specifications | ||
---|---|---|
Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
Number of protected supply lines | 1 | |
Electrical specifications | ||
Nominal voltage | 120 V AC | |
Maximum continuous operating voltage | max. 150 V AC/DC | |
Nominal discharge current (8/20 µs) | 2 kA | |
Max. surge current (8/20 µs) | 4 kA | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 50 g | |
Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
Mounting | in the surge protection barrier M-LB-*.****.* |
General specifications | ||
---|---|---|
Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
Number of protected supply lines | 1 | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 255 V AC/DC | |
Nominal discharge current (8/20 µs) | 3 kA | |
Max. surge current (8/20 µs) | 5 kA | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 50 g | |
Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
Mounting | in the surge protection barrier M-LB-*.****.* |
General specifications | ||
---|---|---|
Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
Number of protected supply lines | 1 | |
Electrical specifications | ||
Nominal voltage | 24 V AC | |
Maximum continuous operating voltage | max. 30 V AC/DC | |
Nominal discharge current (8/20 µs) | 1 kA | |
Max. surge current (8/20 µs) | 2 kA | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 50 g | |
Dimensions | 18 x 45 x 51 mm (0.7 x 1.8 x 2 inch) (1 TE acc. to DIN 43880) | |
Mounting | in the surge protection barrier M-LB-*.****.* |
General specifications | ||
---|---|---|
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 1 | |
Suitable components | protection module M-LB-1.150.M | |
Electrical specifications | ||
Nominal voltage | 120 V AC | |
Maximum continuous operating voltage | max. 150 V AC max. 200 V DC | |
Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 15 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 240 g | |
Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 1 | |
Suitable components | protection module M-LB-1.275.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 275 V AC max. 350 V DC | |
Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 240 g | |
Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
Number of protected supply lines | 2 | |
Suitable components | protection module M-LB-2.150.T3.M | |
Electrical specifications | ||
Nominal voltage | 120 V AC | |
Maximum continuous operating voltage | max. 150 V AC/DC | |
Nominal discharge current (8/20 µs) | 2 kA | |
Max. surge current (8/20 µs) | 4 kA | |
Voltage protection level | max. 640 V (L-N) max. 800 V (L/N-PE) | |
Reaction time | max. 25 ns (L-N) max. 100 ns (L/N-PE) | |
Short-circuit-proof | 6 kA eff at max. mains-side overcurrent protection | |
Overcurrent protection | max. 25 A gL/gG (B 25 A) , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Operating conditions | ||
Installation conditions | ||
Mounting location | indoor | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 120 g | |
Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TN | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 2 | |
Suitable components | protection module M-LB-1.150.M | |
Electrical specifications | ||
Nominal voltage | 120 V AC | |
Maximum continuous operating voltage | max. 150 V AC | |
Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 15 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 240 g | |
Dimensions | 36 x 90 x 73 mm (1.4 x 3.6 x 2.9 inch) (2 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
Number of protected supply lines | 2 | |
Suitable components | protection module M-LB-2.255.T3.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 255 V AC | |
Temporary over-voltage | 335 V 335 V/5 s (TOV withstand) (L-N) 400 V/5 s (TOV withstand) (L/N-PE) 1200 V+Ucs/200 ms (TOV safe failure) (L+N-PE) 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 3 kA | |
Max. surge current (8/20 µs) | 5 kA | |
Voltage protection level | max. 1.25 kV (L-N) max. 1.5 kV (L/N-PE) | |
Reaction time | max. 25 ns (L-N) max. 100 ns (L/N-PE) | |
Short-circuit-proof | 6 kA eff at max. mains-side overcurrent protection | |
Overcurrent protection | max. 25 A gL/gG (B 25 A) , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Operating conditions | ||
Installation conditions | ||
Mounting location | indoor | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 120 g | |
Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TN | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 2 | |
Suitable components | protection module M-LB-1.275.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 275 V AC | |
Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 240 g | |
Dimensions | 36 x 90 x 73 mm (1.4 x 3.6 x 2.9 inch) (2 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TT | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 2 | |
Suitable components | protection module M-LB-1.275.M protection module M-LB-1.NPE.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC | |
Maximum continuous operating voltage | max. 275 V AC (L-N) max. 255 V AC (N-PE) | |
Temporary over-voltage | 335 V/5 s (TOV withstand) (L-N) 1200 V/200 ms (TOV withstand) (N-PE) | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Total discharge current (8/20 µs) | 12 kA (N-PE) | |
Voltage protection level | max. 1.25 kV (L-N) max. 1 kV at 5 kA (L-N) &le 1.5 kV (N-PE) | |
Reaction time | max. 25 ns (L-N) max. 100 ns (N-PE) | |
Follow current extinguishing capability | 100 A eff (N-PE) | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 240 g | |
Dimensions | 36 x 90 x 73 mm (1.4 x 3.6 x 2.9 inch) (2 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
General specifications | ||
---|---|---|
Device type | type 3 acc. to EN 61643-11:2013 class III acc. to IEC 61643-1:2011 | |
Number of protected supply lines | 2 | |
Suitable components | protection module M-LB-2.30.T3.M | |
Electrical specifications | ||
Nominal voltage | 24 V AC | |
Maximum continuous operating voltage | max. 30 V AC/DC | |
Nominal discharge current (8/20 µs) | 1 kA | |
Max. surge current (8/20 µs) | 2 kA | |
Voltage protection level | max. 180 V (L-N) max. 630 V (L/N-PE) | |
Reaction time | max. 25 ns (L-N) max. 100 ns (L/N-PE) | |
Short-circuit-proof | 6 kA eff at max. mains-side overcurrent protection | |
Overcurrent protection | max. 25 A gL/gG (B 25 A) , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529:2013 | |
Operating conditions | ||
Installation conditions | ||
Mounting location | indoor | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 120 g | |
Dimensions | 18 x 90 x 73 mm (0.7 x 3.6 x 2.9 inch) (1 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TN-C | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 3 | |
Suitable components | protection module M-LB-1.150.M | |
Electrical specifications | ||
Nominal voltage | 120 V AC / 240 V AC | |
Maximum continuous operating voltage | max. 150 V AC | |
Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 15 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 360 g | |
Dimensions | 54 x 90 x 73 mm (2.1 x 3.6 x 2.9 inch) (3 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TN-C | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 3 | |
Suitable components | protection module M-LB-1.275.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC / 400 V AC | |
Maximum continuous operating voltage | max. 275 V AC | |
Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 360 g | |
Dimensions | 54 x 90 x 73 mm (2.1 x 3.6 x 2.9 inch) (3 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TN-S | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 4 | |
Suitable components | protection module M-LB-1.150.M | |
Electrical specifications | ||
Nominal voltage | 120 V AC / 240 V AC | |
Maximum continuous operating voltage | max. 150 V AC | |
Temporary over-voltage | 175 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 15 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 0.7 kV max. 0.55 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 480 g | |
Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TN-S | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 4 | |
Suitable components | protection module M-LB-1.275.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC / 400 V AC | |
Maximum continuous operating voltage | max. 275 V AC | |
Temporary over-voltage | 335 V / 5 s (TOV withstand) | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Voltage protection level | max. 1.25 kV max. 1 kV at 5 kA | |
Reaction time | max. 25 ns | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 480 g | |
Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Search characteristics | ||
---|---|---|
Network | TT | |
General specifications | ||
Device type | type 2 acc. to EN 61643-11 class II acc. to IEC 61643-1 | |
Number of protected supply lines | 4 | |
Suitable components | protection module M-LB-1.275.M protection module M-LB-1.NPE.M | |
Electrical specifications | ||
Nominal voltage | 230 V AC / 400 V AC | |
Maximum continuous operating voltage | max. 275 V AC (L-N) max. 255 V AC (N-PE) | |
Temporary over-voltage | 335 V/5 s (TOV withstand) (L-N) 1200 V/200 ms (TOV withstand) (N-PE) | |
Nominal discharge current (8/20 µs) | 20 kA | |
Max. surge current (8/20 µs) | 40 kA | |
Total discharge current (8/20 µs) | 12 kA (N-PE) | |
Voltage protection level | max. 1.25 kV (L-N) max. 1 kV at 5 kA (L-N) &le 1.5 kV (N-PE) | |
Reaction time | max. 25 ns (L-N) max. 100 ns (N-PE) | |
Follow current extinguishing capability | 100 A eff (N-PE) | |
Short-circuit-proof | 50 kA eff | |
Overcurrent protection | max. 125 A gG , mains-side | |
Fault indication output | ||
Connection | terminals 11, 12, 14 | |
Output | volt-free change-over contact | |
Switch power | AC: 250 V / 0.5 A DC: 250 V/0.1 A 125 V/0.2 A 75 V/0.5 A 24 V/0.5 A | |
Indicators/settings | ||
Display elements | status display operating state (green) fault indication (red) | |
Directive conformity | ||
Low voltage | ||
Directive 2014/35/EU | EN 61643-11:2012 | |
Conformity | ||
Degree of protection | IEC 60529 | |
Ambient conditions | ||
Ambient temperature | -40 ... 80 °C (-40 ... 176 °F) | |
Mechanical specifications | ||
Degree of protection | IP20 | |
Core cross-section | - min. 1.5 mm2 solid/flexible - max. 35 mm2 stranded/25 mm2 flexible - max. 1.5 mm2 solid/flexible (for remote signalling contact) | |
Material | ||
Housing | thermoplastic, color grey , UL 94 V-0 | |
Mass | approx. 480 g | |
Dimensions | 72 x 90 x 73 mm (2.8 x 3.6 x 2.9 inch) (4 TE acc. to DIN 43880) | |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |